background image

254595-YTG-C-0308

32

Johnson Controls Unitary Products

used in the furnace compartment and be fastened with ridged 
fasteners to prevent insulation from entering the air stream. 
Cabinet panels shall be “large” size, easily removable for ser-
vicing and maintenance. Full perimeter base rails shall be 
provided to assure reliable transit of equipment, overhead rig-
ging and proper sealing on roof curb applications. Disposable 
1" filters shall be furnished and be accessible through a 
removable access door, sealed airtight. Units filter track shall 
be designed to accommodate either 1” or 2” filters. Fan per-
formance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be direct drive, multi-speed, or a factory 
installed belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected (B.H.P.) brake horsepower 
shall not exceed the motors nameplate horsepower rating, 
plus the service factor. Units shall be designed not to operate 
above service factor. Fan wheel shall be double-inlet type 
with forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 
internally enhanced copper tubes with all joints 
brazed. Special Phenolic coating shall be available 
as a factory option.

b.

Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design.  

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a.

Independent fixed-orifice expansion devices.

b.

Filter drier/strainer to eliminate any moisture or for-
eign matter.

c.

Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary 
servicing or troubleshooting without losing charge.

d.

The refrigeration system shall provide at least 15°F 
of sub-cooling at design conditions.

UNIT CONTROLS

a.

Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit 
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or 
base unit, should any of the following standard 
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

d.

High-pressure switch.

e.

Freeze-protection thermostat, evaporator coil. 

f.

If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.

g.

Unit shall incorporate “AUTO RESET” compressor 
over temperature, over current protection.

h.

Unit shall operate with conventional thermostat 
designs and have a low voltage terminal strip for 
easy hook-up.

i.

Unit control board shall have on-board diagnostics 
and fault code display.

j.

Standard controls shall include anti-short cycle and 
low voltage protection, and permit cooling operation 
down to 0°F.

k.

Control board shall monitor each refrigerant safety 
switch independently.

l.

Control board shall retain last 5 fault codes in non 
volatile memory, which will not be lost in the event of 
a power loss.

ELECTRIC HEATING SECTION

An electric heating section, with nickel chromium elements, 
shall be provided in a range of 5 thru 30 KW, offering two 
stages of capacity - 16 KW and above on 208/230 volt heat-
ers and 20 KW and above on 460 and 575 volt heaters. The 
heating section shall have a primary limit control(s) and auto-
matic reset to prevent the heating element system from oper-
ating at an excessive temperature. The heating section 
assembly shall slide out of the unit for easy maintenance and 

Summary of Contents for Sunline 2000 BQ 036

Page 1: ...er Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Direct Drive or Belt Drive Blower with high static drive option Bottom or side air discharge configuration capability field convertible Manufactured under the quality standards of ISO9001 Simplicity Control Board Copper tube aluminum fin coils Easy access to all components Rigging holes in base rails ...

Page 2: ...E BQ048 BELT DRIVE BOTTOM DUCT APPLICATION 13 11 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE SIDE DUCT APPLICATION 14 12 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE BOTTOM DUCT APPLICATION 14 13 SUPPLY AIR BLOWER PERFORMANCE BQ036 048 060 DIRECT DRIVE SIDE DUCT APPLICATION 14 14 SUPPLY AIR BLOWER PERFORMANCE BQ036 048 060 DIRECT DRIVE BOTTOM DUCT APPLICATION 15 15 BELT DRIVE RPM SELECTION 15...

Page 3: ...quested or an order placed CPC Controller DFS APS Johnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w ModLinc 2 Pleated Filters BAS Ready Economizer 2 10 V D C Actuator without a Controller Any Combination of Additional Options that Don t Have an Option Code Pre assigned AA None Standard Cabine...

Page 4: ...le minimum run times For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of one another All units are programmed with default values based upon their configuration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezest...

Page 5: ...ration at excessive temperatures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed 2 pleated filters are offered as a factory installed option CONVENIENCE OUTLET This 110 volt outlet can be powered by the unit with a stepdown transformer or the unit may be ordered with a non powered convenience outlet that can be wired in the field DISCONNECT SWITCH For heat pump units ...

Page 6: ...TC Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Honeywell W7750C building automation system controller is factory installed Includes air supply sensor return air sensor dirty filter indicator switch and air proving switch SMOKE DETECTORS supply...

Page 7: ...ation NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports POWER EXHAUST Our single input economizer options are available with power exhaust Whenever the outdoor air intake dampers are opened for free cooling the exhaust fan will be energized to prevent the condi tioned...

Page 8: ... 84 74 67 69 62 57 52 74 41 048 1 600 0 55 HIGH 0 80 85 85 75 68 70 63 58 53 75 42 060 2 000 0 45 HIGH 1 00 86 86 76 69 71 64 59 54 76 43 1 These values have been accessed using a model of sound propagation from a point source into the hemispheric free field The dBA values provided are to be used for reference only Calculation of dBA values cover matters of system design and the fan manufacture ha...

Page 9: ... 30 28 25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 30 26 23 19 16 12 34 4 1 30 27 24 21 17 15 11 62 33 3 9 33 32 31 28 24 21 18 32 4 1 32 31 30 27 24 20 17 57 32 3 8 32 32 31 28 24 21 18 32 4 0 32 32 31 28 24 21 18 72 41 4 0 27 23 20 17 13 37 4 2 24 2...

Page 10: ...0 62 42 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36 32 28 23 19 62 41 4 5 41 41 40 35 32 27 23 37 4 7 37 37 36 33 28 24 19 57 41 4 4 41 41 41 36 32 28 23 37 4 7 37 37 37 34 28 25 20 72 47 4 7 32 28 24 20 44 5 0 31 27 23 19 67 42 4 5 38 36 32 28 24 20...

Page 11: ...6 62 53 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45 42 36 31 26 62 52 5 8 52 52 51 46 40 35 30 48 6 4 48 48 46 42 36 31 25 57 52 5 7 52 52 51 46 40 36 31 47 6 4 47 47 46 43 36 32 25 72 60 5 9 41 37 32 27 56 6 7 40 35 30 25 67 55 5 8 48 46 41 36 31 26...

Page 12: ...3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8 4 4 6 5 2 MBH 10 7 15 19 5 24 5 30 5 37 4 45 3 51 8 KW 3 5 3 6 3 8 3 9 4 4 2 4 8 5 4 MBH 10 9 15 3 19 9 24 9 31 7 38 9 47 53 8 KW 3 1 3 2 3 3 3 4 3 5 3 7 4 2 4 8 MBH 10 5 14 7 19 1 24 30 5 37 4 45 2 ...

Page 13: ...27 1489 1 37 Field Supplied Drive TABLE 9 SUPPLY AIR BLOWER PERFORMANCE BQ048 BELT DRIVE SIDE DUCT APPLICATION Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes 1 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 932 0 2 0 4 0 6...

Page 14: ...Supplied Drive Standard Drive Option HIgh Static Drive Option 1200 663 0 48 773 0 53 875 0 59 969 0 65 1056 0 72 1138 0 80 1214 0 88 1286 0 96 1354 1 04 1420 1 13 1400 692 0 57 802 0 61 904 0 67 998 0 73 1085 0 80 1167 0 88 1243 0 96 1315 1 04 1383 1 13 1449 1 21 1600 726 0 67 836 0 72 938 0 78 1032 0 84 1119 0 91 1201 0 98 1277 1 06 1349 1 15 1417 1 23 1483 1 32 1800 766 0 80 876 0 85 977 0 90 10...

