York PS9 Installation Manual Download Page 6

105564-UIM-A-0205

6

Unitary Products Group

IMPORTANT: 

If an external mounted filter rack is being used see the

instructions provided with that accessory for proper hole cut size.

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a filter. A high velocity filter and a side
return filter rack are provided for field installation. Replacement filter
size is shown in Table 4.

Filters must be installed external to the furnace cabinet. 

DO NOT

attempt to install filters inside the furnace.

SIDE RETURN - FILTER INSTALLATION

Locate and mark the side return opening. Refer to Figure 1 for dimen-
sions of the cutout.

Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.If not provided with the furnace, an accessory filter rack is avail-
able for mounting the filter external to the cabinet.

IMPORTANT: 

Some accessories such as electronic air cleaners and

pleated media may require a larger side opening. Follow the instruc-
tions supplied with that accessory for side opening requirements. Do
not cut the opening larger than the dimensions shown in Figure 1.

SECTION IV: GAS PIPING

GAS SAFETY

IMPORTANT: 

Plan your gas supply before determining the correct gas

pipe entry. Use 90-degree service elbow(s), or short nipples and con-
ventional 90-degree elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed con-
nector. Do not use a connector that has previously serviced another gas
appliance.

Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The instal-
lation of a drip leg and ground union is required. Refer to Figure 4.

IMPORTANT: 

An accessible manual shutoff valve must be installed

upstream of the furnace gas controls and within 6 feet (1.8 m) of the fur-
nace.

The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or greater
than 1/2 psig (3.5 kPa).

 FIGURE 2:  

Furnace Base Rectangular Blockoff Panel

TABLE 4: 

Filter Sizes

Input/Output

BTU/H (kW)

Nominal CFM 

(m

3

/min)

Cabinet 

Size

Side Return 

Filter in. (cm)

Bottom Return 

Filter in. (cm)

40/38 

(11.7/10.8)

1200 

(34)

A

16 x 25 

(41 x 64)

14 x 25 

(36 x 64)

60/56 

(17.6/16.1)

1200 

(34)

B

16 x 25 

(41 x 64)

16 x 25 

(41 x 64)

80/74 

(23.4/22.0)

1200 

(34)

B

16 x 25 

(41 x 64)

16 x 25 

(41 x 64)

80/75 

(23.4/22.0)

1600 

(45)

C

16 x 25 

(41 x 64)

20 x 25 

(51 x 64)

80/75 

(23.4/22.0)

2000 

(57)

C

16 x 25 

(41 x 64)

20 x 25 

(51 x 64)

100/93 

(29.3/27.8)

1600 

(45)

C

16 x 25 

(41 x 64)

20 x 25 

(51 x 64)

100/93 

(29.3/27.8)

2000 

(57)

C

16 x 25 

(41 x 64)

20 x 25 

(51 x 64)

120/112 

(35.1/32.8)

2000 

(57)

D

(2) 16 x 25 

(2) (41 x 64)

22 x 25 

(56 x 64)

135/127 

(39.6/36.9)

2000 

(57)

D

(2) 16 x 25 

(2) (41 x 64)

22 x 25 

(56 x 64)

All installations must have a filter installed.

Toe Plate

Removable Rectangular
Base Panel.

An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 PSI {14" w.c. (3.48 kPa)}. Pressures exceed-
ing 0.5 PSI {14” w.c. (3.48 kPa)} at the gas valve will cause damage
to the gas valve, resulting in a fire or explosion or cause damage to
the furnace or some of its components that will result in property
damage and loss of life.

 FIGURE 3:  

Gas Valve

 FIGURE 4:  

Gas Piping

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON

OFF

ON/OFF SWITCH
(Shown in ON position)

MAIN REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT PORT

EXTERNAL MANUAL
SHUTOFF VALVE

TO GAS
SUPPLY

TO GAS
SUPPLY

GROUNDED JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE UNIT.

DRIP
LEG

Summary of Contents for PS9

Page 1: ...TWINNING AND STAGING 9 COMBUSTION AIR AND VENT SYSTEM 11 CONDENSATE PIPING 18 SAFETY CONTROLS 18 START UP AND ADJUSTMENTS 19 WIRING DIAGRAM 25 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Bl...

Page 2: ...ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combu...

Page 3: ...required for passage to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustible...

Page 4: ...sure drop across any applied coil TABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace...

Page 5: ...1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility The supply air temperature MUST NEVER e...

Page 6: ...ctions in this section specify the type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 4 IMPORTANT An acces...

Page 7: ...ing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak TABLE 5 High Altitude Conversion 40 120 MBTUH Models Type Of Gas Orifice at Sea Leve...

Page 8: ...ernate wiring method is to use a field provided 2 5 08 cm x 4 10 2 cm box and cover on the outside of the furnace Route the furnace leads into the box using a protective bushing where the wires pass t...

Page 9: ...using the same duct system it is very important that the two furnace cir culating air blowers operate in unison If one blower starts before the second blower the duct system will become pressurized an...

Page 10: ...then will shut off at the same time Continuous Fan On a thermostat call for continuous fan G signal both furnace blowers will come on at the same time in cooling speed and will stay on until the G sig...

Page 11: ...ow a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for...

Page 12: ...n air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disassemble the combustion air and vent piping...

Page 13: ...0 kW 36 inches 91 cm for models 100 000 BTUH 30 kW Two pipe direct vent applications 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW Single pipe applications 4...

Page 14: ...ombustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 15 or 16 VENTING MULTIPLE UNITS Multiple units can be installed...

Page 15: ...ll bring air in from the outdoors to the furnace combustion air intake collar on the burner box The second pipe Shown in Figure 19 is the furnace vent pipe The combustion air intake pipe should be loc...

Page 16: ...e louver is in the fully open position This type of installation requires that the supply air to the appli ance s be of a sufficient amount to support all of the appliance s in the area Operation of a...

Page 17: ...sage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated a...

Page 18: ...p pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing...

Page 19: ...th x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These item...

Page 20: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Page 21: ...l reference atmo spheric pressure Refer to Figure 26 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or ti...

Page 22: ...s user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins The blower speed connections shown in Figure 27 are typical How...

Page 23: ...35 1175 33 1105 31 1045 30 990 28 905 25 890 25 790 22 80 1600 C 100 1600 C HIGH 1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 M HI 1565 44 1560 44 1560 44 1575 45 15...

Page 24: ...that total system static is 0 58 w c To determine the system airflow complete the follow ing steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2285 CFM 64 70 m3 min A...

Page 25: ...105564 UIM A 0205 Unitary Products Group 25 SECTION XI WIRING DIAGRAM FIGURE 28 Wiring Diagram...

Page 26: ...105564 UIM A 0205 26 Unitary Products Group NOTES...

Page 27: ...105564 UIM A 0205 Unitary Products Group 27 NOTES...

Page 28: ...change without notice Printed in U S A 105564 UIM A 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 035 20377 002 Rev A 0904 Unitary 5005 Norman Product York OK Group Dr...

Reviews: