JOHNSON CONTROLS
62
FORM 201.23-EG2 (713)
Electrical Data - 3 Comp High Efficiency
See page 64 for Electrical Data footnotes.
MODEL NO./NAMEPLATE
SYSTEM 1
SYSTEM 2
SYSTEM 2
SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
YCIV E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CON-
DENSER
FANS
COMP.
CON-
DENSER
FANS
COMP.
CONDENSER
FANS
RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA)
RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA) RLA (5)
QTY. FLA (EA)
1050
400
50
170
5
3.1
170
5
9.3
180
5
3.8
170
5
3.1
170
5
9.3
180
5
3.8
126
4
3.1
126
4
9.3
132
4
3.8
1120
400
50
164
5
3.1
164
5
9.3
173
5
3.8
164
5
3.1
164
5
9.3
173
5
3.8
164
5
3.1
164
5
9.3
173
5
3.8
1220
400
50
183
5
3.1
183
5
9.3
194
5
3.8
183
5
3.1
183
5
9.3
194
5
3.8
169
6
3.1
169
6
9.3
178
6
3.8
1380
400
50
218
6
3.1
218
6
9.3
229
6
3.8
218
6
3.1
218
6
9.3
229
6
3.8
167
6
3.1
167
6
9.3
175
6
3.8
YCIV S/P
CONTROL
KVA (7)
UNIT SHORT CIRCUIT
WITHSTAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
FIELD WIRING LUGS
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/HIGH STATIC
FANS
HIGH HEAD/HIGH STATIC
FANS
TWO-SPEED COND. FANS
STD TERMINAL BLOCK
OPT CIRCUIT BREAKER
TERMINAL
BLOCK
(STD)
CIRCUIT
BREAKER
(OPT)
MINIMUM
CKT. AMPAC-
ITY (MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX. IN
-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
MINIMUM
CKT. AMPAC-
ITY (MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX.
INVERSE
TIME CKT.
BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
MINIMUM
CKT.
AMPACITY
(MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX. IN
-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
LUGS/
PHASE
(1)
LUG WIRE
RANGE
LUGS/
PHASE
(1)
LUG WIRE
RANGE
1070
2.4
30KA
65KA
552
600
700
700
639
700
800
800
590
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
1180
2.4
30KA
65KA
580
700
700
700
673
800
800
800
621
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
1340
2.4
30KA
65KA
631
700
800
800
730
800
800
800
676
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
1500
2.4
30KA
65KA
713
800
800
800
824
1000
1000
1000
760
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
Summary of Contents for YCIV
Page 27: ...JOHNSON CONTROLS FORM 201 23 EG2 713 27...
Page 29: ...JOHNSON CONTROLS FORM 201 23 EG2 713 29...
Page 31: ...JOHNSON CONTROLS FORM 201 23 EG2 713 31...
Page 33: ...JOHNSON CONTROLS FORM 201 23 EG2 713 33...
Page 35: ...JOHNSON CONTROLS FORM 201 23 EG2 713 35...
Page 37: ...JOHNSON CONTROLS FORM 201 23 EG2 713 37...
Page 39: ...JOHNSON CONTROLS FORM 201 23 EG2 713 39...
Page 41: ...JOHNSON CONTROLS FORM 201 23 EG2 713 41...
Page 43: ...JOHNSON CONTROLS FORM 201 23 EG2 713 43...
Page 45: ...JOHNSON CONTROLS FORM 201 23 EG2 713 45...
Page 47: ...JOHNSON CONTROLS FORM 201 23 EG2 713 47...
Page 55: ...JOHNSON CONTROLS FORM 201 23 EG2 713 55 INTENTIONALLY LEFT BLANK...
Page 68: ...JOHNSON CONTROLS 68 FORM 201 23 EG2 713 Typical Control Wiring Two Compressor...
Page 70: ...JOHNSON CONTROLS 70 FORM 201 23 EG2 713 Typical Control Wiring Three Compressor...
Page 72: ...JOHNSON CONTROLS 72 FORM 201 23 EG2 713 Typical Control Wiring Four Compressor...