![background image](http://html2.mh-extra.com/html/york/tiwm006b21s/tiwm006b21s_engineering-manual_4192547012.webp)
WALL MOUNT
2-2
TC-17006-rev.1
2.3 General Data
Indoor Unit Type
Wall Mount
Model
TIWM008B21S
TIWM012B21S
Indoor Unit Power Supply
AC 1Phase, 208/230V, 60Hz
Nominal Cooling Capacity
1
Btu/h
(kW)
Nominal Heating Capacity
1
Btu/h
(kW)
dB
Outer Dimensions
Height
in. (mm)
11-13/16 (300)
11-13/16 (300)
11-13/16 (300)
13-1/8 (333)
Width
in. (mm)
31-1/8 (790)
31-1/8 (790)
35-7/16 (900)
45-1/4 (1150)
Depth
in. (mm)
9-1/16 (230)
9-1/16 (230)
9-1/16 (230)
9-5/8 (245)
Net Weight
lbs. (kg)
22 (10)
22 (10)
24 (11)
35 (16)
Refrigerant
R410A
Indoor Fan
Airflow Rate
cfm
(Hi2-Hi-Me-Lo)
(m
3
/min.)
External Pressure
in.W.G
(Pa)
Motor Nominal Output
W
Connections
Refrigerant Piping
Flare-Nut Connection (with Flare Nuts)
Liquid Line
in. (mm)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
Gas Line
in. (mm)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
Condensate Drain
OD
in. (mm)
7/8 (22)
7/8 (22)
7/8 (22)
7/8 (22)
ID
in. (mm)
5/8 (16)
5/8 (16)
5/8 (16)
5/8 (16)
Indoor Unit Type
Wall Mount
Model
Indoor Unit Power Supply
AC 1Phase, 208/230V, 60Hz
Nominal Cooling Capacity
1
Btu/h
(kW)
Nominal Heating Capacity
1
Btu/h
(kW)
dB
Outer Dimensions
Height
in. (mm)
13-1/8 (333)
13-1/8 (333)
13-1/8 (333)
Width
in. (mm)
45-1/4 (1150)
45-1/4 (1150)
45-1/4 (1150)
Depth
in. (mm)
9-5/8 (245)
9-5/8 (245)
9-5/8 (245)
Net Weight
lbs. (kg)
37 (17)
37 (17)
37 (17)
Refrigerant
R410A
Indoor Fan
Airflow Rate
cfm
(Hi2-Hi-Me-Lo)
(m
3
/min.)
External Pressure
in.W.G
(Pa)
Motor Nominal Output
W
Connections
Refrigerant Piping
Flare-Nut Connection (with Flare Nuts)
Liquid Line
in. (mm)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Gas Line
in. (mm)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
Condensate Drain
OD
in. (mm)
7/8 (22)
7/8 (22)
7/8 (22)
ID
in. (mm)
5/8 (16)
5/8 (16)
5/8 (16)
VP16
VP16
(5.8)
20,000
(5.3)
49-43-40-36
VP16
38
(0)
0.0
(19-17-14-12)
671-600-494-424
0.0
39-35-32-30
353-282-247-229
34,000
30,000
24,000
TIWM030B21S
TIWM024B21S
12,000
(3.5)
13,500
(2.3)
(10-8-7-6.5)
494-388-318-265
46-40-36-33
(14-11-9-7.5)
(4.0)
VP16
(0)
38
VP16
VP16
VP16
15,000
(0)
(10-8-7-6.5)
8,000
6,000
(1.8)
6,700
(2.0)
39-35-32-30
Sound Pressure Level
2
(Overall A Scale)
(Hi2-Hi-Me-Lo)
TIWM006B21S
9,000
(2.6)
38
0.0
(0)
38
0.0
353-282-247-229
(0)
38
38
38
(15-14-13-10)
(22-19-17-15)
(22-19-17-15)
0.0
0.0
0.0
777-671-600-530
(0)
777-671-600-530
(4.4)
(7.0)
(8.8)
17,000
27,000
42-40-38-33
51-49-46-41
51-49-46-41
(5.0)
(7.9)
(10.0)
TIWM015B21S
Sound Pressure Level
2
(Overall A Scale)
(Hi2-Hi-Me-Lo)
(0)
530-494-459-353
18,000
TIWM018B21S
1. Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Heating Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB)
Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
67°F WB (19.4°C WB)
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)
43°F WB (6.1°C WB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0ft. (0m)
2. Sound pressure level is based on following conditions.
3.3 ft. (1m) Front of the Unit and 3.3 ft. (1m) Below the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.