Page 15: ...n Fully Closed 036 3 1 5 1 73 1VL44 AK64 805 865 920 980 1035 1095 1 5 1 73 1VP56 AK66 1115 1170 1225 1280 1335 1390 048 4 1 5 1 73 1VL44 AK56 930 995 1060 1130 1195 1260 1 5 1 73 1VP56 AK61 1210 1270 1330 1390 1455 1515 060 5 1 5 1 73 1VL44 AK56 930 995 1060 1130 1195 1260 2 2 3 1VP56 AK56 1325 1395 1460 1525 1590 1660 TABLE 16 BELT DRIVE BLOWER MOTOR AND DRIVE DATA Size Tons Motor Motor Sheave B...

Page 16: ... HP motor is required 6 1150 RPM is within the range of the 30 40 HP drives but step 5 requires the 40 HP motor 7 Using the 40 HP motor and drive 5 5 turns open will achieve 1150 RPM Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 3 0 3 4 3 8 4 2 4 6 5 0 5 4 5 8 6 2 6 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 30 HP F...

Page 17: ...848 0 817 0 787 0 758 0 730 0 703 0 676 0 651 0 600 0 650 0 700 0 750 0 800 0 850 0 900 0 950 1 000 1 050 1 100 40 50 60 70 80 90 100 Air Temperature ºF Correction Factor Sea Level 1000 ft 2000 ft 3000 ft 4000 ft 6000 ft 7000 ft 8000 ft 9000 ft 10000 ft 5000 ft TABLE 18 ELECTRIC HEATER CFM LIMITATIONS UNIT MODEL SIZE NOMINAL TONS VOLTAGE MINIMUM SUPPLY AIR CFM HEATER SIZE NOMINAL KW 5 7 10 15 20 3...

Page 18: ...7 35 E05 4 0 1 11 1 39 6 50 E07 5 6 1 15 5 45 1 50 E10 8 0 1 22 2 53 4 60 E15 11 9 2 33 0 67 0 70 E20 15 9 2 44 1 80 8 90 230 3 60 14 7 130 0 23 0 2 3 5 0 0 0 None 25 7 35 E05 5 3 1 13 3 41 6 50 E07 7 5 1 18 8 48 2 50 E10 10 6 1 26 6 57 5 60 E15 15 9 2 39 9 73 5 80 E20 21 2 2 53 2 89 4 90 460 3 60 7 7 64 0 12 0 1 3 2 2 0 0 None 13 1 20 E07 6 8 1 8 5 23 3 25 E10 10 1 1 12 7 28 3 30 E15 13 6 2 17 1 ...

Page 19: ... 35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E07 7 5 1 18 8 48 4 50 E10 10 6 1 26 6 57 7 60 E15 15 9 2 39 9 73 7 80 E20 21 2 2 53 2 89 6 90 460 3 60 7 7 64 0 12 0 1 3 2 6 0 0 None 13 5 20 E07 6 8 1 8 5 23 7 25 E10 10 1 1 12 7 28 7 30 E15 13 6 2 17 1 3...

Page 20: ...e 25 9 35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E07 7 5 1 18 8 48 4 50 E10 10 6 1 26 6 57 7 60 E15 15 9 2 39 9 73 7 80 E20 21 2 2 53 2 89 6 90 460 3 60 7 7 64 0 12 0 1 3 2 6 0 0 None 13 5 20 E07 6 8 1 8 5 23 7 25 E10 10 1 1 12 7 28 7 30 E15 13 6 2 ...

Page 21: ...45 E05 4 0 1 11 1 49 6 60 E07 5 6 1 15 5 55 1 60 E10 8 0 1 22 2 63 4 70 E15 11 9 2 33 0 77 0 80 E20 15 9 2 44 1 90 8 100 230 3 60 14 7 130 0 23 0 2 3 5 0 10 0 None 35 7 45 E05 5 3 1 13 3 51 6 60 E07 7 5 1 18 8 58 2 60 E10 10 6 1 26 6 67 5 70 E15 15 9 2 39 9 83 5 90 E20 21 2 2 53 2 99 4 100 460 3 60 7 7 64 0 12 0 1 3 2 2 5 0 None 18 1 25 E07 6 8 1 8 5 28 3 30 E10 10 1 1 12 7 33 3 35 E15 13 6 2 17 1...

