Unitary Products Group

COOLING CAPACITIES

-

3 TON (BCH036)

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

85

°

F

95

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1750

72

51

3.4

37

32

28

24

19

-

-

47

3.7

34

29

25

22

17

-

-

67

46

3.4

40

40

36

31

26

21

16

44

3.7

38

38

34

29

24

20

15

62

42

3.3

42

42

41

39

34

29

24

38

3.6

38

38

37

35

30

26

21

57

42

3.3

42

42

42

40

35

30

25

37

3.6

37

37

37

35

30

26

22

1500

72

49

3.4

35

30

26

22

18

-

-

46

3.7

32

28

24

20

16

-

-

67

45

3.4

39

37

33

29

24

20

15

42

3.7

36

34

30

27

22

18

14

62

41

3.3

41

41

40

37

32

28

24

37

3.6

37

37

36

33

28

25

21

57

41

3.3

41

41

41

38

34

29

25

36

3.6

36

36

36

33

29

25

21

1400

72

48

3.4

33

29

24

20

16

-

-

45

3.7

30

27

22

18

15

-

-

67

44

3.3

39

36

32

28

23

20

15

41

3.7

36

33

29

26

21

18

13

62

40

3.3

40

39

38

34

30

26

22

36

3.6

36

35

34

30

27

23

19

57

40

3.3

40

40

39

35

31

27

23

36

3.5

36

36

35

31

27

24

20

1200

72

47

3.4

31

27

24

20

16

-

-

44

3.7

29

25

22

18

14

-

-

67

41

3.3

36

32

29

25

22

18

14

39

3.6

34

30

27

23

20

17

13

62

38

3.3

38

37

36

32

29

25

21

35

3.6

35

34

33

29

26

23

19

57

37

3.3

37

37

36

33

30

26

22

35

3.5

35

35

34

31

28

24

20

1050

72

45

3.3

28

25

22

19

16

-

-

42

3.6

26

23

20

17

14

-

-

67

41

3.3

34

30

27

24

20

17

14

38

3.6

31

27

25

22

18

15

12

62

36

3.3

36

35

33

30

27

24

21

34

3.5

34

33

31

28

25

22

19

57

36

3.3

36

36

34

31

28

25

22

33

3.5

33

33

31

28

25

22

20

900

72

45

3.3

26

24

20

17

15

-

-

40

3.6

23

21

17

15

13

-

-

67

39

3.3

31

28

25

22

19

17

14

35

3.6

27

25

22

19

17

15

12

62

35

3.2

35

34

32

29

25

23

20

32

3.5

32

30

28

25

22

20

17

57

35

3.2

35

35

32

30

26

24

21

31

3.5

31

31

28

26

23

21

18

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

105

°

F

115

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

1

, MBH

CFM

WB

°

F

Entering Dry Bulb,

°

F

Entering Dry Bulb,

°

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

1750

72

44

4.0

31

27

24

20

16

-

-

42

4.2

30

26

23

19

15

-

-

67

40

4.0

34

34

31

26

22

18

13

36

4.1

31

31

28

24

20

16

12

62

35

3.9

35

35

34

32

28

24

20

34

4.1

34

34

33

31

27

23

19

57

35

3.9

35

35

35

33

29

25

20

33

4.1

33

33

33

31

27

23

19

1500

72

43

4.0

30

26

22

19

15

-

-

41

4.2

29

25

21

18

15

-

-

67

38

4.0

32

31

27

24

20

16

12

35

4.1

30

28

25

22

18

15

11

62

34

3.9

34

34

33

30

26

23

19

33

4.1

33

33

32

29

25

22

19

57

34

3.9

34

34

34

31

28

24

20

32

4.1

32

32

32

29

26

22

19

1400

72

42

4.0

28

25

21

17

14

-

-

39

4.2

26

23

19

16

13

-

-

67

37

4.0

32

30

26

23

19

16

12

34

4.1

30

27

24

21

17

15

11

62

33

3.9

33

32

31

28

24

21

18

32

4.1

32

31

30

27

24

20

17

57

32

3.8

32

32

31

28

24

21

18

32

4.0

32

32

31

28

24

21

18

1200

72

41

4.0

27

23

20

17

13

-

-

37

4.2

24

21

18

15

12

-

-

67

35

3.9

30

27

24

21

18

15

11

32

4.1

28

24

22

19

17

14

10

62

32

3.9

32

31

30

26

24

21

17

30

4.1

30

29

28

25

22

19

16

57

31

3.8

31

31

31

27

25

21

18

29

4.0

29

29

29

25

23

20

17

1050

72

40

3.9

24

22

19

16

14

-

-

35

4.1

21

19

17

14

12

-

-

67

34

3.9

28

24

22

19

16

14

11

31

4.0

25

22

20

18

15

12

10

62

30

3.8

30

29

27

25

22

20

17

29

4.0

29

28

26

24

21

19

16

57

30

3.8

30

30

28

25

23

20

18

28

4.0

28

28

26

24

21

19

17

900

72

38

3.9

21

20

16

14

12

-

-

34

4.1

19

18

15

12

11

-

-

67

32

3.9

25

22

20

18

15

13

11

29

4.0

23

20

18

16

14

12

10

62

29

3.8

29

27

25

23

20

18

16

27

4.0

27

25

24

21

18

17

15

57

29

3.8

29

29

26

24

21

19

17

26

4.0

26

26

23

22

19

17

15

1

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by

3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2

These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.

Refer to the Blower Performance Table for the KW of the supply air blower motor.

ALL SENSIBLE CAPACITY

NOMINAL RATING

Summary of Contents for SUNLINE 2000 2000

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...r to gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove a...

Page 17: ...TY CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 1...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 003 A 1005 Unitary Products Group 23...

Page 24: ...8QLWDU 3URGXFWV URXS RUN ULYH 1RUPDQ 2 6XEMHFW WR FKDQJH ZLWKRXW QRWLFH 3ULQWHG LQ 8 6 RS ULJKW E RUN QWHUQDWLRQDO RUSRUDWLRQ OO 5LJKWV 5HVHUYHG 6XSHUVHGHV...

Reviews: