(10) Wired Controller Connections.
When the wired controller or receiver kit is used, the setting
of SW2 is required.
Wired
Wireless
SW2
DIP Switch PCB
Change to “Wired” .
(c) Wired Controller connections between different refrigerant cycles
(a) Wired Controller at each unit for an individual operation setting
(b) Single Wired Controller for an individual operation setting
Outdoor Unit
A B
Outdoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
A B
A B
A B
Individual
Simultaneous
(Thermo ON / OFF individually)
Individual
Wired
Controller
Wired
Controller
Wired
Controller
Indoor Unit
Indoor Unit
A B
Outdoor Unit
A B
Wired
Controller
Wired
Controller
Outdoor Unit
Indoor Unit
A B
Communication cables
for the wired controller
are necessary.
Indoor Unit
A B
Wired
Controller
1. The DIP switch settings for the outdoor unit should be performed in accordance with the "Installation and
Maintenance Manual" for the outdoor unit.
2. Be aware that communication cable for the wired controller is required in these instances:
a The following functions are set to the sub unit which is not installed with the wired controller.
•
Remote ON/OFF function settings, (No.1, 2, and 3), (External Input / Output Function)
•
Power supply ON/OFF functions, (No.1 and 2), (Function Selection)
•
Prohibiting the wired controller after manual stoppage (External Input / Output Function)
•
Group setting by the centralized controller
b The address for the indoor unit is changed from the wired controller.