COOLING TROUBLESHOOTING GUIDE

On calls for cooling, if the compressors are operating but the
supply air blower motor does not energize after a short delay
(the room thermostat fan switch is in the “AUTO” position):

1.

Turn  the thermostat fan switch to the ON position.  If the 
supply air blower motor does not energize, go to Step 3.

2.

If the blower motor runs with the fan switch in the ON 
position but will not run after the first compressor has 
energized when the fan switch is in the AUTO position, 
check the room thermostat for contact between R and G 
in the AUTO position during calls for cooling.

3.

If the supply air blower motor does not energize when 
the fan switch is set to ON, check that line voltage is 
being supplied to the contacts of the M3, contactor, and 
that the contactor is pulled in.  Check for loose wiring 
between the contactor and the supply air blower motor.

4.

If M3 is pulled in and voltage is supplied to M3, lightly 
touch the supply air blower motor housing.  If it is hot, the 
motor may be off on internal protection.  Cancel  any 
thermostat calls and set the fan switch to AUTO.  Wait for 
the internal overload to reset.  Test again when cool.

5.

If M3 is not pulled in, check for 24 volts at the M3 coil.  If 
24 volts are present at M3 but M3 is not pulled in, 
replace the contactor.

6.

Failing the above, if there is line voltage supplied at M3, 
M3 is pulled in, and the supply air blower motor still does 
not operate, replace the motor.

7.

If 24 volts is not present at M3, check that 24 volts is 
present at the UCB supply air blower motor terminal, 
“FAN”.  If 24 volts is present at the FAN, check for loose 
wiring between the UCB and M3.

8.

If 24 volts is not present at the “FAN” terminal, check for 
24 volts from the room thermostat.  If 24 volts are not 
present from the room thermostat, check for the follow-
ing:

a.

Proper operation of the room thermostat (contact
between R and G with the fan switch in the ON posi-
tion and in the AUTO position during operation
calls).

b.

Proper wiring between the room thermostat and the
UCB, and

c.

Loose wiring from the room thermostat to the UCB

9.

If 24 volts is present at the room thermostat but not at the 
UCB, check for proper wiring between the thermostat 
and the UCB, i.e. that the thermostat G terminal is con-
nected to the G terminal of the UCB, and for loose wir-
ing.

10. If the thermostat and UCB are properly wired, replace 

the UCB.

On calls for cooling, the supply air blower motor is operating
but compressor #1 is not (the room thermostat fan switch is in
the “AUTO” position):

1.

If installed, check the position of the economizer blades.  
If the blades are open, the economizer is providing free 
cooling and the compressors will not immediately oper-
ate.  If both stages of cooling are requested simulta-
neously and the economizer provides free cooling, 
following a short delay compressor #1 will be energized 
unless it is locked out.  If compressor #1 is locked out, 
compressor #2 is energized.  Compressor #2 is always 
energized in place of compressor #1 when compressor 
#1 is requested but locked out.

2.

If no economizer is installed or the economizer is not 
opening to provide free cooling and compressor #1 does 
not energize on a call for cooling, check for line voltage 
at the compressor contactor, M1, and that the contactor 
is pulled in.  Check for loose wiring between the contac-
tor and the compressor.

3.

If M1 is pulled in and voltage is supplied at M1, lightly 
touch the compressor housing.  If it is hot, the compres-
sor may be off on inherent protection.  Cancel any calls 
for cooling and wait for the internal overload to reset.  
Test again when cool.

4.

If M1 is not pulled in, check for 24 volts at the M1 coil.  If 
24 volts are present and M1 is not pulled in, replace the 
contactor.

5.

Failing the above, if voltage is supplied at M1, M1 is 
pulled in, and the compressor still does not operate, 
replace the compressor.

6.

If 24 volts is not present at M1, check for 24 volts at the 
UCB terminal, C1.  If 24 volts is present, check for loose 
wiring between C1 and the compressor contactor.

7.

If 24 volts is not present at the C1 terminal, check for 24 
volts from the room thermostat at the UCB Y1 terminal.  
If 24 volts is not present from the room thermostat, check 
for the following:

a.

24 volts at the thermostat Y1 terminal

b.

Proper wiring between the room thermostat and the
UCB, i.e. Y1 to Y1, Y2 to Y2, and

c.

Loose wiring from the room thermostat to the UCB

8.

If 24 volts is present at the UCB Y1 terminal, the com-
pressor may be out due to an open high-pressure switch, 
low-pressure switch, or freezestat. Check for 24 volts at 
the HPS1, LPS1, and FS1 terminals of the UCB. If a 
switch has opened, there should be a voltage potential 
between the UCB terminals, e.g. if LPS1 has opened, 
there will be a 24-volt potential between the LPS1 termi-
nals.

9.

If 24 volts is present at the UCB Y1 terminal and none of 
the protection switches have opened, the UCB may have 

Summary of Contents for PREDATOR 120

Page 1: ...the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal inj...

Page 2: ...AIR BALANCE 31 CHECKING AIR QUANTITY 31 METHOD ONE 31 METHOD TWO 31 SUPPLY AIR DRIVE ADJUSTMENT 32 OPERATION 33 SEQUENCE OF OPERATIONS OVERVIEW 33 COOLING SEQUENCE OF OPERATION 34 CONTINUOUS BLOWER 34...

Page 3: ...10 REAR DUCT DIMENSIONS 14 11 PREDATOR ROOF CURB DIMENSIONS 15 12 SUNLINE TO PREDATOR TRANSITION ROOF CURBS 15 Fig Pg 13 SIDE PANELS WITH HOLE PLUGS 16 14 RETURN DOWNFLOW PLENUM WITH PANEL 16 15 DISCH...

Page 4: ...MOTOR DOWN SHOT BLOWER PERFORMANCE 25 19 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE 26 Tbl Pg 20 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE 26 21 12 1 2 TON STANDARD MOTOR DOWN SHOT B...

Page 5: ...ow Factory Installed 035 18286 000 Downflow Field Installed 035 18285 000 Horizontal Field Installed 035 18287 000 Motorized Outdoor Air Damper 035 18283 000 Manual Outdoor Air Damper 0 100 035 18282...

Page 6: ...ctor S A 4 Smoke Detector R A 5 Pwr d Conv Outlet A Standard Motor B Standard Motor Economizer Barometric Relief Downflow only C Standard Motor Economizer Power Exhaust Downflow only D Standard Motor...

Page 7: ...p Cond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Cond Coils Phase Mo...

Page 8: ...APS Technicoat Evap Cond Coils Phase Monitor JQ Johnson UNT Controller DFS APS Technicoat Evap Cond Coils Coil Guard JR Johnson UNT Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Gu...

Page 9: ...uard TP Technicoat Evaporator Coil Phase Monitor Dirty Filter Switch TQ Technicoat Evaporator Coil Coil Guard Dirty Filter Switch TR Technicoat Evaporator Coil Phase Monitor Coil Guard Dirty Filter Sw...

Page 10: ...the condenser coil external protective covering prior to operation 4 Remove the toolless doorknobs and instruction packet prior to installation LIMITATIONS These units must be installed in accordance...

Page 11: ...PREDATOR COMPONENT LOCATION Tool less door latch Side entry power and control wiring knockouts Disconnect location optional disconnect switch Filter access 2 throw away Roof curbs in eight and fourte...

Page 12: ...n place when the unit is lifted The condenser coils should be protected from rig ging cable damage with plywood or other suitable material FIGURE 5 UNIT 4 POINT LOAD TABLE 3 UNIT WEIGHTS Model Shippin...

Page 13: ...C o n t r o l E n t r y 7 8 P o w e r E n t r y 2 1 2 L E F T F R O N T F o r D r a i n D i m e n s i o n s S e e D e t a i l B TABLE 6 UNIT CLEARANCES Top Units must be installed outdoors Overhanging...

Page 14: ...13 16 27 1 2 18 21 24 Return Air Supply Air Bottom Condensate Entry FRONT Bottom Power Control and Convenience Outlet Wiring Entries Bottom Gas Supply Entry 12 15 16 LEFT FIGURE 10 REAR DUCT DIMENSION...

Page 15: ...necessary For side duct application remove the side duct covers and install over the bottom duct openings The panels removed from the side duct connections are designed to be reused by securing each...

Page 16: ...h filters are supplied with each unit One inch filters may be used with no modification to the filter racks Filters must always be installed ahead of evaporator coil and must be kept clean or replaced...

Page 17: ...s the replaced wire A disconnect must be utilized for these units Factory installed disconnects are available If installing a disconnect field supplied or York International supplied accessory refer t...

Page 18: ...1 0 0 2 4 i n c l u d e s s u b b a s e 2 T e r m i n a l s A 1 a n d A 2 p r o v i d e a r e l a y o u t p u t t o c l o s e t h e o u t d o o r e c o n o m i z e r d a m p e r s w h e n t h e t h e...

Page 19: ...P size is applicable 0 0 Max Fuse Size Amps Max Fuse Size w Power Exhaust 3 1 4 1 2 2 Actual KW Heater Amps Min Circuit Ampacity Amps 380 7 1 54 0 0 8 MCA w Power Exhaust Amps Pwr Exh Motor Pwr Conv O...

Page 20: ...LA Max Fuse Size w Power Exhaust FLA FLA Heater Amps Min Circuit Ampacity Amps MCA w Power Exhaust Amps Max Fuse Size Amps Pwr Exh Motor Pwr Conv Outlet Electric Heater Model No Maximum HACR breaker o...

Page 21: ...field installed accessory If factory installed refer to the instructions included with the outdoor air hood to com plete the assembly Field installed Motorized Outdoor Damper accessories include comp...

Page 22: ...esired minimum damper position has been attained ENTHALPY SET POINT ADJUSTMENT The enthalpy set point may now be set by selecting the desired set point shown in the Enthalpy Set Point Adjustment Figur...

