16
5. Drain Tubing
·
Install the drain tubing
·
Make sure the drain works properly.
The diameter of drain
connection hole should
·
tube
be same as that of the drain
.
tube
Keep the drain
short and sloping down wards at
·
tube
a gradient of at least 1/100 to prevent air pockets from
forming.
Refrigerant pipes
Drain pipe connection hole
(external straight pipe thread)
Water accumulating in the drain tubing can cause
the drain to clog.
Refrigerant
pipes
Bucket
Installation and Maintenance
CAUTION
CAUTION
·
To keep the drain tube from sagging, space hanging
wires every 1 to 1.5 m.
Use the drain hose and the clamp. Insert the drain
·
hose fully into the drain socket and firmly tighten the
drain hose and warm-keeping material with the clamp.
The two areas below should be insulated because
·
condensation may form there causing water to leak.
Drain
ing passing indoors
·
tub
Drain sockets.
·
Referring the figure below, insulate the drain socket
·
and drain hose using the included large sealing pad.
Drain hose
Sealing material
Sealing material
INDOOR
UNIT
INDOOR
UNIT
Drain tubing connections
Do not connect the drain directly to sewage tubes that
smell of ammonia. The ammonia in the sewage might
enter the indoor unit through the drain tubes and corrode
the heat exchanger.
Do not twist or bend the drain hose, so that excessive
force is not applied to it.
This type of treatment may cause leaking.
After tubing work is finished, check drainage flows
smoothly.
Gradually insert approximately 1000 cc of water into
the drain pan to check drainage in the manner described
below.
Gradually pour approximately 1000 cc of water from
the outlet hole into the drain pan to check drainage.
Check the drainage.
·
·
·
·
·
·
AUV-18HR4SSA1
AUV-24HR4SFA1
AUV-36HR6SDB1
AUV-48HR6SEC1
AUV-60HR6SPC1
RPFC-2.0UNZ1NH
RPFC-3.0UNZ1NH
RPFC-4.0UNZ1NH
RPFC-6.0UNZ1NH
RPFC-6.5UNZ1NH
YFGN18BZNRZUH1
YFGN24BZNRZUH1
YFGN36BZMRZUH1
YFGN48BZMRZUH1
YFGN55BZMRZUH1
RAS-2.0UNZGNH1
RAS-3.0UNZGNH1
RAS-4.0UNZGMH1
RAS-6.0UNZGMH1
RAS-6.5UNZGMH1
●