Page 22: ...0 E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E07 7 5 1 18 8 58 4 60 E10 10 6 1 26 6 67 7 70 E15 15 9 2 39 9 83 7 90 E20 21 2 2 53 2 99 6 100 460 3 60 7 7 64 0 12 0 1 3 2 6 5 0 None 18 5 25 E07 6 8 1 8 5 28 7 30 E10 10 1 1 12 7 33 7 35 E15 13 6 2 17 1 ...

Page 23: ...35 9 50 E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E07 7 5 1 18 8 58 4 60 E10 10 6 1 26 6 67 7 70 E15 15 9 2 39 9 83 7 90 E20 21 2 2 53 2 99 6 100 460 3 60 7 7 64 0 12 0 1 3 2 6 5 0 None 18 5 25 E07 6 8 1 8 5 28 7 30 E10 10 1 1 12 7 33 7 35 E15 13 6 2...

Page 24: ...1 2 1 2 Nom CFM 4300 4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2 1 1 1 Total Face Area sq ft 6 6 6 6 6 6 CHARGE Refrigerant 22 lbs oz 7 12 9 2 8 4 TABLE 26 ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAG...

Page 25: ...SFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER 3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT 4 COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE REMOVE JUMPER J2 FROM TERMINALS...

Page 26: ...254595 YTG C 0308 26 Johnson Controls Unitary Products FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A ...

Page 27: ...254595 YTG C 0308 Johnson Controls Unitary Products 27 FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW ...

Page 28: ... 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 29 MINIMUM CLEARANCES LOCATION CLEARANCE Front 24 Cooling Electric Heat 32 Gas Heat Rear 12 Less Economizer 36 With Economizer or Fixed Air Motorized Damper Left Side Filter Access 24 Less Economizer 36 With Economizer Righ...

Page 29: ...254595 YTG C 0308 Johnson Controls Unitary Products 29 FIGURE 8 TYPICAL APPLICATIONS ...

Page 30: ...OTAL A B C D BQ036 628 139 137 174 177 BQ048 668 148 146 185 189 BQ060 693 154 151 192 196 TABLE 31 BQ 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BQ036 628 93 92 91 116 117 119 BQ048 668 99 98 97 123 125 126 BQ060 693 103 102 100 128 129 131 TABLE 32 CENTER OF GRAVITY DIMENSION 3 5 TON X 40 Y 19 TABLE 33 OPERATING WEIGHTS LBS MODEL SIZE 3 TON 4 TON 5 TON BASIC UNIT BQ 628 668 693 OPT...

Page 31: ...sure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compressor lockout circuit a terminal strip for thermostat wiring plus an additional set of pin connectors to simplify the interface of additional field controls All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTMB117 pr...

Page 32: ...dent mounting Coils a Evaporator and condenser coils shall have alumi num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed Special Phenolic coating shall be available as a factory option b Evaporator and Condenser coils shall be of the direct expansion draw thru design Refrigerant Circuit and Refrigerant Safety Components shall include a Independen...

Page 33: ...essor to economizer oper ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module The out door intake opening shall be covered with a rain hood that matches the exterior of the unit Water eliminator fil ters shall be provided Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss MOTORIZED OUTDOOR AIR ...

Page 34: ...10 V D C ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION 2 PLEATED FILTERS DISCONNECT SWITCH SUPPLY AIR SMOKE DETECTOR RETURN AIR SMOKE DETECTOR HIGH STATIC DRIVE OPTION May include a belt blower pulley motor pulley or a motor change to enhance blower performance ...

Page 35: ...254595 YTG C 0308 Johnson Controls Unitary Products 35 ...

Page 36: ... change without notice Printed in U S A 254595 YTG C 0308 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 254595 YTG B 0507 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Reviews: