FORM 150.63-EG1
NOTES:
1. SST = Saturated Suction Temperature
2. kW
o
= Unit kW Cooling Capacity Output
3. kW
i =
Compressors kW Input
4. COP = Coefficient of Performance (based on compressor and fan input kW)
YCUL0086EB
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C
30°C
35°C
40°C
45°C
50°C
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
2.0
269.6
72.4
3.4
255.0
80.5
2.9
240.0
89.4
2.5
224.8
99.2
2.1
174.4
85.6
1.9
135.1
74.1
1.7
3.0
279.2
73.0
3.5
264.2
81.1
3.0
248.7
90.1
2.6
233.0
99.9
2.2
181.0
86.2
2.0
140.3
74.6
1.7
4.0
289.0
73.7
3.6
273.5
81.8
3.1
257.6
90.8
2.6
241.4 100.7
2.2
187.8
86.7
2.0
145.6
75.0
1.8
5.0
299.0
74.4
3.7
283.1
82.5
3.2
266.7
91.6
2.7
250.0 101.6
2.3
194.8
87.3
2.1
151.1
75.5
1.8
6.0
309.3
75.0
3.8
292.9
83.2
3.3
276.0
92.4
2.8
258.8 102.4
2.4
202.0
87.9
2.1
156.4
76.2
1.9
7.0
319.9
75.8
3.9
302.8
84.0
3.3
285.5
93.2
2.9
267.8 103.3
2.4
174.2
69.2
2.3
162.2
76.6
1.9
8.0
330.6
76.5
4.0
313.0
84.8
3.4
295.2
94.1
2.9
277.1 104.2
2.5
180.5
69.6
2.4
168.2
77.1
2.0
9.0
341.5
77.3
4.1
323.5
85.7
3.5
305.1
94.9
3.0
286.4 105.2
2.6
187.0
70.0
2.4
174.4
77.5
2.1
10.0
352.7
78.2
4.2
334.2
86.5
3.6
315.3
95.8
3.1
296.0 106.2
2.6
193.7
70.4
2.5
180.7
78.0
2.1
11.0
364.2
79.0
4.2
345.1
87.4
3.7
325.6
96.8
3.1
256.4
82.6
2.9
200.5
70.9
2.6
187.2
78.5
2.2
12.0
375.8
79.9
4.3
356.2
88.3
3.7
336.2
97.8
3.2
265.1
83.3
2.9
207.5
71.4
2.7
193.8
79.0
2.3
YCUL0090EB
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C
30°C
35°C
40°C
45°C
50°C
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
2.0
292.1
79.9
3.4
276.6
88.9
2.9
260.7
98.7
2.5
244.5 109.6
2.1
158.6
73.7
2.0
147.4
81.8
1.7
3.0
302.2
80.8
3.5
286.4
89.7
3.0
270.0
99.6
2.5
253.2 110.5
2.2
164.5
74.1
2.0
152.9
82.2
1.7
4.0
312.7
81.5
3.5
296.4
90.5
3.1
279.4 100.5
2.6
262.1 111.4
2.2
170.6
74.5
2.1
158.6
82.8
1.8
5.0
323.4
82.3
3.6
306.5
91.3
3.1
289.1 101.4
2.7
271.2 112.4
2.3
176.9
75.0
2.2
164.5
83.2
1.8
6.0
334.4
83.1
3.7
317.0
92.1
3.2
298.9 102.3
2.7
280.5 113.4
2.3
183.3
75.4
2.2
170.5
83.7
1.9
7.0
345.5
83.9
3.8
327.4
93.1
3.3
309.0 103.2
2.8
290.0 114.5
2.4
189.8
75.9
2.3
176.7
84.2
1.9
8.0
356.9
84.7
3.9
338.2
94.1
3.4
319.3 104.2
2.9
299.7 115.5
2.5
196.5
76.4
2.4
183.0
84.7
2.0
9.0
368.5
85.6
4.0
349.2
95.0
3.4
329.7 105.2
2.9
309.5 116.6
2.5
203.4
76.9
2.4
189.5
85.2
2.1
10.0
380.3
86.5
4.1
360.5
96.0
3.5
340.4 106.3
3.0
319.7 117.7
2.6
210.4
77.4
2.5
196.1
85.8
2.1
11.0
392.3
87.4
4.2
371.9
97.0
3.6
351.1 107.5
3.1
330.0 118.9
2.6
217.6
77.9
2.6
203.0
86.3
2.2
12.0
404.5
88.4
