INSTALLING THE DRAIN HOSE
Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) (outside diameter 38 mm)
During installation of the drain pipe, be careful to avoid applying pressure to the drain point of the unit.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate (8mm or over thick) the indoor side of the drain pipe.
BAD
Supporter
5 to 6.5 ft
(1.5 to 2m)
(1) Install insulation for the drain pipe
Insulation for Drain pipe
(To be obtained locally.
Length
should
be at least 8mm.)
Indoor unit (drain port)
Drain pipe insulation (accessories)
Drain pipe
Indoor unit
No gap
10mm or over
Drain pipe
Drain pipe insulation
2
1
Installation Procedure
GOOD
BAD
Cut the included insulation material to an appropriate size and adhere it to the pipe.
Indoor unit
(Rear view)
Cable VT
drain pipe
Fasten the drain pipe with cable VT so that there is a proper slope for drain pipe to
exit from the indoor unit.
(2) When drain pipe is put in the right rear position