LIMITATIONS

These units must be installed in accordance with applicable na-
tional, local and municipal safety codes.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's ex-
pense. Refer to Table 2 for Unit Application Data.

LOCATION

This blower unit is not designed for outdoor installation. It must
be located within the building structure, either inside or outside
the conditioned space.

The unit should be located as close to the condensing unit as
practical and positioned to minimize bends in the refrigerant
piping.

Units being installed vertically or horizontally can be set directly
on a floor or platform, or they can be supported by metal or
wooden beams.

Units being installed horizontally can also be suspended from
above. Refer to the suspension accessory instruction installa-
tion procedures.

CLEARANCES

The clearances listed on the unit dimension drawing (Figure 7)
are required for the proper service and operation of the unit.

RIGGING AND HANDLING

Be careful when moving the unit. Do not remove any packaging
until the unit is near its final location.

The packaging consists of a bottom wooden skid that can be
lifted with a fork truck from any direction, a clear heavy mil bag
that covers the entire unit, and strapping that secures the clear
bag to the bottom of the skid.

These units can be rigged with slings under the bottom skid.

CAUTION: Spreader bars should be used to prevent slings

from crushing the unit panels and frame.

Before rigging any unit, determine its weight from Table 1. Bef-
ore rigging a unit for horizontal installation, make sure that its
weight will be distributed equally.

2

Unitary Products Group

035-12124-000 Rev. A (0501)I

Evaporator Coil

Rows Deep

4

Rows High

26

Finned Length (in./mm)

54.5/1384

Fin/Inch

13

Tube O.D. (in./mm)

3/8/9.6

Face Area (Ft

.2

/m

2

)

12.4/1.15

Centrifugal
Blower

1

Wheel Dia. x Width

inches

18 x 18

mm

457 x 457

Filters

2

(6 Req'd)

Size

inches

20 x 20 x1

mm

508 x 508

x 25

Face Area (Ft.

2

/m

2

)

16.7/1.5

Operating Charge ( Refrigerant 22) (Lbs/Kg)

5.5/2.5

Weight (Lbs/Kg)

Shipping

480/218

Operating

440/200

Accessory
Weights(Lbs/Kg)

Electric Heaters

10 kW

63/28.5

16 kW

66/29.9

26 kW

71/32.2

36 kW

74/33.5

Supply Air Plenum

144/65

Base

65/29

Return Air Grille

19/9

Horizontal Suspension

68/31

Steam Coil

149/68

Hot Water Coil

135/61

1

Refer to data in Table 7 for complete motor specifications.

2

Filters are throwaway type. Two inch (50mm) filters may be used, if required by
removing the 1" (25mm) filter retaining angles provided in the filter rack.

Table 1 - PHYSICAL DATA

Power
Supply

Voltage

Variation*

Supply Air Range

CFM/m

3

s

Entering Air Temperature, °F(°C)

Cooling-db/wb

Heating-db

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

380/415-3-50

342

457

4800/2.26

7200/3.40

68/57 (20/14)

86/72 (30/22)

-

77 (25)

TABLE 2 - UNIT APPLICATION DATA

*Utilization Range “A”  in accordance with ARI Standard 110.

INSTALLATION

Summary of Contents for WORLD 50 HZ K3EU180A50

Page 1: ...n as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate request for...

Page 2: ...the skid These units can be rigged with slings under the bottom skid CAUTION Spreader bars should be used to prevent slings from crushing the unit panels and frame Before rigging any unit determine i...

Page 3: ...n Pack fiber glass insulation and a sealing material such as Per magum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility Support all refrigerant l...

Page 4: ...the refrigerant connections The line should be in sulated where moisture drippage will be objectionable or cause damage to the area Seal the unused drain connec tion with a suitable mastic The 3 76mm...

Page 5: ...dry coil the refrigerant system should be de energized while the test is being run 4 Knowing the pressure drop across a dry coil the actual air flow through the unit can be determined from the curve i...

Page 6: ...2 2 20 2 68 404 2 46 2 99 311 2 73 1 Unit resistance is based on a wet evaporator coil and clean filters 2 Available static pressure in IWG Pa to overcome the resistance of the duct system and any acc...

Page 7: ...tom 4 NOTES 1 Overall dimension of the unit will vary if an electric heater a supply air plenum or a base is used 2 This dimension is required for removal of the DX coil Only 26 660mm is required for...

Page 8: ...terminals on blower motor contactor 10M Route the control wires into the unit through the other 7 8 22 2mm dia knockout and connect them to the terminals on block 4TB Refer to the unit drawing in Figu...

Reviews: