036-21578-002 Rev. B (0205)

4

Unitary Products Group

NOTES:

1. Airflow expressed in standard cubic feet per minute.
2. Return air is through side opposite motor (left side).
3. Airflows above 1800 CFM require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE: 

The filter pressure drop values in the “Filter Perfor-

mance” table shown below are typical values for the type of 
filter listed and should only be used as a guideline. Actual 
pressure drop ratings for each filter type vary between filter 
manufacturer.

BLOWER PERFORMANCE CFM

AIRFLOW WITH BOTTOM OR ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7 0.8

0.9

1.0

CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM 

PS9A12N040UP11

HIGH 1635

1590

1535

1480

1415

1340

1280

1185

NR

NR

M-HI 1245 1225 1205 1185 1160

1110 1065

995

NR

NR

M-LO 1005  1000  995

975

955

925

885

825

NR

NR

LOW 775 770 765

750

725

680

655

620

NR

NR

PS9B12N060UP11
PS9B12N080UP11

HIGH 1650 1605 1570 1525 1465 1410 1350 1275 1170 1060 

M-HI 1165 1185 1175 1165 1150 1140 1100 1050  970  875 

M-LO 895 915 935 940 940 920 905 860 815 750 

LOW 710 725 725 725 720 700 685 660 625 560 

PS9C20N080UP11
PS9C20N100UP11

HIGH 2300

2210

2120

2020

1930

1830

1715

1595

1480

1350

M-HI 1950

1900

1830

1755

1680

1595

1500

1390

1270

1155

M-LO 1610

1545

1490

1440

1390

1315

1230

1155

1050

920

LOW 1325

1270

1225

1175

1105

1045

990

905

890

790

PS9C16N080UP11 
PS9C16N100UP11

HIGH 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 

M-HI 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 

M-LO 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 

LOW 930 945 965 975 975 975 975 950 910 850 

PS9D20N120UP11
PS9D20N135UP11

HIGH 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 

M-HI 2090 2050 1990 1970 1885 1820 1760 1675 1545 1405 

M-LO 1695 1675 1665 1615 1565 1510 1460 1385 1285 1140 

LOW 1175 1150 1135 1110 1085 1055 1005  980  970  845 

AIRFLOW WITH TWO SIDE RETURNS OR WITH BOTTOM AND ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM 

PS9C20N080UP11
PS9C20N100UP11

HIGH 2465

2380

2295

2195

2095

1995

1875

1760

1620

1470

M-HI 2085

2035

1960

1880

1800

1705

1605

1485

1360

1235

M-LO 1725

1625

1595

1540

1485

1405

1315

1235

1125

995

LOW 1420

1360

1310

1255

1180

1120

1070

970

950

845

PS9D20N120UP11
PS9D20N135UP11

HIGH 2615 2535 2450 2385 2285 2175 2075 1945 1825 1670 

M-HI 2055 2045 2015 1985 1932 1855 1785 1730 1605 1470 

M-LO 1690 1650 1620 1600 1570 1525 1470 1395 1300 1200 

LOW 1345 1335 1335 1285 1250 1230 1180  1115 1010  850 

Summary of Contents for PS9A12N040UP11

Page 1: ... warranty FEATURES Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit amp requirement for easy replacement applica tion Integrated control module for reliable economical opera tion High velocity filter and side return filter rack provided for easy fi...

Page 2: ...LE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in PS9A12N040UP11 1200 A 14 1 2 13 1 4 12 1 8 6 1 4 PS9B12N060UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PS9B12N080UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PS9C16N080UP11 1600 C 21 19 3 4 18 1 2 8 7 8 PS9C20N080UP11 2000 C 21 19 3 4 18 1 2 8 7 8 PS9C16N100UP11 1600 C 21 19 3 4 ...

Page 3: ...0 45 75 PS9C16N080UP11 80 75 11 x 10 3 4 10 2 20 45 75 PS9C20N080UP11 80 75 11 x 11 1 12 7 20 40 70 PS9C16N100UP11 100 93 11 x 10 3 4 10 2 20 45 75 PS9C20N100UP11 100 93 11 x 11 1 12 7 20 40 70 PS9D20N120UP11 120 112 11 x 11 1 12 7 20 40 70 PS9D20N135UP11 135 127 11 x 11 1 12 7 20 45 75 Model Max Outlet Air Temp Nominal Airflow Cabinet Width Total Unit AFUE Min Wire Size awg 75 ft One Way Approxim...

Page 4: ... 1410 1350 1275 1170 1060 M HI 1165 1185 1175 1165 1150 1140 1100 1050 970 875 M LO 895 915 935 940 940 920 905 860 815 750 LOW 710 725 725 725 720 700 685 660 625 560 PS9C20N080UP11 PS9C20N100UP11 HIGH 2300 2210 2120 2020 1930 1830 1715 1595 1480 1350 M HI 1950 1900 1830 1755 1680 1595 1500 1390 1270 1155 M LO 1610 1545 1490 1440 1390 1315 1230 1155 1050 920 LOW 1325 1270 1225 1175 1105 1045 990 ...

Page 5: ... the following example Example For a 120 000 Btuh furnace with 2 return openings and operating on high speed blower it is found that total sys tem static is 0 58 w c To determine the system airflow com plete the following steps 1 Obtain the airflow values at 0 50 0 60 ESP Airflow 0 50 2285 CFM Airflow 0 60 2175 CFM 2 Subtract the airflow 0 50 from the airflow 0 60 to obtain airflow difference 2175...

Page 6: ...14 1 2 cabinets 1BR0317 For 17 1 2 cabinets 1BR0321 For 21 cabinets 1BR0324 For 24 1 2 cabinets EXTERNAL SIDE RETURN FILTER RACK 1SF0101 Fits all cabinet sizes Attaches to side of furnace cabinet in side return applications Holds any 16x25x1 permanent or disposable filter HIGH ALTITUDE PRESSURE SWITCHES These accessory kits may be used to convert units for high altitude operation Conversion must b...

Page 7: ...036 21578 002 Rev B 0205 Unitary Products Group 7 NOTES ...

Page 8: ...e without notice Printed in U S A 036 21578 002 Rev B 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 036 21578 002 Rev A 0904 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: