036-21020-003 Rev. C (0203)

4

Unitary Products Group

- = Not applicable

COOLING CAPACITY - With Air Handler Coils

UNIT MODEL

AIR HANDLER

COIL

1

MODEL

1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.

COOLING

MODEL

ELECTRIC 

2

HEAT KW

2. Single phase units require single phase 2HK heaters. 

W

RATED 

CFM

NET MBH

SEER

W/O TXV

SEER

+ TXV

3

3. TXV = Use 1TV700 Series Kit.

EER

TOTAL SENS.

1 PH 12 SEER AC / N1AH + G2FD

H4DH018S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

650

18.6

14.0

12.50

-

10.80

N1AHB0806

2,5,8,10

17

G2FD030(S,H)17

650

19.0

14.3

12.50

-

10.80

H4DH024S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

850

23.4

17.6

12.10

-

10.90

N1AHB0806

2,5,8,10

17

G2FD030(S,H)17

850

23.4

17.6

12.00

-

10.90

H4DH030S06

N1AHB1206

5,8,10,15,19

17

G2FD030(S,H)17

1030

29.4

22.1

-

12.40

10.50

N1AHB1206

5,8,10,15,19

17

G2FD036(S,H)17

1030

30.0

22.5

12.40

-

10.60

H4DH036S06

N1AHB1206

5,8,10,15,19

17

G2FD036(S,H)17

1200

35.8

26.5

12.15

-

11.20

N1AHB1206

5,8,10,15,19

17

G2FD046(S,H)17

1200

36.2

26.8

12.30

-

11.20

N1AHD1406

5,8,10,15,19

24

G2FD048(S,H)24

1200

38.0

28.1

13.50

-

12.05

N1AHD1406

5,8,10,15,19

24

G2FD060(S,H)24

1200

38.5

28.5

13.70

-

12.20

H4DH042S06

N1AHC1606

5,8,10,15,20

21

G2FD042(S,H)21

1400

40.5

30.4

12.00

-

10.60

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)21

1400

42.0

31.5

12.35

-

10.90

H4DH048S06

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)21

1600

48.5

36.4

12.35

-

11.15

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1600

50.0

37.5

12.50

13.00

11.45

H4DH060S06

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1800

58.5

43.9

12.00

12.50

11.05

N1AHD2006

8,10,15,20,25,30

24

G2FD061H24

2000

60.0

45.0

12.50

12.50

11.25

1 PH 12 SEER AC / N1VS - VARIABLE SPEED

H4DH018S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

650

20.0

15.0

-

13.50

11.20

H4DH024S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

850

24.4

18.3

13.50

-

12.10

N1VSB12

10,15,18

17

G2FD036(S,H)17

860

24.6

18.5

13.55

-

12.10

H4DH030S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1030

31.0

23.3

13.40

-

11.30

N1VSB12

10,15,18

17

G2FD046(S,H)17

1000

32.6

22.8

13.50

-

11.50

H4DH036S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1200

35.6

26.7

13.10

-

12.05

N1VSC16

10,15,18

21

G2FD048(S,H)21

1200

38.0

28.5

14.10

-

12.55

H4DH042S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1380

42.5

31.9

13.35

-

11.70

H4DH048S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1590

49.0

36.8

13.00

-

11.70

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1600

50.5

37.9

13.10

-

11.90

H4DH060S06

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1780

59.0

44.3

12.40

-

11.40

N1VSD20

10,15,18,30

24

G2FD061H24

1780

60.5

45.4

-

13.00

11.80

1 PH 12 SEER AC / F2RP / RC / FP / FC / FV

4,5

4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC

models. All ratings remain the same.

5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.

H4DH018S06

F2RC/FC024

5,8,10

18

-

650

18.6

14.0

12.20

-

10.90

F2RP/FP018

2,5,8

18

-

650

18.0

13.5

12.00

-

10.70

F2RP/FP024

5,8,10

18

-

650

18.6

14.0

12.50

-

11.00

H4DH024S06

F2RC/FC024

5,8,10

18

-

850

23.0

17.3

12.00

-

10.80

F2RC/FC030

5,8,10,15

18

-

850

23.4

17.6

12.00

-

10.90

F2RP/FP024

5,8,10

18

-

850

24.0

18.0

12.10

-

10.90

F2RP/FP030

5,8,10,15

18

-

850

24.4

18.3

12.00

-

10.80

F2FP040

5,8,10,15

21

-

850

24.8

18.6

-

12.70

11.30

H4DH030S06

F2RC/FC030

5,8,10,15

18

-

1030

28.4

21.3

12.00

-

10.50

F2RP/FP030

5,8,10,15

18

-

1030

30.0

22.5

12.30

12.50

10.50

F2RP/FP036

5,8,10,15,19

21

-

1030

31.0

23.3

12.50

-

10.60

F2FP048

5,8,10,15,20,25

24

-

1030

31.4

23.6

12.60

-

10.70

H4DH036S06

F2RC/FC036

5,8,10,15

21

-

1200

35.6

26.7

12.35

-

11.10

F2RP/FP036

5,8,10,15,19

21

-

1200

36.2

27.2

12.50

-

11.45

F2RP/FP042

5,8,10,15

21

-

1200

36.4

27.3

12.50

-

11.50

F2FP045

5,8,10,15

24

-

1200

38.0

28.5

-

13.50

12.20

F2FP048

5,8,10,15,20,25

24

-

1200

36.8

27.6

12.80

-

11.80

H4DH042S06

F2RP/FP042

5,8,10,15

21

-

1400

40.5

30.4

12.00

-

10.50

F2FP045

5,8,10,15

24

-

1400

42.5

31.9

13.00

-

11.20

F2FP048

5,8,10,15,20,25

24

-

1400

41.5

31.1

12.20

-

10.65

H4DH048S06

F2FP048

5,8,10,15,20,25

24

-

1600

48.0

36.0

12.00

-

11.00

F2FP060

5,8,10,15,20,25

24

-

1600

49.0

36.8

12.30

-

10.95

F2FV060

8,10,15,20,25

24

-

1600

50.5

37.9

13.10

-

11.90

H4DH060S06

F2FP060

5,8,10,15,20,25

24

-

1900

59.0

44.3

12.00

-

10.90

F2FV060

8,10,15,20,25

24

-

1780

59.0

44.3

-

12.40

11.40

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. 
Cooling MBH based on 8

0

°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in 
watt-hours during the same period.

Summary of Contents for STELLAR PLUS H4DH018 THRU 060

Page 1: ...RESSOR The compressor is inter nally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur DURABLE FINISH Cabinet is made of powder painted steel over pre primered steel The pre treated galvanized steel provides a better paint ...

Page 2: ... Load 0 5 0 5 0 9 1 2 1 2 1 2 1 4 Fan Diameter Inches 18 18 18 24 24 24 24 Fan Motor Rated HP 1 12 1 12 1 8 1 4 1 4 1 4 1 3 Nominal RPM 1100 1100 1075 850 850 850 1100 Nominal CFM 1500 1500 2050 3100 3100 3100 4100 Coil Face Area Sq Ft 14 1 14 1 14 1 20 20 24 24 Rows Deep 1 1 1 1 1 1 1 Fin Inches 20 20 20 18 18 20 20 Liquid Line OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line OD 5 8 3 4 3 4 3 4 7 8 7 8 ...

Page 3: ...n the flow control device of each indoor coil 3 A TXV Kit must be used with these units to obtain system performance 701 702 703 indicates 1TV07 Series System Orifice Additional Charge Oz G2FD024 S H 14 17 61 57 6 63 2 G2FD030 S H 17 65 57 8 63 4 69 0 7013 0 G2FD035 S H 14 65 57 8 63 4 69 3 75 0 G2FD036 S H 17 21 75 63 8 69 3 75 10 G2FD042 S H 21 78 75 13 75 5 G2FD046 S H 17 78 71 6 75 13 75 5 87 ...

Page 4: ...H048S06 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 49 0 36 8 13 00 11 70 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1600 50 5 37 9 13 10 11 90 H4DH060S06 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1780 59 0 44 3 12 40 11 40 N1VSD20 10 15 18 30 24 G2FD061H24 1780 60 5 45 4 13 00 11 80 1 PH 12 SEER AC F2RP RC FP FC FV4 5 4 To meet R 4 2 insulation requirements substitute F2FP for F2RP and F2FC for F2RC models Al...

Page 5: ...23 4 17 6 12 00 10 90 14 G2FD035 S H 14 850 23 4 17 6 12 00 10 80 17 G2FD036 S H 17 850 24 0 18 0 12 10 10 90 H4DH030S06 900 1150 14 G1FA030S14 1030 29 0 21 8 12 00 10 30 17 21 G1FA036S17 21 1030 30 4 22 8 12 10 10 40 17 G1FA048S17 1030 31 4 23 6 12 60 10 70 21 24 G1FA048S21 1030 31 4 23 6 12 60 10 70 G1HD036 1030 30 0 22 5 12 20 10 50 17 G1NA030S17K 1030 29 4 22 1 12 00 10 50 14 G1UA030S14 1030 2...

Page 6: ... 48 0 36 0 12 20 11 00 21 24 G1FA048S21 1600 48 0 36 0 12 20 11 00 21 24 G1FA060S21 24 1600 49 5 37 1 12 50 13 00 11 35 G1HD048 1600 49 0 36 8 12 00 11 10 G1HD060 1600 49 5 37 1 12 20 11 35 21 G1NA048S21D 1600 47 0 35 3 12 00 10 85 17 G1UA048S17 1600 48 0 36 0 12 20 11 00 21 24 G1UA048S21 1600 48 0 36 0 12 20 11 00 21 24 G1UA060S21 24 1600 49 5 37 1 12 50 13 00 11 35 17 G2FD046 S H 17 1500 47 0 35...

Page 7: ...FD024 S H 17 17 815 23 8 17 9 13 00 11 80 P1XUB12V G1FA024S17 17 820 24 0 18 0 13 00 11 95 P1XUB12V G1FA036S17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G1UA024S17 17 820 24 0 18 0 13 00 11 95 P1XUB12V G1UA036S17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G2FD024 S H 17 17 820 24 0 18 0 13 00 12 05 P1XUB12V G2FD030 S H 17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G2FD036 S H 17 17 820 24 6 18 5 13 00 12 00 H4D...

Page 8: ...5 P1XUC20V G1UA048S21 21 1200 38 0 28 1 13 90 12 60 P1XUC20V G2FD036 S H 21 21 1200 36 6 27 1 13 50 12 50 P1XUC20V G2FD042 S H 21 21 1200 37 0 27 4 13 50 12 45 P1XUC20V G2FD048 S H 21 21 1200 38 5 28 5 13 90 12 65 H4DH042S06 P1DUB16V G1FA048S17 17 1400 41 0 30 8 12 50 10 95 P1DUB16V G1HD048 1425 41 5 31 1 13 00 11 45 P1DUB16V G1UA048S17 17 1400 41 0 30 8 12 50 10 95 P1DUB16V G2FD046 S H 17 17 1400...

Page 9: ... 25 11 55 P1XUC20V G2FD048 S H 21 21 1450 48 5 36 4 13 00 11 65 P1XUD20V G1FA060S24 24 1620 49 5 37 1 13 25 11 55 P1XUD20V G1UA060S24 24 1620 49 5 37 1 13 25 11 55 P1XUD20V G2FD048 S H 24 24 1620 48 5 36 4 12 50 11 25 P1XUD20V G2FD060 S H 24 24 1620 50 0 37 5 12 70 11 60 H4DH060S06 P1DUC20V G1FA060S21 21 1800 59 0 44 3 12 00 11 20 P1DUC20V G1HD060 1730 59 0 44 3 12 10 11 50 P1DUC20V G1UA060S21 21 ...

Page 10: ...o the price book or consult factory Rated in accordance with ARI Standard 270 COOLING PERFORMANCE MODEL SUCT T P COMPR AIR TEMP ON CONDENSER MODEL SUCT T P COMPR AIR TEMP ON CONDENSER 75 F 95 F 115 F 75 F 95 F 115 F TEMP PSIG MBH KW MBH KW MBH KW TEMP PSIG MBH KW MBH KW MBH KW H4DH018S06 35 61 5 18 7 1 92 12 6 2 06 7 3 2 24 H4DH042S06 35 61 5 36 8 3 07 32 2 3 69 27 6 4 37 40 68 5 20 8 1 92 14 3 2 ...

Page 11: ...8 OVERHEAD CLEARANCE 12 REAR AND SIDES NOTE All outdoor wiring must be weatherproof ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE NEC AND OR LOCAL CODES POWER WIRING 208 230 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM THERMOSTAT CONDENSIN...

Page 12: ...9 12 3 11 3 K W 2 08 2 09 2 08 2 05 2 10 2 11 2 10 2 08 2 12 2 13 2 12 2 10 125 T C 12 8 11 5 10 2 9 5 12 8 11 5 10 6 9 6 13 0 11 6 10 9 9 8 S C 11 1 11 0 10 9 9 1 11 8 11 4 11 2 9 3 12 2 12 0 10 9 9 5 K W 2 26 2 26 2 24 2 20 2 28 2 28 2 26 2 23 2 31 2 30 2 28 2 25 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB08 G2FD024 S H 17 1 02 1 02 1 00 N1...

Page 13: ...9 8 18 2 16 4 21 6 19 9 18 3 16 7 S C 15 6 15 6 16 0 15 7 16 1 16 1 16 7 16 2 16 6 16 6 16 8 16 7 K W 2 77 2 75 2 71 2 67 2 78 2 77 2 73 2 71 2 80 2 78 2 75 2 73 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB08 G2FD024 S H 17 1 00 1 00 0 99 N1AHB08 G2FD030 S H 17 1 00 1 00 0 99 N1VSB12 G2FD024 S H 17 1 04 1 04 0 93 N1VSB12 G2FD036 S H 17 1 05 1 ...

Page 14: ...0 3 78 3 76 3 86 3 84 3 82 3 80 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB12 G2FD030 S H 17 0 97 0 97 0 96 N1AHB12 G2FD036 S H 17 0 99 0 99 0 97 N1VSB12 G2FD036 S H 17 1 02 1 02 0 98 N1VSB12 G2FD046 S H 17 1 05 1 05 1 00 F2RC FC030 0 93 0 93 0 93 F2RP FP030 0 99 0 99 0 98 F2FP040 1 03 1 03 1 00 F2RP FP036 1 02 1 02 1 00 G1HD036 0 99 0 99 0 9...

Page 15: ...1AHB12 G2FD046 S H 17 1 03 1 03 1 01 N1AHD14 G2FD048 S H 24 1 08 0 91 0 99 N1AHD14 G2FD060 S H 24 1 09 0 93 0 99 N1VSB12 G2FD036 S H 17 1 01 1 03 0 92 F2RP FP036 1 03 1 04 0 99 N1VSC16 G3FD048S21 1 08 1 09 0 95 F2RP FP042 1 03 1 05 0 99 F2FP045 1 08 1 09 0 97 F2FP048 1 05 1 06 0 97 F2RC FC036 1 01 1 03 1 00 G1FA048S24 1 06 1 06 1 01 G1HD036 1 00 1 00 1 00 G1HD048 1 07 1 07 1 06 G1NA036S17J 1 01 1 ...

Page 16: ...9 6 29 7 29 3 30 7 30 6 30 9 30 7 K W 5 19 5 07 4 94 4 81 5 25 5 13 4 99 4 88 5 30 5 18 5 06 4 99 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHC16 G2FD042 S H 21 0 99 0 99 1 00 N1AHC16 G2FD048 S H 21 1 02 1 02 1 01 N1VSC16 G2FD048 S H 21 1 04 1 04 0 95 F2FP045 1 04 1 04 0 99 F2FP048 1 01 1 01 1 02 F2RP FP042 0 99 0 99 1 01 G1NA048S21D 0 99 0 99 ...

Page 17: ... 31 2 30 9 31 3 31 8 32 8 32 1 33 4 33 2 34 5 35 0 34 4 35 1 K W 6 28 6 24 6 16 6 10 6 35 6 22 6 22 6 16 6 40 6 34 6 30 6 27 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHC16 G2FD048 S H 21 1 01 1 01 1 00 N1AHD20 G2FD060 S H 24 1 04 1 04 1 00 N1VSC16 G2FD048 S H 21 1 02 1 02 0 96 N1VSD20 G2FD060 S H 24 1 05 1 05 0 97 F2FP048 1 00 1 00 1 00 F2FP06...

Page 18: ... 5 44 8 45 5 45 7 K W 6 03 5 98 5 93 5 88 6 10 6 05 6 00 5 95 6 15 6 10 6 05 6 00 115 T C 57 3 53 0 48 5 44 5 57 6 53 3 49 1 45 1 58 0 53 6 49 5 45 4 S C 40 2 40 4 40 8 41 1 41 7 41 9 42 9 43 0 43 6 43 6 44 5 44 5 K W 6 70 6 64 6 61 6 55 6 76 6 72 6 66 6 61 6 81 6 77 6 72 6 67 125 T C 54 3 50 3 45 9 42 0 54 6 50 5 46 6 42 8 55 0 50 7 47 0 43 0 S C 39 1 39 4 39 5 39 6 40 6 40 7 41 9 41 9 42 7 42 4 ...

Page 19: ...ON UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RC F2FC OR F2RC F2FP F2FV FAN COIL UNITS UPFLOW HORIZONTAL G2FD COIL ...

Page 20: ...ge without notice Printed in U S A 036 21020 003 Rev C 0203 Copyright by York International Corp 2003 All rights reserved Supersedes 036 21020 003 Rev B 0702 Unitary 5005 Norman Product York OK Group Drive 73069 NOTES ...