FORM 160.60-O2 (1004)
15
YORK INTERNATIONAL
DISPLAY
Return Condenser Water Temperature
Displays the temperature of the cooling water returning
to the condenser
Leaving Condenser Water Temperature
Displays the temperature of the cooling water leaving
the condenser
Condenser Refrigerant Temperature
Displays the temperature of the condenser refrigerant
Subcooled Drop Leg Temperature
Displays the temperature of the refrigerant in the drop
leg of the subcooler
Condenser Small Temperature
Difference
Displays the temperature expressed as the differential
between the water entering and the water leaving the
condenser
Condenser Pressure
Displays the current operating pressure of the
condenser
Subcooler Level (Graphical)
Displays the level of refrigerant inside the subcooler
OVA Output
Displays the status of the subcooler level control valve
from fully open to fully closed in percent
Condenser High Pressure Cutout
Indicates the status of the high pressure cutout switch
INTERACTIVE
(F3) Subcooler Level Setpoint
Allows the operator to adjust the subcooler refrigerant
level setpoint
CONDENSER SCREEN
LD09882
FIG. 8 - CONDENSER SCREEN