Page 23: ...C C B B A A CONTROL CURVE CONTROL POINT APPROX 0 F 0 C AT 50 RH A D C B 63 17 73 23 70 21 67 19 FIGURE 21 HONEYWELL ECONOMIZER CONTROL W7212 N1 N P1 P EXH Set EXH Min Pos IAQ Max IAQ IAQ Min Free Coo...

Page 24: ...per rotation to oper ate correctly Units are properly phased at the fac tory Do not change the internal wiring to make the blower condenser fans or compressor rotate cor rectly TABLE 16 SUPPLY AIR LIM...

Page 25: ...ariable pitch motor sheave where 0 Turns Open is fully closed W Watts TABLE 18 7 1 2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP CFM W BHP CFM W BHP CFM W BHP...

Page 26: ...fully closed W Watts TABLE 20 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP 0 4 4965 3485 3 74 4875 3150 3...

Page 27: ...ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP 0 4 5994 5400 5 79 5565 4369 4 69 5488 4169 4 47 5264 3599 3 86 4990 3085 3 31 4738 2812 3 02 0 6 5824 5216 5 59...

Page 28: ...refers to the setting of the variable pitch motor sheave where 0 Turns Open is fully closed W Watts TABLE 24 7 1 2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP...

Page 29: ...fully closed W Watts TABLE 26 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP 0 4 4965 3485 3 74 4875 3150 3...

Page 30: ...iable pitch motor sheave where 0 Turns Open is fully closed W Watts TABLE 28 12 1 2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE ESP TURNS OPEN 0 1 2 3 4 5 CFM W BHP CFM W BHP CFM W BHP CFM W BHP C...

Page 31: ...in the supply air duct as close to the outlet of the unit as possible 2 Using the whole drilled in step 1 insert eight inches of 1 4 inch metal tubing into the airflow of the return and supply air duc...

Page 32: ...DD for the new motor sheave 4 000 CFM 3 800 CFM Use Table 31 to locate the DD nearest to 4 21 in Close the sheave to 1 turn open New BHP 3 Speed increase BHP at 3 800 CFM 3 Speed increase Original BH...

Page 33: ...3900 0 23 0 04 0 19 0 20 0 23 0 24 0 28 4100 0 25 0 04 0 21 0 22 0 25 0 26 0 31 4300 0 28 0 05 0 23 0 24 0 28 0 29 0 34 4500 0 30 0 05 0 25 0 26 0 30 0 31 0 37 4700 0 33 0 05 0 28 0 29 0 33 0 34 0 40...

Page 34: ...ol circuit from R to G and Y1 is com pleted The UCB energizes the blower motor if the fan switch on the room thermostat is set in the AUTO position and drives the economizer dampers from fully closed...

Page 35: ...ration the UCB will lock out the associated compressor and flash a code 37 If the other compressor is inactive the condenser fans will be de energized LOW AMBIENT COOLING To determine when to operate...

Page 36: ...l times If the temperature limit opens three times within one hour it will lock on the indoor blower motor and a flash code is initi ated See Table 37 SAFETY CONTROLS The UCB monitors the temperature...

Page 37: ...will energize after the built in time delay five minutes 4 The second stage of the thermostat will energize second stage compressor if needed POST START CHECK LIST 1 Verify proper system pressures for...

Page 38: ...9 105 5 7 8 1 10 6 13 1 15 5 110 5 5 7 7 10 0 12 2 115 6 9 8 9 TABLE 36 12 5 TON STANDARD EFFICIENCY SUPERHEAT CHARGING Outdoor Temp F Superheat at Compressor Suction F Airflow 5000 CFM Indoor WB Tem...

Page 39: ...sion a 1 flash flash code is not used Current alarms are flashed on the UCB LED The alarm his tory can be checked by pressing and releasing the ALARMS button on the UCB The UCB will cycle through the...

Page 40: ...ashes Compressors Locked Out Because The Economizer Is Using Free Cooling 12 Flashes Fan Overload Switch Trip Not Applicable On This Unit 13 Flashes Compressor Held Off Due To Low Voltage 14 Flashes E...

Page 41: ...f the thermostat and UCB are properly wired replace the UCB On calls for cooling the supply air blower motor is operating but compressor 1 is not the room thermostat fan switch is in the AUTO position...

Page 42: ...or this programming 15 If none of the above corrected the error test the integrity of the UCB Disconnect the C1 terminal wire and jumper it to the Y1 terminal DO NOT jump the Y1 to C1 termi nals If th...

Page 43: ...ll does not operate replace the compressor 6 If 24 volts is not present at M1 check for 24 volts at the UCB terminal C1 If 24 volts is present check for loose wiring between C1 and the compressor cont...

Page 44: ...trol may have faulted and is not returning the 24 volts to the Y1 ECON terminal even though the economizer is not providing free cooling To test the economizer control disconnect the Mate N Locks and...

Reviews: