INSTALLING THE INDOOR UNIT
Install the room air conditioner as follows
Connection pipe requirement
1. Remove the intake grill and side cover
(1) Remove the Air filters
(2) Remove the intake grilles
(3) Remove the Side cover (Right and left side)
(4) This air conditioner can be set up to intake fresh air.
The information about how to install for fresh-air intake, refer to
"Fresh air intake".
2. Location of ceiling supension bolts
For half-concealed installation
Supension-bolt pitch should be as shown below
Ceiling Opening:1530mm
40mm
40mm
Ceiling panel
Suspension bolt should
extend outward 30 to 50mm.
Ceiling Opening
640mm
Ceiling panel
15mm
Suspension bolt should
extend outward 30 to 50mm.
Suspension bolt pitch 1530mm
30mm
30mm
INDOOR UNIT (TOP VIEW)
Dimensions (Space Required for
installation)
10mm
155mm
300mm
Side cover A (Right side) Side cover A (Left side)
Intake grille
Air filter
19
Installation Procedure
Model
Diameter
Liquid side
Gas side
Maximum
length
Maximum height
(between indoor
and outdoor)
9.52 mm
19.05mm
50 m
30 m
36K
48K
55K