Procedures:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2.Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evap adder for line 

set.

5.If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
6.Due to serial compressor, hard start components are not required when using coils with TXV or solenoid valve kits.

Additional R-22 Charge / Orifice Size for Various Matched Systems

ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS

Outdoor Unit 

H4DH018S06 H4DH024S06 H4DH030S06

H4DH036S06

H4DH042S06

H4DH048S06

H4DH060S06

Unit Orifice (s) 

1

1. These orifices are packed in the customer packet of each outdoor unit.

55, 57

61, 63

69, 71

75, 78

75, 78

87, 90

99

Factory R-22 Charge, lbs-oz

4 - 14

5 - 1

5 - 4

5 - 15

6 - 12

8 - 10

7 - 13

Indoor Coil

Coil Orifice 

2

2. These orifices are factory mounted in the flow control device of each indoor coil.
3.  A TXV Kit must be used with these units to obtain system performance (701,702,703 indicates 1TV07

---

Series).

System Orifice = Additional Charge, Oz

G2FD024(S,H)14,17

61

57 + 6

63 + 2

G2FD030(S,H)17

65

57 + 8

63 + 4

69 + 0

701

+ 0

G2FD035(S,H)14

65

57 + 8

63 + 4

69 + 3

75 + 0

G2FD036(S,H)17,21

75

63 + 8

69 + 3

75 + 10

G2FD042(S,H)21

78

75 + 13

75 + 5

G2FD046(S,H)17

78

71 + 6

75 + 13

75 + 5

87+ 0

G2FD048(S,H)21,24

84

71 + 7

75 + 24/702

+ 24

75 + 20

87 + 8

G2FD060(S,H)24

90

78 + 15

90 + 10/703

+ 10 99 + 13/703

+ 13

G2FD061(H)24

90

90 + 21

703

+ 5

G1HD024

59

55 + 7

63 + 3

G1HD036

69

63 + 10

69 + 3

75 + 18

G1HD048

84

78 + 22

75 + 14

87 + 1

G1HD060

96

90 + 5

99 + 9

G1UA024S14,17

59

57 + 4

61 + 0

GIFA024S14,17

59

57 + 4

61 + 0

G1UA030S14

65

57 + 6

63 + 2

701

+  0

GIFA030S14

65

57 + 6

63 + 2

701

+  0

G1UA036S14,17,21

73

55 + 8

63 + 2

69 + 3

75 + 0

GIFA036S14,17,21

73

55 + 8

63 + 2

69 + 3

75 + 0

G1UA048S17

84

71 + 6

78 + 20

75 + 15

87 + 7

GIFA048S17

84

71 + 6

78 + 20

75 + 15

87 + 7

G1UA048S21

84

71 + 6

78 + 20/702

+ 20

75 + 19

87 + 7

GIFA048S21

84

71 + 6

78 + 20/702

+ 20

75 + 19

87 + 7

G1UA060S21,24

90

78 + 16

90 + 10/703

+ 15

99 + 9

GIFA060S21,24

90

78 + 16

90 + 10/703

+ 15

99 + 9

G1NA030S17H

57

57  +  6

G1NA030S17K

63

65 + 6

69 + 0

G1NA036S17J

67

75 + 6

G1NA048S21D

78

702

+ 15

75 + 12

87 + 3

F2RC/F2FC024

61

55 + 4

63 + 0

F2RC/F2FC030

65

63 + 4

69 + 0

F2RC/F2FC036

73

73 + 3

78 + 12

F2RP/F2FP018

59

55  +  0

F2RP/F2FP024

61

55 + 6

61 + 0

F2RP/F2FP030

65

63 + 4

69 + 0/701

+  0

F2RP/F2FP036

75

71 + 3

78 + 12

F2FP040

63

701

+ 14

71 + 6

F2RP/F2FP042

78

78 + 14

75 + 8

F2FP045

78

702

+ 28

78 + 20

F2RP/F2FP048

84

78 + 23

75 + 16

87 + 7

F2RP/F2FP060

90

90 + 10

99 + 13/703

+ 13

F2FV060

90

90 + 10

703

+ 0

Footnotes:

Summary of Contents for STELLAR PLUS H4DH018 THRU 060

Page 1: ...RESSOR The compressor is inter nally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur DURABLE FINISH Cabinet is made of powder painted steel over pre primered steel The pre treated galvanized steel provides a better paint ...

Page 2: ... Load 0 5 0 5 0 9 1 2 1 2 1 2 1 4 Fan Diameter Inches 18 18 18 24 24 24 24 Fan Motor Rated HP 1 12 1 12 1 8 1 4 1 4 1 4 1 3 Nominal RPM 1100 1100 1075 850 850 850 1100 Nominal CFM 1500 1500 2050 3100 3100 3100 4100 Coil Face Area Sq Ft 14 1 14 1 14 1 20 20 24 24 Rows Deep 1 1 1 1 1 1 1 Fin Inches 20 20 20 18 18 20 20 Liquid Line OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line OD 5 8 3 4 3 4 3 4 7 8 7 8 ...

Page 3: ...n the flow control device of each indoor coil 3 A TXV Kit must be used with these units to obtain system performance 701 702 703 indicates 1TV07 Series System Orifice Additional Charge Oz G2FD024 S H 14 17 61 57 6 63 2 G2FD030 S H 17 65 57 8 63 4 69 0 7013 0 G2FD035 S H 14 65 57 8 63 4 69 3 75 0 G2FD036 S H 17 21 75 63 8 69 3 75 10 G2FD042 S H 21 78 75 13 75 5 G2FD046 S H 17 78 71 6 75 13 75 5 87 ...

Page 4: ...H048S06 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 49 0 36 8 13 00 11 70 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1600 50 5 37 9 13 10 11 90 H4DH060S06 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1780 59 0 44 3 12 40 11 40 N1VSD20 10 15 18 30 24 G2FD061H24 1780 60 5 45 4 13 00 11 80 1 PH 12 SEER AC F2RP RC FP FC FV4 5 4 To meet R 4 2 insulation requirements substitute F2FP for F2RP and F2FC for F2RC models Al...

Page 5: ...23 4 17 6 12 00 10 90 14 G2FD035 S H 14 850 23 4 17 6 12 00 10 80 17 G2FD036 S H 17 850 24 0 18 0 12 10 10 90 H4DH030S06 900 1150 14 G1FA030S14 1030 29 0 21 8 12 00 10 30 17 21 G1FA036S17 21 1030 30 4 22 8 12 10 10 40 17 G1FA048S17 1030 31 4 23 6 12 60 10 70 21 24 G1FA048S21 1030 31 4 23 6 12 60 10 70 G1HD036 1030 30 0 22 5 12 20 10 50 17 G1NA030S17K 1030 29 4 22 1 12 00 10 50 14 G1UA030S14 1030 2...

Page 6: ... 48 0 36 0 12 20 11 00 21 24 G1FA048S21 1600 48 0 36 0 12 20 11 00 21 24 G1FA060S21 24 1600 49 5 37 1 12 50 13 00 11 35 G1HD048 1600 49 0 36 8 12 00 11 10 G1HD060 1600 49 5 37 1 12 20 11 35 21 G1NA048S21D 1600 47 0 35 3 12 00 10 85 17 G1UA048S17 1600 48 0 36 0 12 20 11 00 21 24 G1UA048S21 1600 48 0 36 0 12 20 11 00 21 24 G1UA060S21 24 1600 49 5 37 1 12 50 13 00 11 35 17 G2FD046 S H 17 1500 47 0 35...

Page 7: ...FD024 S H 17 17 815 23 8 17 9 13 00 11 80 P1XUB12V G1FA024S17 17 820 24 0 18 0 13 00 11 95 P1XUB12V G1FA036S17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G1UA024S17 17 820 24 0 18 0 13 00 11 95 P1XUB12V G1UA036S17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G2FD024 S H 17 17 820 24 0 18 0 13 00 12 05 P1XUB12V G2FD030 S H 17 17 820 24 6 18 5 13 00 12 00 P1XUB12V G2FD036 S H 17 17 820 24 6 18 5 13 00 12 00 H4D...

Page 8: ...5 P1XUC20V G1UA048S21 21 1200 38 0 28 1 13 90 12 60 P1XUC20V G2FD036 S H 21 21 1200 36 6 27 1 13 50 12 50 P1XUC20V G2FD042 S H 21 21 1200 37 0 27 4 13 50 12 45 P1XUC20V G2FD048 S H 21 21 1200 38 5 28 5 13 90 12 65 H4DH042S06 P1DUB16V G1FA048S17 17 1400 41 0 30 8 12 50 10 95 P1DUB16V G1HD048 1425 41 5 31 1 13 00 11 45 P1DUB16V G1UA048S17 17 1400 41 0 30 8 12 50 10 95 P1DUB16V G2FD046 S H 17 17 1400...

Page 9: ... 25 11 55 P1XUC20V G2FD048 S H 21 21 1450 48 5 36 4 13 00 11 65 P1XUD20V G1FA060S24 24 1620 49 5 37 1 13 25 11 55 P1XUD20V G1UA060S24 24 1620 49 5 37 1 13 25 11 55 P1XUD20V G2FD048 S H 24 24 1620 48 5 36 4 12 50 11 25 P1XUD20V G2FD060 S H 24 24 1620 50 0 37 5 12 70 11 60 H4DH060S06 P1DUC20V G1FA060S21 21 1800 59 0 44 3 12 00 11 20 P1DUC20V G1HD060 1730 59 0 44 3 12 10 11 50 P1DUC20V G1UA060S21 21 ...

Page 10: ...o the price book or consult factory Rated in accordance with ARI Standard 270 COOLING PERFORMANCE MODEL SUCT T P COMPR AIR TEMP ON CONDENSER MODEL SUCT T P COMPR AIR TEMP ON CONDENSER 75 F 95 F 115 F 75 F 95 F 115 F TEMP PSIG MBH KW MBH KW MBH KW TEMP PSIG MBH KW MBH KW MBH KW H4DH018S06 35 61 5 18 7 1 92 12 6 2 06 7 3 2 24 H4DH042S06 35 61 5 36 8 3 07 32 2 3 69 27 6 4 37 40 68 5 20 8 1 92 14 3 2 ...

Page 11: ...8 OVERHEAD CLEARANCE 12 REAR AND SIDES NOTE All outdoor wiring must be weatherproof ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE NEC AND OR LOCAL CODES POWER WIRING 208 230 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM THERMOSTAT CONDENSIN...

Page 12: ...9 12 3 11 3 K W 2 08 2 09 2 08 2 05 2 10 2 11 2 10 2 08 2 12 2 13 2 12 2 10 125 T C 12 8 11 5 10 2 9 5 12 8 11 5 10 6 9 6 13 0 11 6 10 9 9 8 S C 11 1 11 0 10 9 9 1 11 8 11 4 11 2 9 3 12 2 12 0 10 9 9 5 K W 2 26 2 26 2 24 2 20 2 28 2 28 2 26 2 23 2 31 2 30 2 28 2 25 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB08 G2FD024 S H 17 1 02 1 02 1 00 N1...

Page 13: ...9 8 18 2 16 4 21 6 19 9 18 3 16 7 S C 15 6 15 6 16 0 15 7 16 1 16 1 16 7 16 2 16 6 16 6 16 8 16 7 K W 2 77 2 75 2 71 2 67 2 78 2 77 2 73 2 71 2 80 2 78 2 75 2 73 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB08 G2FD024 S H 17 1 00 1 00 0 99 N1AHB08 G2FD030 S H 17 1 00 1 00 0 99 N1VSB12 G2FD024 S H 17 1 04 1 04 0 93 N1VSB12 G2FD036 S H 17 1 05 1 ...

Page 14: ...0 3 78 3 76 3 86 3 84 3 82 3 80 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB12 G2FD030 S H 17 0 97 0 97 0 96 N1AHB12 G2FD036 S H 17 0 99 0 99 0 97 N1VSB12 G2FD036 S H 17 1 02 1 02 0 98 N1VSB12 G2FD046 S H 17 1 05 1 05 1 00 F2RC FC030 0 93 0 93 0 93 F2RP FP030 0 99 0 99 0 98 F2FP040 1 03 1 03 1 00 F2RP FP036 1 02 1 02 1 00 G1HD036 0 99 0 99 0 9...

Page 15: ...1AHB12 G2FD046 S H 17 1 03 1 03 1 01 N1AHD14 G2FD048 S H 24 1 08 0 91 0 99 N1AHD14 G2FD060 S H 24 1 09 0 93 0 99 N1VSB12 G2FD036 S H 17 1 01 1 03 0 92 F2RP FP036 1 03 1 04 0 99 N1VSC16 G3FD048S21 1 08 1 09 0 95 F2RP FP042 1 03 1 05 0 99 F2FP045 1 08 1 09 0 97 F2FP048 1 05 1 06 0 97 F2RC FC036 1 01 1 03 1 00 G1FA048S24 1 06 1 06 1 01 G1HD036 1 00 1 00 1 00 G1HD048 1 07 1 07 1 06 G1NA036S17J 1 01 1 ...

Page 16: ...9 6 29 7 29 3 30 7 30 6 30 9 30 7 K W 5 19 5 07 4 94 4 81 5 25 5 13 4 99 4 88 5 30 5 18 5 06 4 99 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHC16 G2FD042 S H 21 0 99 0 99 1 00 N1AHC16 G2FD048 S H 21 1 02 1 02 1 01 N1VSC16 G2FD048 S H 21 1 04 1 04 0 95 F2FP045 1 04 1 04 0 99 F2FP048 1 01 1 01 1 02 F2RP FP042 0 99 0 99 1 01 G1NA048S21D 0 99 0 99 ...

Page 17: ... 31 2 30 9 31 3 31 8 32 8 32 1 33 4 33 2 34 5 35 0 34 4 35 1 K W 6 28 6 24 6 16 6 10 6 35 6 22 6 22 6 16 6 40 6 34 6 30 6 27 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHC16 G2FD048 S H 21 1 01 1 01 1 00 N1AHD20 G2FD060 S H 24 1 04 1 04 1 00 N1VSC16 G2FD048 S H 21 1 02 1 02 0 96 N1VSD20 G2FD060 S H 24 1 05 1 05 0 97 F2FP048 1 00 1 00 1 00 F2FP06...

Page 18: ... 5 44 8 45 5 45 7 K W 6 03 5 98 5 93 5 88 6 10 6 05 6 00 5 95 6 15 6 10 6 05 6 00 115 T C 57 3 53 0 48 5 44 5 57 6 53 3 49 1 45 1 58 0 53 6 49 5 45 4 S C 40 2 40 4 40 8 41 1 41 7 41 9 42 9 43 0 43 6 43 6 44 5 44 5 K W 6 70 6 64 6 61 6 55 6 76 6 72 6 66 6 61 6 81 6 77 6 72 6 67 125 T C 54 3 50 3 45 9 42 0 54 6 50 5 46 6 42 8 55 0 50 7 47 0 43 0 S C 39 1 39 4 39 5 39 6 40 6 40 7 41 9 41 9 42 7 42 4 ...

Page 19: ...ON UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RC F2FC OR F2RC F2FP F2FV FAN COIL UNITS UPFLOW HORIZONTAL G2FD COIL ...

Page 20: ...ge without notice Printed in U S A 036 21020 003 Rev C 0203 Copyright by York International Corp 2003 All rights reserved Supersedes 036 21020 003 Rev B 0702 Unitary 5005 Norman Product York OK Group Drive 73069 NOTES ...