YORK INTERNATIONAL
65
FORM 150.40-NM25
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.2°F (.66°C)
Setpoint plus 0.6°F (.33°C)
Lag Compressor (Stage 1)
Setpoint plus 0.6°F (.33°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 0.6°F (.33°C)
Lead Compressor (Stage 1)
Setpoint minus 0.6°F (.33°C)
Setpoint minus 1.2°F (.66°C)
COOLING RANGE
SWITCH = 1
COOLING RANGE
OF
±
1.2°F (
±
.66°C)
DUAL CIRCUIT UNITS
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.4°F (.77°C)
Setpoint plus 0.7°F (.38°C)
Lag Compressor (Stage 1)
Setpoint plus 0.7°F (.38°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 0.7°F (.38°C)
Lead Compressor (Stage 1)
Setpoint minus 0.7°F (.38°C)
Setpoint minus 1.4°F (.77°C)
COOLING RANGE
SWITCH = 2
COOLING RANGE
OF
±
1.4°F (
±
.78°C)
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.5°F (.83°C)
Setpoint plus 0.8°F (.44°C)
Lag Compressor (Stage 1)
Setpoint plus 0.7°F (.38°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 0.8°F (.44°C)
Lead Compressor (Stage 1)
Setpoint minus 0.7°F (.38°C)
Setpoint minus 1.5°F (.83°C)
COOLING RANGE
SWITCH = 3
COOLING RANGE
OF
±
1.5°F (
±
.83°C)
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.6°F (.88°C)
Setpoint plus 0.8°F (.44°C)
Lag Compressor (Stage 1)
Setpoint plus 0.8°F (.44°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 0.8°F (.44°C)
Lead Compressor (Stage 1)
Setpoint minus 0.8°F (.444°C)
Setpoint minus 1.6°F (.88°C)
COOLING RANGE
SWITCH = 4
COOLING RANGE
OF
±
1.6°F (
±
.88°C)
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.8°F (.99°C)
Setpoint plus 0.9°F (.49°C)
Lag Compressor (Stage 1)
Setpoint plus 0.9°F (.49°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 0.9°F (.49°C)
Lead Compressor (Stage 1)
Setpoint minus 0.9°F (.49°C)
Setpoint minus 1.8°F (.99°C)
COOLING RANGE
SWITCH = 5
COOLING RANGE
OF
±
1.8°F (
±
.99°C)
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 1.9°F (1.05°C)
Setpoint plus 1.1°F (.61°C)
Lag Compressor (Stage 1)
Setpoint plus 1.1°F (.61°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 1.1°F (.61°C)
Lead Compressor (Stage 1)
Setpoint minus 1.0°F (.55°C)
Setpoint minus 1.9°F (1.05°C)
COOLING RANGE
SWITCH = 6
COOLING RANGE
OF
±
1.9°F (
±
1.05°C)
STAGE
ON
OFF
Lag Compr. Loader Stage 2
Setpoint plus 2.0°F (1.11°C)
Setpoint plus 1.0°F (.55°C)
Lag Compressor (Stage 1)
Setpoint plus 1.0°F (.55°C)
Setpoint
Lead Compr. Loader Stage 2
Setpoint
Setpoint minus 1.0°F (.55°C)
Lead Compressor (Stage 1)
Setpoint minus 1.0°F (.55°C)
Setpoint minus 2.0°F (1.11°C)
COOLING RANGE
SWITCH = 7
COOLING RANGE
OF
±
2.0°F (
±
1.11°C)