036-21606-001 Rev. A (0804)
4
Unitary Products Group
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m
3
/min).
2. Return air is through side opposite motor (left side).
3. Airflows above 1800 CFM (50.97 m
3
/min) require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
INPUT High Fire: 60,000 / Low Fire: 39,000
INPUT High Fire: 80,000 / Low Fire: 52,000
JUMPER SETTINGS
CFM CFM
High Low High Low
COOL
Tap
ADJ
Tap
1340 740 1675 920 A
B
1155 635 1555 850 B
B
1220 671 1525 830 A
A
1050 578 1410 795 B
A
1100 605 1355 760 A
C
913 502 1330 750 C
B
945 520 1280 710 B
C
726 400 1145 625 D
B
830 456 1235 680 C
A
660 400 1035 555 D
A
747 411 1105 600
C
C
594 400 920 495
D
C
INPUT High Fire: 100,000 / Low Fire: 65,000
INPUT High Fire: 120,000 / Low Fire: 78,000
JUMPER SETTINGS
CFM CFM
High Low High Low
COOL
Tap
ADJ
Tap*
2050 1135 2020 1130 A
B
1860 980 1855 960 B
B
1945 1035 1920 1010 A
A
1665 910 1680 850 B
A
1740 950 1765 910 A
C
1575 880 1630 820 C
B
1440 830 1485 760 B
C
1325 760 1355 720 D
B
1410 820 1465 745 C
A
1190 725 1210 650 D
A
1245 745 1260 695 C
C
1065 690 1080 595 D
C
HIGH / LOW HEAT CFM
INPUT High Fire: 60,000 / Low Fire: 39,000
INPUT High Fire: 80,000 / Low Fire: 52,000
JUMPER SETTINGS
CFM CFM
High Low High Low
COOL
Tap
ADJ
Tap*
1315 880 1490 990 A
Any
1185 795 1350 900 B
Any
1075 720 1240 820 C
Any
990 665 1140 760 D
Any
INPUT High Fire: 100,000 / Low Fire: 65,000
INPUT High Fire: 120,000 / Low Fire: 78,000
JUMPER SETTINGS
CFM CFM
High Low High Low
COOL
Tap
ADJ
Tap*
1480 975 1950 1330
A
Any
1350 900 1840 1165
B
Any
1235 815 1705 1055
C
Any
1140 770 1535 960 D
Any
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure.
From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
NOTE - The ADJ “D” tap should not be used.