YORK VRF Air-Conditioner IOM

 

polythylene materials. 

z

Be sure to insulate the field piping all the way to 
the piping connection inside the unit. Any exposed 
piping may casue condensate water or being 
burned if touched. 

7

DRAIN PIPING WORK 

z

Drain pipe connection diameter may vary 
depending on different models. It can be divided as 
free drainage and pump drainage. So please 
confirm the model name and use the right method 
for that model. 

z

Be sure the drain pipe works well and smothly 
before making the duct connection. (It is not easy 
to check the drain pipe when the duct has been 
connected.)

7.1 Install the drain pipe 

z

Make sure the drain works properly. 

z

Diameter of the drain pipe should be larger than or 
equal to the one of the connecting pipe. (drain pipe 
connection diameter of indoor unit is 3/4” 
(19.05mm)) 

z

Make a water trap on the drain pipe outlet from 
indoor unit. The water trap should meet below 

requirements. (A, B 

ı

 50mm) 

Fig. 7 Water Trap 

 

z

If central drain pipe has been used, keep the drain 
pipe short and sloping downwards at a gradient of 
at least 2/100 to prevent air pockets from forming. 
(Refer to Fig. 8) 

 

z

Select central drain pipe of proper size according to 
the total capacity of the connected unit. 

 

>100mm                              Central drain pipe 

Fig. 8 Central Drain Pipe 

 

 

z

For the indoor unit with pump drainage   

(a) Be sure the drain raising pipe height is within 

700mm. 

(b) Place the drain raising pipe vertically and make 

sure it is no further than 300mm. (Refer to Fig. 
8) 

(c) The spare drain hole also needs to be 

thoroughly insulated to avoid accumulating of 
condensate water. 

 

Fig. 9 Pump Drainage 

z

To prevent the drain pipe from sagging, install 
hanging bracket every 1~1.5 m. 

z

When connecting the drain pipe, effective method 
should be carried out to guarantee no leakage on 
each connection area. 

z

To avoid condensate water accumulating on the 
drain pipe and dropping down, the drain pipe 
should be insulated.

7.2 Check the drain pipe 

z

After piping work is finished, check if drainage 
flows smoothly. 

(a)

Free drainage 

Gradually insert approximately 1000 ml clean 
water into the drain pan to check drainage 
status. 

 

(b)

Pump drainage 

Remove the lid of the control box. Connect 
the relevant power supply and ground lines, 
then close the lid. 
Gradually insert approximately 1000 ml clean 
water from the fin coil side. 
Power on the unit and inspect the drain 
pump working status. 

 

z

The electric wiring works should be performed by 
specially qualified electricians. 

z

If no electricians in site, please flow the above 
steps to do drainage confirmation after the system 
test running. 

8

INSTALLING THE DUCT 

z

Materials for duct installation are supplied in the 
field. 

z

Refer to Fig. 10 to connect the duct. 
 

NO

TE

CAUTION 

Summary of Contents for YDCC018-115

Page 1: ... YORKVRFAir Conditioner 250 12 YDCC IOM English YGF 0911 Installation Manual ...

Page 2: ...TY CONSIDERATIONS 2 BEFORE INSTALLATION 2 3 SELECTING INSTALLATION SITE 2 4 BEFORE INSTALLATION 3 5 INDOOR UNIT INSTALLTION 4 6 REFRIGERANT PIPING WORK 4 7 DRAIN PIPING WORK 6 8 INSTALLING THE DUCT 7 9 SET THE ESP 7 10 ELECTRIC WIRING WORK 7 ϭ ...

Page 3: ... the doors and windows immediately to ventilate the room thoroughly z Toxic gas may be produced if the refrigerant comes in contact with fire such as a fan heater stove or cooking device z Power off the unit before touching the electrical parts z Do not touch the switch with wet fingers Touching the switch with wet fingers may cause electric shock z Be sure the air conditioner is well grounded Nev...

Page 4: ...utdoor unit 3 SELECTING INSTALLATION SITE z If it has the possibility that the temperature and humidity inside the ceiling might exceed 30 C and RH80 please reinforce the insulation on the unit Use glass wool or polyethylene foam as insulation and its thickness is more than 10mm 3 1 INSTALLATION SITE REQUIREMENTS z The ceiling is strong enough to bear the indoor unit weight If not please reinforce...

Page 5: ... opening for repairing should be installed in the ceiling right below the unit The size should be no smaller than the unit diameter BhE shown in the Fig 2 YDCC06 45 YDCC018 112 Indoor Units Models A B C D E YDCC066 078 1205 1235 1450 1213 222 YDCC095 115 1505 1535 1780 1513 237 Note indoor unit series type of A B C and D is determined by the specific letter in the bar code on the unit For example ...

Page 6: ... installed within the hanger bracket for fear of bolt rolling out this may result in danger 6 REFRIGERANT PIPING WORK z Execute insulation completely on both sides of the gas piping and the liquid piping Otherwise water leakage can result sometimes Please use the insulation materials that can withstand temperature of at least 120 C Reinforce the insulation on the refrigerant piping according to th...

Page 7: ...frigerant piping and let the pressure slowly rise to 4 15MPa b The specified pressure should be maintained for 10 minutes and then soapy water or other foaming agent are applied to the connection positions such as brazing seams screwed joints etc for leakage detection c If it has leakage then tighten or braze the leakage point d After it has been confirmed that the piping does not leak the dwellin...

Page 8: ...8 Central Drain Pipe z For the indoor unit with pump drainage a Be sure the drain raising pipe height is within 700mm b Place the drain raising pipe vertically and make sure it is no further than 300mm Refer to Fig 8 c The spare drain hole also needs to be thoroughly insulated to avoid accumulating of condensate water Fig 9 Pump Drainage z To prevent the drain pipe from sagging install hanging bra...

Page 9: ...ording to the actual pressure drop of the air duct z Indoor unit ESP can be adjusted by changing the connection site of fan wiring in the control board For detail setting method of different indoor ESP please refer to the wiring diagram attached to the control box lid 10 ELECTRIC WIRING WORK 10 1 General introduction z Shut off the power before doing any work z All field supplied parts and materia...

Page 10: ... system while the other indoor units are controlled by another switch 10 4 Indoor unit field wiring z For detail indoor unit wiring see the Wring Diagram attached to the control box lid when laying the indoor unit electrical wiring 10 5 Setting indoor unit model z Refer to the Wring Diagram attached to the control box lid for indoor unit model setting 10 5 Communication network Note indoor unit co...

Page 11: ...roller can connect to max 4 indoor units Note indoor unit series type of A B C and D is determined by the specific letter in the bar code attached on the unit For example indoor unit YDCC C means C type series unit and YDCC B means B type z The indoor units in one group should be connected in a same power supply to guarantee normal initialization of wire controller when power on z Connection of in...

Page 12: ...721239 YDCC IOM English YGF 0911 NOTHING ...

Reviews: