YORK INTERNATIONAL
30
(YCHA100)
LWT COOLING RANGES
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.0°F
Setpoint plus 0.5°F
SWITCH = 0
Loader Stage 3
Setpoint plus 0.5°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.5°F
OF + 1.0°F
Compressor Stage 1
Setpoint minus 0.5°F
Setpoint minus 1.0°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.2°F
Setpoint plus 0.6°F
SWITCH = 1
Loader Stage 3
Setpoint plus 0.6°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.6°F
OF + 1.2°F
Compressor Stage 1
Setpoint minus 0.6°F
Setpoint minus 1.2°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.4°F
Setpoint plus 0.7°F
SWITCH = 2
Loader Stage 3
Setpoint plus 0.7°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.7°F
OF + 1.4°F
Compressor Stage 1
Setpoint minus 0.7°F
Setpoint minus 1.4°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.5°F
Setpoint plus 0.8°F
SWITCH = 3
Loader Stage 3
Setpoint plus 0.7°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.8°F
OF + 1.5°F
Compressor Stage 1
Setpoint minus 0.7°F
Setpoint minus 1.5°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.6°F
Setpoint plus 0.8°F
SWITCH = 4
Loader Stage 3
Setpoint plus 0.8°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.8°F
OF + 1.6°F
Compressor Stage 1
Setpoint minus 0.8°F
Setpoint minus 1.6°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.8°F
Setpoint plus 0.9°F
SWITCH = 5
Loader Stage 3
Setpoint plus 0.9°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 0.9°F
OF + 1.8° F
Compressor Stage 1
Setpoint minus 0.9°F
Setpoint minus 1.8°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 1.9°F
Setpoint plus 1.1°F
SWITCH = 6
Loader Stage 3
Setpoint plus 1.1°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 1.1°F
OF + 1.9°F
Compressor Stage 1
Setpoint minus 1.0°F
Setpoint minus 1.9°F
STAGE
ON
OFF
COOLING RANGE
Loader Stage 4
Setpoint plus 2.0°F
Setpoint plus 1.0°F
SWITCH = 7
Loader Stage 3
Setpoint plus 1.0°F
Setpoint
COOLING RANGE
Loader Stage 2
Setpoint
Setpoint minus 1.0°F
OF + 2.0°F
Compressor Stage 1
Setpoint minus 1.0°F
Setpoint minus 2.0°F
Summary of Contents for YCAQ10
Page 20: ...YORK INTERNATIONAL 20 LD01779 YCHA100 FIG 9 WIRING DIAGRAM YCHA100...
Page 21: ...FORM 150 40 NM20 21 YORK INTERNATIONAL YCHA100 LD01779 D...
Page 22: ...YORK INTERNATIONAL 22 LD01780 L YCHA100 FIG 9 Continued...
Page 23: ...FORM 150 40 NM20 23 YORK INTERNATIONAL LD01780 R YCHA100...
Page 24: ...YORK INTERNATIONAL 24 YCHA100 LD01781 FIG 9 Continued...
Page 25: ...FORM 150 40 NM20 25 YORK INTERNATIONAL LD01782 YCHA100...
Page 46: ...YORK INTERNATIONAL 46 LD01787...
Page 47: ...FORM 150 40 NM20 47 YORK INTERNATIONAL LD01788...
Page 48: ...YORK INTERNATIONAL 48 LD01789...
Page 49: ...FORM 150 40 NM20 49 YORK INTERNATIONAL LD01790...
Page 50: ...YORK INTERNATIONAL 50 LD01791...
Page 51: ...FORM 150 40 NM20 51 YORK INTERNATIONAL LD01792...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......