Integrity of the unit structure and components
Check:
• The correct condition of the unit structure and exterior components.
• No knocks or dents.
• correct fixture of bolts.
• The correct closure of access doors, including the condition of the sealing strip and locks.
Hot water coil
Where the unit is fitted with this accessory, check the following at the start of the heating season:
• The control elements.
• System water filling.
• Bleeding of air from the coil.
N O T E
Check that the proportion of antifreeze is correct, if necessary, depending on the area and the installation.
1.14 Unit sound power level indication (Lw in dB A)
Outdoor units
VCH models
Octave band sound
spectrum
dB(A), indoor
20A
25A
30A
40A
45A
60A
75A
90A
125 Hz
65
65,2
75,1
75,4
77,7
78,1
79,8
79,8
250 Hz
66,2
66,5
75,7
75,9
79,1
80,5
81,7
81,7
500 Hz
70,6
70,7
79,1
79,3
78,7
79
79,9
80
1000 Hz
73,9
74,1
82,2
82,4
81,8
82,2
83,1
83,2
2000 Hz
71
71,2
81,6
81,9
80,2
80,6
81,6
81,6
4000 Hz
68,2
68,4
76,6
76,8
76,3
76,3
77,1
77
8000 Hz
59,6
59,9
69,2
69,5
68,6
68,9
69,8
69,8
Sound power level
dB (A)
77,8
78
87
87,3
87,5
88
88,8
88,8
Indoor units
VIR Models
Octave band sound
spectrum dB(A)
25A
40A
45A
60A
75A
90A
125 Hz
63,7
68,6
73,9
75,5
67
68,6
250 Hz
63,7
70,1
73,5
75,1
70
71,6
500 Hz
69,8
73,8
74,5
76,1
73,8
75,4
1000 Hz
70,6
74,8
77,2
78,8
74
75,6
2000 Hz
68,7
75,1
77,1
78,7
74,6
76,2
4000 Hz
64,9
70,5
72,5
74,1
73,7
75,3
8000 Hz
55,8
62,3
655
66,6
67,5
69,1
Sound power level dB
(A)
75,4
81,3
82,7
84,3
81,5
83,5
Installation manual
1
Unit sound power level indication (Lw in dB A) 1.14
45