FORM 150.66-NM2
ISSUE DATE: 09/25/2020
101
JOHNSON CONTROLS
SECTION 7 - UNIT CONTROlS
7
“STATUS” KEY
UNIT STATUS
Pressing the STATUS key will enable the operator to
determine current chiller operating status. The messages
displayed will include running status, cooling demand,
fault status, external cycling device status. The display
will be a single message relating to the highest priority
message as determined by the micro. Status messages
fall into the categories of General Status and Fault
Status.
The following General, Safety, and Warning messages
are displayed when the Status key is pressed. Following
each displayed message is an explanation pertaining to
that particular message.
GENERAL STATUS MESSAGES
In the case of messages which apply to individual
systems, SYS 1 and SYS 2 messages will both be
displayed and may be different. In the case of single
system units, all SYS 2 messages will be blank.
This message informs the operator that the UNIT switch
on the control panel is in the OFF position which will
not allow the unit to run.
The REMOTE CONTROLLED SHUTDOWN message
indicates that either an ISN system or RCC has turned
the unit “OFF”, not allowing it to run.
The DAILY SCHEDULE SHUTDOWN message
indicates that the daily/holiday schedule programmed
is keeping the unit from running.
NO RUN PERM shows that either the flow switch is
open or a remote start/stop contact is open in series
with the flow switch. A 3-second delay is built into the
software to prevent nuisance shutdowns due to erroneous
signals on the run permissive input.
SYS SWITCH OFF tells that the system switch under
OPTIONS is turned “OFF”. The system will not be
allowed to run until the switch is turned back on.
U N I T S W I T C H O F F
S H
U T D
O
W
N
R E M O T E C O N T R O L L E D
S H
U T D
O
W
N
D A I L Y S C H E D U L E
S H
U T D
O
W
N
F L O W S W I T C H / R E M S T O P
N O R U N P E R M
00066VIP
S Y S 1 S Y S S W I T C H O F F
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...