FORM 150.63-EG1
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1
COMPR. #2
COMPR. #3
FANS
RLA
LRA
RLA
LRA
RLA
LRA
QTY
FLA(EA)
100.2
550
100.2
550
—
—
3
8.2
92.8
550
92.8
550
—
—
3
7.8
53.5
305
53.5
305
—
—
3
4.8
44.2
270
44.2
270
—
—
3
4.0
35.4
210
35.4
210
—
—
3
3.1
100.2
550
100.2
550
—
—
3
8.2
92.8
550
92.8
550
—
—
3
7.8
53.5
305
53.5
305
—
—
3
4.8
44.2
270
44.2
270
—
—
3
4.0
35.4
210
35.4
210
—
—
3
3.1
73.9
450
73.9
450
73.9
450
4
8.2
68.5
450
68.5
450
68.5
450
4
7.8
39.5
260
39.5
260
39.5
260
4
4.8
32.6
215
32.6
215
32.6
215
4
4.0
26.1
180
26.1
180
26.1
180
4
3.1
73.9
450
73.9
450
73.9
450
4
8.2
68.5
450
68.5
450
68.5
450
4
7.8
39.5
260
39.5
260
39.5
260
4
4.8
32.6
215
32.6
215
32.6
215
4
4.0
26.1
180
26.1
180
26.1
180
4
3.1
100.2
550
100.2
550
100.2
550
4
8.2
92.8
550
92.8
550
92.8
550
4
7.8
53.5
305
53.5
305
53.5
305
4
4.8
44.2
270
44.2
270
44.2
270
4
4.0
35.4
210
35.4
210
35.4
210
4
3.1
SYSTEM #2 COMPRESSOR & FAN
COMPR. #1
COMPR. #2
COMPR. #3
FANS
RLA
LRA
RLA
LRA
RLA
LRA
QTY
FLA(EA)
73.9
450
73.9
450
—
—
3
8.2
68.5
450
68.5
450
—
—
3
7.8
39.5
260
39.5
260
—
—
3
4.8
32.6
215
32.6
215
—
—
3
4.0
26.1
180
26.1
180
—
—
3
3.1
100.2
550
100.2
550
—
—
3
8.2
92.8
550
92.8
550
—
—
3
7.8
53.5
305
53.5
305
—
—
3
4.8
44.2
270
44.2
270
—
—
3
4.0
35.4
210
35.4
210
—
—
3
3.1
100.2
550
100.2
550
—
—
4
8.2
92.8
550
92.8
550
—
—
4
7.8
53.5
305
53.5
305
—
—
4
4.8
44.2
270
44.2
270
—
—
4
4.0
35.4
210
35.4
210
—
—
4
3.1
73.9
450
73.9
450
73.9
450
4
8.2
68.5
450
68.5
450
68.5
450
4
7.8
39.5
260
39.5
260
39.5
260
4
4.8
32.6
215
32.6
215
32.6
215
4
4.0
26.1
180
26.1
180
26.1
180
4
3.1
73.9
450
73.9
450
73.9
450
4
8.2
68.5
450
68.5
450
68.5
450
4
7.8
39.5
260
39.5
260
39.5
260
4
4.8
32.6
215
32.6
215
32.6
215
4
4.0
26.1
180
26.1
180
26.1
180
4
3.1
YCUL0096 - YCUL0130
MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)
(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect
Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)