6. Capacity Tables
Model: YKCA-YKHA 18 (compact)
COOLING
OUTDOOR TEMPERATURE DRY
Indoor
Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
Total capacity kW
5.12
4.90
4.72
4.45
4.27
4.14
Sensitive capacity kW
4.10
3.92
3.78
3.56
3.42
3.31
21ºC D
15ºC W
Input kW.
1.29
1.48
1.66
1.85
2.03
2.21
Total capacity kW
5.61
5.36
5.17
4.88
4.68
4.53
Sensitive capacity kW
4.49
4.29
4.13
3.90
3.74
3.63
24ºC D
17ºC W
Input kW.
1.36
1.56
1.75
1.95
2.14
2.34
Total capacity kW
6.10
5.83
5.62
5.30
5.09
4.93
Sensitive capacity kW
4.88
4.66
4.49
4.24
4.07
3.94
27ºC D
19ºC W
Input kW.
1.44
1.64
1.85
2.05
2.26
2.46
Total capacity kW
7.01
6.70
6.46
6.10
5.85
5.67
Sensitive capacity kW
5.61
5.36
5.17
4.88
4.68
4.53
32ºC D
23ºC W
Input kW.
1.65
1.89
2.12
2.36
2.59
2.83
Model: YKHA 18
(compact)
HEATING
OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
10.35
8.28
6.90
6.21
5.87
5.18
4.83
4.49
15ºC
Input kW.
3.54
2.83
2.36
2.24
2.12
2.00
1.89
1.65
Capacity kW
9.72
7.78
6.48
5.83
5.51
4.86
4.54
4.21
18ºC
Input kW.
3.32
2.66
2.21
2.10
1.99
1.88
1.77
1.55
Capacity kW
9.00
7.20
6.00
5.40
5.10
4.50
4.20
3.90
20ºC
Input kW.
3.08
2.46
2.05
1.95
1.85
1.74
1.64
1.44
Capacity kW
8.28
6.62
5.52
4.97
4.69
4.14
3.86
3.59
22ºC
Input kW.
2.83
2.26
1.89
1.79
1.70
1.60
1.51
1.32
Capacity kW
7.20
5.76
4.80
4.32
4.08
3.60
3.36
3.12
27ºC
Input kW.
2.46
1.97
1.64
1.56
1.48
1.39
1.31
1.15