8. Electric Characteristics
Indoors power supply wiring
Indoor Units
Power Supply
Indoor fan motor
Power input(W)
Model
Hz
Voltage
Min. Max.
MCA
MFA
kW
FLA
Cooling
Heating
YKCA 18
YKCA 18
YKHA 18
YKCA 24
YKHA 24
YKCA 36
YKHA 36
YKCA 36
YKHA 36
YKCA 48
YKHA 48
(compact)
10.6
30
0.06
0.29
2050
YKHA 18 (compact)
10.6
30
0.06
0.29
2050
2100
12.4
30
0.10
0.35
2050
12.4
30
0.10
0.35
2050
2100
18.7
60
0.12
0.54
3000
18.7
60
0.12
0.54
3000
2950
26
80
0.14
0.62
4400
220-240
198
264
26
80
0.14
0.62
4400
4500
9.8
20
0.14
0.62
4400
9.8
20
0.14
0.62
4400
4500
11.5
30
0.14
0.62
5400
50
380
342
418
11.5
30
0.14
0.62
5400
5500
Symbols:
MCA: Min. Circuit Amps.
MFA: Max. Fuse Amps..
FLA: Full Load Amps.
Kw: Rate Motor Output
Notes:
5. Voltage range should not over the value of above table.
6. Maximum allowable voltage variation between phase is 2%
7. Selection wire size based on the larger value of MCA.
8. MCA/MFA
MCA = 1.25 × FLA
MFA
≤
4 × FLA
(Next lower standard fuse rating min. 15A)
5. Instead of fuse, circuit breaker is also acceptable.