P5417052
17
NOTE:
If left side piping access is selected, the condensate pipe outlet should be left side and the mounting plate
downslope should be adjusted to left side. It does not change the mounting plate downslope to the left
side.
(2) Determine the direction for the piping connection according to the layout for the site of installation as
shown below.
(3) Secure the securing plate for pipes (accessory) as
shown in the figure at right. (only for 006 to 012 Type)
Unit: inch (mm)
Model
a
b
c
f
d
TIWM006B21S
TIWM008B21S
1-3/4
(45)
25-1/8
(638)
4-3/16
(107)
2-9/16
(65)
TIWM012B21S
1-3/4
(45)
25-7/8
(657)
4-3/16
(107)
2-9/16
(65)
TIWM015B21S
TIWM018B21S
TIWM024B21S
TIWM030B21S
1-5/8
(42)
37-7/16
(951)
5-9/16
(141)
3-1/8
(80)
• For the pipe installation embedded in the wall, the positions for piping are as follows.
• For Left Side Piping
With the appropriate cutting tool, remove the left-side "knock-out" panel and smooth away any sharp
edges. Do this before the unit is mounted onto the wall.
Left Side Cover
Cutter for Plastic
Cut this portion.
Rear Side Piping
Left Side Piping
Left Side of Indoor Unit
Right Side of Indoor Unit
Refrigerant and Condensate
Pipe Connection
Exterior Contour for Indoor Unit
a
φ
d
b
c
φ
d
Refrigerant and Condensate Pipe Connection
a
Securing Plate
Catches
Secure the securing plate onto
upper and lower catches.