LOCAL PRINTER OPTION
The micro panel is capable of supplying a print-out of
chiller conditions or fault shutdown information at any
given time. This allows operator and service personnel
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the micro
panel will provide an automatic print-out whenever a fault
occurs. An explanation of the keypad use to obtain a
print-out is discussed in the PRINT KEY Section on
Page 55.
YORK recommends the field tested WEIGH-TRONIX
IMP-24, Model 2600 printer. This is a compact low cost
printer that is ideal for service work and data logging.
Paper is in the form of a compact roll and is easily handled
compared to larger printers using wider business form
style paper. The paper is 2.25" wide desk-top calculator
paper that can be easily and inexpensively purchased at
most stationery stores. Shown in Fig. 32 and 33 is the
WEIGH-TRONIX printer and a typical sample print-out.
The WEIGH-TRONIX IMP-24 Model 2600 printer can be
purchased for approximately $150.00. Contact WEIGH-
TRONIX for purchase information:
Weigh-Tronix
2320 Airport Blvd.
Santa Rosa, Ca. 95402
Phone: 1-800-358-9110 or 1-707-527-5555
(International Orders Only)
NOTE: The print-out is made to be universal to all types
of chillers both air and water cooled with or with-
out options. Items may be indicated on the print-
out which may not be present on the chiller.
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/95
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP
65.0 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
4 4 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
5 0 %FLA
SUCTION PRESSURE
6 1 PSIG
DISCHARGE PRESSURE
1 4 3 PSIG
OIL PRESSURE
7 5 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
0 %FLA
SUCTION PRESSURE
6 1 PSIG
DISCHARGE PRESSURE
8 0 PSIG
OIL PRESSURE
1 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
*=HOLIDAY
SUN
START=06:00AM
STOP=11:00AM
MON
START=06:00AM
STOP=11:00AM
TUE
START=06:00AM
STOP=11:00AM
WED
START=06:00AM
STOP=11:00AM
THU
START=06:00AM
STOP=11:00AM
FRI
START=06:00AM
STOP=11:00AM
SAT
START=06:00AM
STOP=11:00AM
HOL
START=00:00AM
STOP=00:00AM