SECTION 7 - UNIT CONTROlS
S Y S 1 S P = 7 2 . 1 P S I G
D P = 2 2 7 . 0 P S I G
These displays show suction and discharge pressures
for each system. The discharge pressure transducer is
optional on some models.
If the
optional
discharge transducer is not installed, the
discharge pressure would display 0 psig (0 barg).
Some models come factory wired with a low pressure
switch in place of the suction transducer. In this case,
the suction pressure would only be displayed as the
maximum suction pressure reading of >200 psig (13.79
barg) when closed, or < 0 psig (0 barg) when open.
The minimum limits for the display are:
• Suction Pressure: 0 psig (0 barg)
• Discharge Pressure: 0 psig (0 barg)
The maximum limits for the display are:
• Suction Pressure: 200 psig (13.79 barg)
• Discharge Pressure: 400 psig (27.58 barg)
These messages will be displayed for each system, if an
EEV is installed in the system. The EEV % is the EEV
controller output.
Cooler inlet temperatures, as measured by the refrigerant
temperature sensor in the cooler, will be displayed on
R-407c units for both systems.
The above two messages will appear sequentially for
each system. The first display shows accumulated
running hours of each compressor for the specific
system. The second message shows the number of starts
for each compressor on each system.
Run times and starts will only be
displayed for the actual number of
systems and compressors on the unit.
A total of 99,999 hours and starts can be logged before
the counter rolls over to “0”.
This display of the load and unload timers indicate
the time in seconds until the unit can load or unload.
Whether the systems loads or unloads is determined by
how far the actual liquid temperature is from setpoint.
A detailed description of unit loading and unloading is
covered under the topic of Capacity Control.
The display of COOLING DEMAND indicates the
current “step” in the capacity control scheme when in
Return Water Control Mode. The number of available
steps are determined by how many compressors are in
the unit. In the above display, the “2” does not mean
that two compressor are running but only indicates that
the capacity control scheme is on step 2 of 8. Capacity
Control is covered in more detail in this publication
which provides specific information on compressor
staging (for Return Water Control only).
The COOLING DEMAND message will be replaced
with this message when Leaving Chilled liquid control
is selected. This message indicates the temperature
error and the rate of change of the chilled liquid
temperature.
S Y S 1 S U C T = X X X . X ° F
S A T S U C T = X X X . X ° F
S Y S 1 E E V = X X X . X %
S U C T S H E A T = X X X . X ° F
S Y S 1 H O U R S 1 = X X X X X
2 = X X X X X, 3 = X X X X X
C O O L I N G D E M A N D
2 O F 8 S T E P S
L O A D T I M E R 5 8 S E C
U N L O A D T I M E R 0 S E C
S Y S 1 S T A R T S 1 = X X X X X
2 = X X X X X, 3 = X X X X X
S Y S 1 C O O L E R I N L E T
R E F R I G T E M P = X X X . X ° F
T E M P E R R O R X X X . X ° F
T E M P R A T E X X X . X ° F / M
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...