GENERAL

This completely assembled blower unit is manufactured under
ISO 9002 Quality System Certification and includes a well-
insulated cabinet, a DX cooling coil with copper tubes and alu-
minum fins, an expansion valve, a distributor, throwaway fil-
ters, a centrifugal blower, a blower motor, a blower motor
contactor, an adjustable belt drive and a small holding charge
of Refrigerant-22.

The unit is shipped in the vertical position with a vertical air dis-
charge. The blower section can be repositioned as shown in Fig-
ure1 for horizontal applications.

REFERENCE

This instruction covers the installation of the evaporator blower
unit. For information on the installation and operation of the
matching condensing unit refer to Form 035-17263-000.

Additional information for the accessories on this equipment is
available in the following instructions:

Electric Heater - 550.13-N10.1V

Supply Air Plenum - 550.13-N10.2V

Return Air Grille - 550.13-N10.3V

Base - 550.13-N10.4V

Hot Water & Steam Coil - 550.13-N10.7V

Suspension Mounting - 550.13-N7.1

Renewal Parts:

Refer to Parts Manual for complete listing of replacement
parts on this equipment.

All forms may be ordered from:

Standard Register
2101 West Tecumseh Road
Norman, OK 73069

INSPECTION

As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's delivery receipt. A
separate request for inspection by the carrier's agent should
be made in writing. See Local Distributor for additional infor-
mation.

Installer should pay particular attention to the words: NOTE, CAU-
TION 
and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment dam-
age. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not

MODEL K3EU180A50

(WORLD 50 HZ)

® 

INSTALLATION INSTRUCTION

SUNLINE™ SPLIT-SYSTEM

EVAPORATOR BLOWER

(AIR COOLED)

Supersedes:  550.39-N5YI (894)

035-12124-000 Rev. A (0501)

CAUTION

THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE

LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED

TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.

THIS PRO DUCT M UST BE INSTALLED IN STRICT COMPLIANCE W ITH

WARNING

OPERATION OF THE  PRODUCT COULD CAUSE  PERSONAL  INJURY

O R   P R O P E R T Y   D A M A G E .

INCORRECT INSTALLATION MAY CREATE A CONDITION W HERE THE

Voltage Code

Refrigerant Line Connections

Nominal Cooling Capacity

K

180 A 50

3 EU

Product Category

Product Generation

Product  Identifier

K = Split-System Evaporator Blower

1,2,3 = Design Level

EU = Evaporator Blower Unit

180 = 180Mbh (52.7kW)

A = Cooling Only

50 = 380/415-3-50

NOMENCLATURE

Summary of Contents for WORLD 50 HZ K3EU180A50

Page 1: ...n as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate request for...

Page 2: ...the skid These units can be rigged with slings under the bottom skid CAUTION Spreader bars should be used to prevent slings from crushing the unit panels and frame Before rigging any unit determine i...

Page 3: ...n Pack fiber glass insulation and a sealing material such as Per magum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility Support all refrigerant l...

Page 4: ...the refrigerant connections The line should be in sulated where moisture drippage will be objectionable or cause damage to the area Seal the unused drain connec tion with a suitable mastic The 3 76mm...

Page 5: ...dry coil the refrigerant system should be de energized while the test is being run 4 Knowing the pressure drop across a dry coil the actual air flow through the unit can be determined from the curve i...

Page 6: ...2 2 20 2 68 404 2 46 2 99 311 2 73 1 Unit resistance is based on a wet evaporator coil and clean filters 2 Available static pressure in IWG Pa to overcome the resistance of the duct system and any acc...

Page 7: ...tom 4 NOTES 1 Overall dimension of the unit will vary if an electric heater a supply air plenum or a base is used 2 This dimension is required for removal of the DX coil Only 26 660mm is required for...

Page 8: ...terminals on blower motor contactor 10M Route the control wires into the unit through the other 7 8 22 2mm dia knockout and connect them to the terminals on block 4TB Refer to the unit drawing in Figu...