Fig. 3.3.9
Fig. 3.3.10
Fig. 3.3.8
Installation and Maintenance
14
Wall
Floor
Pattern board
Hanging plate
Hanging plate
fixing bolts(M8)
Hanging plate
screw (M5)
Ceiling
Hanging plate
2
5
m
m
o
r
m
o
re
4
5
m
m
o
r
le
s
s
Suspension bolt
·
·
Place the left hanger bracket on the nuts and
washers of the suspension bolts.
Make sure that the left hanger bracket has been
fixed on the nuts and washers securely, install the
right hanger bracket suspension hook on the nuts
and washers.
(When installing the indoor unit, you can slightly
remove the suspension bolts.)
(3) Fix with 4 suspension bolts, which can endure
load of 530N.
(4) Check the measurements of the length of the
suspension bolts.
(5) Fasten the hanging plate onto the suspension
bolts.
(6) Install the unit to the hanging plate.
i.Slide the unit from front side to get it hanged on the
hanging plate with bolts.
ii.Fasten the four fixing bolts (M8:2 each on the left
and right sides) firmly.
iii.Fasten the two screws (M5:1 each on the left and
right sides
).
Floor standing type installation
(1) Select the suspension bolt locations and the
tube hole location.
.Use enclosed paper pattern as a reference, and drill
the holes for the suspension bolts and tube.
Note:
Decide the locations based on the direct
measurements.
ii.After the locations are properly placed, the paper
pattern can be removed.
(2) Install the suspension bolts in place.
i
(3) Fix with 4 suspension bolts, and
fasten the four
fixing bolts (M8:2 each on the left and right sides)
firmly.
(4) Fasten the two screws of Air Intake Grille (M5:1
each on the left and right sides).
3.3.5 The horizontal adjustment of the indoor unit
(1) Make sure that the hanger bracket is fixed by the
nut and the washer.
(2) Adjust the height of the unit.
(
3
)
Check
if
the
unit
is
positioned
horizontally
.
*To ensure smooth drain flow, install the unit with a
descending slope (0-3mm) toward the drain outlet.
(4) After the adjustment, tighten the nut and smear the
thread locker on the suspension to prevent the nuts
from loosening.
During the installation, please cover the unit with the
plastic cloth to keep it clean.
CAUTION
AUV-18HR4SSA1
AUV-24HR4SFA1
AUV-36HR6SDB1
AUV-48HR6SEC1
AUV-60HR6SPC1
RPFC-2.0UNZ1NH
RPFC-3.0UNZ1NH
RPFC-4.0UNZ1NH
RPFC-6.0UNZ1NH
RPFC-6.5UNZ1NH
YFGN18BZNRZUH1
YFGN24BZNRZUH1
YFGN36BZMRZUH1
YFGN48BZMRZUH1
YFGN55BZMRZUH1
RAS-2.0UNZGNH1
RAS-3.0UNZGNH1
RAS-4.0UNZGMH1
RAS-6.0UNZGMH1
RAS-6.5UNZGMH1
●
Blowing out the surviwal heating air
When
stoping
the
air
conditioner
in
normal
operation
,
the
fan
motor
would
run
with
low
speed
for
a
while
to
blow
out
the
residual
heating
air
.