4.3
383.6
98.0
3.7
362.2 108.6
3.1
239.8
70.7
3.1
225.0
78.4
2.6
209.9
86.9
2.2
YCUL0096EB
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C
30°C
35°C
40°C
45°C
50°C
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
2.0
282.1
71.9
3.4
267.8
79.1
3.0
252.8
87.1
2.6
236.9
96.4
2.2
221.8 105.8
1.9
203.5 118.0
1.6
3.0
292.8
72.4
3.5
278.1
79.6
3.1
262.6
87.7
2.7
246.2
96.9
2.3
230.5 106.4
2.0
211.7 118.6
1.6
4.0
303.9
73.0
3.6
288.7
80.2
3.2
272.8
88.3
2.8
255.8
97.5
2.4
239.4 107.0
2.0
220.2 119.1
1.7
5.0
315.1
73.5
3.7
299.5
80.8
3.3
283.0
88.9
2.8
265.7
98.1
2.4
247.1 108.6
2.1
228.8 119.7
1.8
6.0
326.6
74.1
3.9
310.5
81.5
3.4
293.6
89.6
2.9
275.7
98.7
2.5
257.9 108.5
2.2
237.7 120.4
1.8
7.0
338.4
74.8
4.0
321.8
82.2
3.5
304.4
90.3
3.0
286.0
99.4
2.6
267.6 109.2
2.2
246.9 121.0
1.9
8.0
350.3
75.5
4.1
333.3
82.9
3.6
315.4
91.0
3.1
296.5 100.1
2.7
276.4 110.5
2.3
255.1 122.5
1.9
9.0
362.5
76.2
4.2
345.1
83.6
3.7
326.7
91.8
3.2
307.2 100.9
2.8
286.6 111.3
2.4
264.7 123.2
2.0
10.0
375.1
76.8
4.3
357.1
84.4
3.8
338.2
92.6
3.3
318.2 101.7
2.8
297.1 112.1
2.4
274.7 123.9
2.0
11.0
388.0
77.5
4.4
369.3
85.2
3.9
349.9
93.4
3.4
329.4 102.5
2.9
307.8 112.9
2.5
212.1
87.0
2.2
12.0
401.1
78.3
4.5
381.9
86.0
4.0
362.0
94.2
3.5
340.9 103.4
3.0
318.7 113.7
2.6
220.1
87.4
2.2
YCUL0100EB
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C
30°C
35°C
40°C
45°C
50°C
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
KW
o
KW
i
COP
2.0
304.9
79.0
3.4
290.0
86.8
3.0
274.6
95.2
2.6
258.2 104.7
2.2
240.6 115.5
1.9
221.6 127.9
1.6
3.0
316.3
79.7
3.5
300.9
87.5
3.1
284.8
96.0
2.7
268.0 105.5
2.3
250.0 116.2
2.0
230.4 128.5
1.7
4.0
328.0
80.4
3.6
312.0
88.2
3.2
295.5
96.8
2.8
278.1 106.3
2.4
259.5 117.0
2.0
239.5 129.2
1.7
5.0
339.9
81.0
3.7
323.3
89.0
3.2
306.3
97.6
2.8
288.3 107.1
2.5
269.3 117.8
2.1
248.8 129.9
1.8
6.0
352.1
81.7
3.8
334.9
89.8
3.3
317.3
98.4
2.9
298.8 108.0
2.5
279.2 118.7
2.2
258.2 130.7
1.8
7.0
364.5
82.4
3.9
346.8
90.6
3.4
328.6
99.3
3.0
309.6 108.9
2.6
289.4 119.6
2.2
267.9 131.6
1.9
8.0
377.0
83.3
4.0
359.0
91.4
3.5
340.2 100.2
3.1
320.6 109.8
2.7
299.9 120.5
2.3
277.8 132.5
1.9
9.0
390.1
84.0
4.1
371.5
92.2
3.6
352.1 101.0
3.2
331.8 110.7
2.7
310.5 121.5
2.4
288.0 133.4
2.0
10.0
403.4
84.7
4.2
384.0
93.1
3.7
364.1 102.0
3.2
343.4 111.7
2.8
321.5 122.4
2.4
298.3 134.3
2.1
11.0
417.1
85.4
4.3
397.0
93.9
3.8
376.6 102.9
3.3
355.1 112.7
2.9
332.7 123.4
2.5
163.5
60.0
2.3
12.0
431.1
86.1
4.5
410.3
94.8
3.9
389.3 103.8
3.4
367.2 113.6
3.0
344.1 124.4
2.5
169.5
60.3
2.4