background image

(1) -- Loss--of--charge/Low--pressure switch.

(2) -- High--pressure switch.

If any of the above safety devices trip, an LED (light emitting
diode) indicator shall illuminate.

C. Unit shall incorporate “AUTO RESET” compressor

over--temperature, over--current protection.

D. Unit shall operate with conventional thermostat designs

and have a low voltage terminal strip for easy hook--up.

E. Unit shall have freeze--protection thermostat on evapo-

rator coil.

F. Unit shall incorporate an ambient compensated, time

and temperature defrost control.

(1) -- Defrost shall be initiated on the basis of time and liq-
uid line temperature.

(2) -- A 50/80/110--minute timer shall activate defrost cycle
only if liquid line temperature is low enough to indicate a
heavy frost condition.

(3) -- Defrost cycle shall terminate when liquid line sensor
is satisfied and shall have a positive termination time of 10
minutes.

ELECTRIC HEATING SECTION

1. An electric heating section, with nickel chromium ele-

ments, shall be provided in a range of 5 thru 30 KW, of-
fering two stages of capacity -- 16 KW and above on
208/230 volt heaters and 20 KW and above on 460 and
575 volt heaters.

2. The heating section shall have a primary limit control(s)

and automatic reset, to prevent the heating element sys-
tem from operating at an excessive temperature.

3. The Heating Section assembly shall slide out of the unit

for easy maintenance and service.

4. Units with Electric Heating Sections shall be wired for a

single point power supply with branch circuit fusing
(where required).

UNIT OPERATING CHARACTERISTICS

1. Unit shall be capable of starting and cooling at 125° F

outdoor temperature, exceeding maximum load criteria of
ARI Standard 210/240.

2. The compressor, with standard controls, shall be capable

of cooling down to 45° F outdoor temperature.

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.

STANDARD LIMITED WARRANTIES

Compressor-- 5 Years

Elect. Heat. Elem.-- 5 Years

Parts -- 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):

1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-

MIZER -- Outdoor and return air dampers that are inter-
locked and positioned by a fully--modulating, spring--
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit--mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed--air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer op-
eration shall be provided by an integral electronic en-
thalpy control that feeds input into the basic module. The
outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.

2. DUAL INPUT DIFFERENTIAL ELECTRONIC

ENTHALPY AUTOMATIC ECONOMIZER -- Outdoor and
return air dampers that are interlocked and positioned by
a fully--modulating, spring--return damper actuator. The
maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer
operation, a mixed--air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer
operation shall be provided by two integral electronic
enthalpy controls -- one that senses outdoor air and one
that senses indoor air. Both enthalpy sensors supply
input to the logic module which modulates both sets of
dampers for maximum economizer savings. The outdoor
intake opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided. Simultaneous economizer/compressor
operation is also possible. Dampers shall fully close on
power loss.

OTHER PRE--ENGINEERED ACCESSORIES AVAILABLE

1. ROOF CURB -- 14" AND 8" high, full perimeter knock-

down curb with hinged design for quick assembly.

2. MANUAL OUTDOOR DAMPER -- Provides 0% through

35% or 0% through 100% outdoor air capability (field ad-
justable). Designed for duct mounted side supply/return
applications. Includes a hood and a screen assembly.

3. OUTDOOR COIL GUARD -- Prevents coil damage.

4. BAROMETRIC RELIEF DAMPER -- Contains a rain

hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.

5. BURGLAR BARS -- Designed to work with above

roofcurbs. Fits duct openings of curb supply and return
air openings.

036-21564-003-A-1005

Unitary Products Group

21

Summary of Contents for SUNLINE 2000 2000

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...r to gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove a...

Page 17: ...TY CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 1...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 003 A 1005 Unitary Products Group 23...

Page 24: ...8QLWDU 3URGXFWV URXS RUN ULYH 1RUPDQ 2 6XEMHFW WR FKDQJH ZLWKRXW QRWLFH 3ULQWHG LQ 8 6 RS ULJKW E RUN QWHUQDWLRQDO RUSRUDWLRQ OO 5LJKWV 5HVHUYHG 6XSHUVHGHV...

Reviews: