background image

ENGLISH

8

ø 65 mm

PARTS INSTALLATION

NOTES

INDOOR UNIT

INSTALLATION PROCEDURE

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

 Fixing

   Place the installation guide pattern on the designated 

installation place and mark the hole position.

   Drill a hole and mount installation plate.

   After determining the pipe hole position. Drill the hole    

at a slight downward slant towards the outdoor side.

Outdoor

Indoor

Note: 

When installing the 
refrigerant pipes from 
others side. A hole 
must be place to 
allow fall towards the 
outdoor unit.

  Make 6 mm 4-6 holes, in the wall at the four corners of 

mouting plate (bracket) then insert appropriate mouting 
devices.

  Install the mounting plate using 4-6 pieces of mounting 

screw securely at four corners and tighten the screw 
completely. Do not over tighten the screws and deform 
the back plate.

CAUTIONS

  Ensure that the space around the left and right of the 

indoor unit is more than 12cm.

 

The indoor unit should be installed allowing a minimum 
clearance of 15cm from the ceiling.

  Use a stud 

fi

 nder to locate studs to prevent unnecessary 

damage to the wall.

  A minimum pipe run of 3 metres is required to minimise 

vibration & excessive noise.

  The indoor unit should be installed on the wall at a height 

of 2.3 metres or more from the 

fl

 oor .

  A, B and C directions should be free from obstructions.

NOTES

  This illustration is for explanation purposes only.

  Copper lines must be insulated independently.

C

B

A

1

2

3

5

4

7

6

Self-tapping screw B
ST3.9X10

Loop the 
connective 
cable.

Remote Controller

Air F

ilter

Remote Controller
holer

30cm

 mini

mum

200cm m

inimum

60cm m

inimum

30cm m

inimum

12cm minim

um

12cm min

imu

m

15cm mi

nimum

60cm minimum

Except the above parts provided, the other parts needed 
during installation you must purchase.

750

45

250

Right refrigerant
pipe hole 

65

Installation plate

Indoor unit outline

Left refrigerant
pipe hole 

65

150mm or more to ceiling

120mm or more
to wall

120mm or more
to wall

150mm or more to ceiling

Indoor unit outline

Installation plate

920

293

Right refrigerant
pipe hole 

65

Left refrigerant
pipe hole 

65

120mm or more
to wall

120mm or more
to wall

(

12000Btu/h model)

MODEL 07-12

MODEL 18

Number

Name of part

Q’ty

1

Installation plate

1

2

Clip anchor

8

3

Self-tapping screw A ST3.9X25

8

4

Connecting

pipe

assembly

Liquid side ø 6.35

Parts you

must

purchase

Gas side

ø 9.53 (<12000Btu/h model)

ø 12.7 (21000Btu/h model > Cooling 
capacity 

f

 

12000Btu/h model) 

ø 16 (

f

21000Btu/h model)

5

Remote controller

1

6

Self-tapping screw B ST3.9X10

2

7

Remote controller holder

1

8

Seal

1

9

Drain joint

1

J277-EN.indd   8

J277-EN.indd   8

26.12.2005   15:15:19 Uhr

26.12.2005   15:15:19 Uhr

Summary of Contents for RACCxxFSAAAR

Page 1: ...DELS RLCA RLHA 07 30 RLCB RLHB 07 28 RACC RAHC 07 28 MINISPLIT HIGH WALL AIR CONDITIONER EN 035M80147 000 The units comply with one or more of the following marks see unit for details J277 EN 1 J277 EN indd revise by Arisa 16 02 06 ...

Page 2: ...stent reli ability in product service and support through superior quality service culture and distinctive technology R22 R407C 50Hz 60Hz 50Hz Set RLCAxxFSAAAR RLCAxxFSAADR RLCBxxFSAAAR RLHAxxFSAAAR RLHAxxFSAADR RLHBxxFSAAAR Outdoor RLDAxxFS AAR RLDAxxFS ADR RLDBxxFS AAR RLJAxxFS AAR RLJAxxFS ADR RLJBxxFS AAR Indoor RLEAxxFS AAR RLEAxxFS ADR RLEBxxFS AAR RLKAxxFS AAR RLKAxxFS ADR RLKBxxFS AAR R410...

Page 3: ...rous and can cause injury Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power supply has been disconnected WARNING CAUTIONS Do not store or unpack the unit in a wet area or expose to rain or water...

Page 4: ...PERATURE indicator Displays the temperature settings when the air conditioner is operational 4 OPERATION indicator This indicator flashes after power is on and illuminates when the unit is in operation 5 TIMER indicator This indicator illuminates when TIMER is set ON OFF NOTE All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner yo...

Page 5: ...r conditioner will automatically increase cooling or decrease heating 1 C per hour The set temperature will be steady 2 hours later The fan speed will be automatically controlled DRYING OPERATION The dry mode will automatically select the drying operation based on the difference between the set temperature and the actual room temperature Thetemperatureisregulatedwhiledehumidifyingbyrepeating turni...

Page 6: ...cord and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements Check that the power supply available agrees with name plate voltage Electrical work wiring and cables must be in compliance with national and local wiring codes and standard Do not use the extension cables In the case extended cables are needed use the terminal block SELECT...

Page 7: ... 548 115 90 266 272 298 285 290 530 110 62 590 750 RLDA RLJA 07 09 RLDB RLJB 07 09 RADC RAJC 07 RLDA RLJA 12 18 RLDB RLJB 12 RADC RAJC 09 12 RLDA RLJA 24 30 RLDB RLJB 24 28 RADC RAJC 18 28 RLDB RLJB 18 335 125 560 1 141 5 135 351 2 694 5 301 5 843 313 235 J277 EN indd 7 J277 EN indd 7 26 12 2005 15 15 18 Uhr 26 12 2005 15 15 18 Uhr ...

Page 8: ...es or more from the floor A B and C directions should be free from obstructions NOTES This illustration is for explanation purposes only Copper lines must be insulated independently C B A 1 2 3 5 4 7 6 Self tapping screw B ST3 9X10 Loop the connective cable Remote Controller Air Filter Remote Controller holer 30cm minimum 200cm minimum 60cm minimum 30cm minimum 12cm minimum 12cm minimum 15 cm mi n...

Page 9: ...ll Carefully arrange pipes so that pipes do not stick out of the rear plate of the indoor unit A B C D E F MODEL 24 30 Right Right Right Right Left Rear Bottom Drain hose Drain hose is flexible and can be routed to suit vari ous piping arrangements The drain line must include elbow trap U bend Connect a plastic condensate pipe with an internal diameter of 12 mm The drain hose can be connected to t...

Page 10: ...nsmitted to the building struc ture Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines must be insulated separately Maximum Piping Length The suction line must have a 2 gradient up to the compressor on horizontal sections Where piping lengths are unusually lon...

Page 11: ...ers Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R22 R407C R410A Outdoor heat pump unit install the unit at least 10 cm above ground level to facilitate drainage of defrost water and prevent accumulation of ice In effect defrost water can cause accumulation of ice under the unit during subfr...

Page 12: ...Disconnecting device must have a contact separation of at least 3 mm Models 07 18 Cooling only Power supply Indoor L N 1 2 N 1 2 N Outdoor CAUTIONS Models 07 18 Cooling and Heating L N 1 2 N 3 4 1 2 N 3 4 Outdoor Indoor Models 24 30 Cooling only Cooling and Heating Outdoor Indoor For correct installation a proper ground connection must be made for unit Power supply L N 1 2 N S 1 2 N S Perform the ...

Page 13: ...m 1 2 N S L N Terminal block of indoor unit Cooling only type cooling heating type Terminal block of indoor unit Cord clamp To outdoor unit To outdoor unit Terminal block of outdoor unit Wire holding board Terminal block of outdoor unit Cooling only type cooling heating type Cooling only type Cooling heating type J277 EN indd 13 J277 EN indd 13 26 12 2005 15 15 26 Uhr 26 12 2005 15 15 26 Uhr ...

Page 14: ...V 50Hz 32A 220 230V 60Hz NOTE b Unit has been running at high temperature protection mode for 90 minute High temperature protection mode when coil temperature of indoor unit reaches 55 C outdoor unit will turn off external unit fan but still keep compressor running 2 Condition to stop defrosting Units will switch back to heating mode when either of the following conditions is met a Unit has been r...

Page 15: ...f the unit 2 Stop the air conditioner and disconnect power Remove the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer Checks before operation Check that the wiring is not broken off or disconnected Check that the air filter is installed Check if the air outlet or inlet is blocked a...

Page 16: ...l condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell comes out from the indoor unit This is caused by the indoor unit giving off smells permeated from building material from furniture or smoke 6 The air conditioner turns to FAN only mode from COOL or HEAT for cooling and heating models only mode When indoor temperature reaches th...

Page 17: ...ys tem 1 Remove charge repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs con tinuously 1 Thermostat adjustment too low in heating mode or too high in cool ing mode 2 Faulty fan 3 Refrigerant charge too low leak 4 Air or incondensables in refrigerant circuit 1 Check thermostat setting 2 Check condenser air circulation 3 ...

Page 18: ...h Hz 220 240 1 50 Ph 1 1 1 1 1 1 Fan Air flow m3 h 400 400 450 450 580 580 800 800 1080 1080 1150 1150 Input Power W 39 5 39 5 39 5 39 5 38 5 38 5 53 53 65 65 70 70 Running Current A 0 17 0 17 0 17 0 17 0 17 0 17 0 24 0 24 0 29 0 29 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190 190 195...

Page 19: ... 0 14 0 14 0 14 0 14 0 24 0 24 0 68 0 68 0 34 0 34 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190 190 195 195 225 225 225 225 225 225 Weight kg 8 5 8 5 8 5 8 5 9 0 9 0 13 13 17 17 17 17 System Operation Control Wireless Control with LCD Display Outdoor Unit Power Supply V Ph Hz 220 230 1 60 Ph 1 ...

Page 20: ...0 Running Current A 0 17 0 17 0 17 0 17 0 2 0 2 0 26 0 26 0 37 0 37 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190 190 195 195 225 225 225 225 225 225 Weight kg 8 8 8 8 9 9 13 13 17 17 17 17 System Operation Control Wireless Control with LCD Display Outdoor Unit Power Supply V Ph Hz 220...

Page 21: ... 65 65 70 70 Running Current A 0 17 0 17 0 17 0 17 0 2 0 2 0 26 0 26 0 37 0 37 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190 190 193 193 225 225 225 225 225 225 Weight kg 8 8 8 8 9 9 13 13 17 17 17 17 System Operation Control Wireless Control with LCD Display Outdoor Unit Power Supply ...

Page 22: ...nces should refrigerant be vented to atmosphere Where appropriate drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes 3 Packaged unit can generally be removed in one piece after disconnection as above Any fixing down bolts should be removed and then unit lifted from position using the points p...

Reviews: