66396-YIM-C-1004
18
Unitary Products Group
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 7: VOLTAGE LIMITATIONS
POWER SUPPLY
VOLTAGE
MIN.
MAX.
380/415-3-50
342
456
TABLE 8: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW
2
STAGES
AMPS
BQ240
380
9.6
66
2.1
11.7
0.0
-
0.0
-
-
57.2
60
E18
11.3
1
17.1
78.7
80
E36
22.6
2
34.3
78.7
80
E54
33.8
2
51.4
78.8
80
E72
45.1
2
68.6
100.3
110
415
9.6
66
2.1
11.7
0.0
-
0.0
-
-
57.2
60
E18
13.5
1
18.7
80.7
90
E36
26.9
2
37.4
80.7
90
E54
40.4
2
56.2
84.9
90
E72
53.8
2
74.9
104.0
110
TABLE 9: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW
2
STAGES
AMPS
BQ240
380
9.6
66
2.1
11.7
6.3
-
0.0
-
-
63.5
70
E18
11.3
1
17.1
85.0
90
E36
22.6
2
34.3
85.0
90
E54
33.8
2
51.4
86.7
90
E72
45.1
2
68.6
108.2
110
415
9.6
66
2.1
11.7
6.3
-
0.0
-
-
63.5
70
E18
13.5
1
18.7
87.0
90
E36
26.9
2
37.4
87.0
90
E54
40.4
2
56.2
92.8
100
E72
53.8
2
74.9
110.3
125
TABLE 10: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
KW CAP. MULTIPLIER
380
380
0.627
415
415
0.75