Outdoor Fan Assembly -

 The outdoor fan shall be of the 

direct-driven propeller type, discharge air vertically, have 
aluminum blades riveted to corrosion resistant steel spider 
bracket and shall be statically balanced for smooth operation. 
The outdoor fan motor shall be totally enclosed with 
permanently lubricated bearings and internally protected 
against overload conditions.

REFRIGERANT COMPONENTS

Protected Compressor -

 The compressor shall be a fully 

hermetic type, direct drive compressor, that is internally pro-
tected against high pressure and temperature. This is 
accomplished by the simultaneous operation of high pres-
sure internal relief valve and a temperature sensor which 
protect the compressor if undesirable operating conditions 
occur. The hermetic motor shall be suction gas cooled and 
have a voltage range of +/- 10% of the unit nameplate volt-
age. Compressors shall have internal isolation and sound 
muffling to minimize vibration and noise, and be externally 
isolated on a dedicated, independent mounting.

Indoor Coils -

 Indoor coils shall be of the direct expansion, 

draw through design and have aluminum plate fins mechani-
cally bonded to seamless internally enhanced tin-coated 
copper tubes with all joints brazed.

Condensate Pan -

 A corrosion-resistant, long-lasting, water-

tight pan is positioned below the indoor coil to collect and 
drain all condensate, preventing build-up of stagnant con-
densate. The condensate pan conforms to ASHRAE 62-89 
standards (Ventilation for Acceptable Indoor Air Quality).

Condensate Drain - 

The 3/4 inch NPT female connection is 

rigidly mounted to assure proper fit and leak tight seal.

Outdoor Coils -

 Outdoor coils shall have aluminum plate 

fins mechanically bonded to seamless internally enhanced 
copper tubes with all joints brazed, and be a draw through 
design.

Refrigerant Circuit and Refrigerant Safety Components 
shall include:

 Thermal expansion devices (TXVs) shall be 

factory mounted and provided, Filter/strainer to eliminate any 
foreign matter, reversing valves to control refrigerant flow.

GAS HEATING SECTION

Heat exchanger and exhaust system shall be constructed of 
corrosion-resistant materials and shall be designed with 
induced draft combustion with post purge logic and redundant 
main gas valve. The heat exchanger shall be of the tubular 
type, constructed of stainless steel for corrosion resistance and 
allowing minimum mixed air entering temperature of 40 °

F. 

Burners shall be of the in-shot type, constructed of 
aluminumized steel. All gas piping shall enter the unit cabinet at 
a single location through either the side or bottom, without any 
field modifications. An integrated control board shall provide 
timed control of indoor fan functioning and burner ignition. 
Heating section shall be provided with the following minimum 
protection:

a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(s) (manual reset).
d. Flame proving controls.

All gas heat models will meet California requirement for 
emissions of less than 40 nanograms per Joule (California 
requirement on single phase models only).

CONTROLS

Simple Control Circuit -

 Field thermostat wiring connects to 

color coded leads using twist on wire connections. Cooling 
controls use contactor and relays for simple application and 
troubleshooting. Mate-n-lock plug connectors are used. 
Heating controls consist of direct spark ignition control and 
demand defrost heat pump control. The electrical control box 
is not located in the compressor compartment. The controls 
are mounted to allow the separate access panel to be 
removed for trouble shooting and maintenance without 
affecting the normal system operating pressures. All wiring 
internal to the unit is color/number coded.

Pressure Switches -

 A high pressure switch is standard in 

all units. When abnormal conditions are sensed through the 
pressure switch, the unit will lock out preventing any further 
operation until reset or problem is corrected.

Factory Testing -

 Installation time and costs are reduced by 

easy power and control wiring connections. All units are 
completely wired, charged with R-410A and tested prior to 
shipment. Test stations using a state-of-the-art computerized 
process system shall be used to insure product quality. 
Refrigerant charge and component part numbers are verified 
via computer bar code scans during assembly. Vital run test 
statistics such as system pressure, motor currents, air veloc-
ity and temperature, unit vibration, and gas system safeties 
are monitored and recorded by the system to insure unit per-
formance. This data could be provided by serial number 
tracking if requested.

Spark To Burner Ignition -

 No pilot assembly required, which 

provides more consistent ignition in gas heating mode. This 
ignition is highly reliable, durable and eliminates nuisance 
lockouts.

Summary of Contents for PHG6A24

Page 1: ...t and tested prior to shipment Test sta tions using a state of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via com...

Page 2: ...ed The electrical control box is not located in the compressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affect...

Page 3: ...minal Capacity etc 9 Revision Level A original release B second release Examples PHG4B421002X1 is a dual fuel 14 SEER 3 1 2 ton large cabinet single stage heat 100 000 BTU gas heat 230 volt single pha...

Page 4: ...e to round duct adapter Adapters are preformed and designed to fit over current horizontal duct openings on the base unit Transition is from rectangle to 12 round for the 1AK0110 kit and from rectangl...

Page 5: ...it Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPT female ridged mount connection Durable Finish The cabinet shall be is made of G90 galva ni...

Page 6: ...l be of the tubular type constructed of stainless steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 F Burners shall be of the in shot type constructed of aluminu...

Page 7: ...burners 2 3 2 3 2 3 2 3 2 3 4 2 3 4 No stages 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 20 50 20 50 25 55 25...

Page 8: ...gal Centrifugal Centrifugal Centrifugal Motor HP each 1 3 1 2 1 3 1 2 1 2 3 4 3 4 3 4 1 RPM 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max Frame size 48 48 48 48 48 48 Filters Filter Size A A B...

Page 9: ...6 6 9 0 7 1 7 9 8 5 7 9 K W 1 71 1 71 1 70 1 69 1 68 1 64 1 64 1 64 1 63 1 62 1 57 1 56 1 58 1 57 1 55 COOLING PERFORMANCE DATA 2 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A24 CONDENSER ENTERING AIR...

Page 10: ...9 2 8 9 10 1 8 2 11 6 8 8 8 1 10 3 9 1 K W 2 55 2 54 2 54 2 53 2 51 2 54 2 53 2 53 2 53 2 50 2 53 2 51 2 53 2 53 2 50 COOLING PERFORMANCE DATA 2 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A30 CONDEN...

Page 11: ...5 16 1 14 3 14 9 11 2 15 7 17 5 16 6 17 4 12 8 K W 2 68 2 67 2 68 2 66 2 64 2 62 2 61 2 63 2 61 2 58 2 56 2 56 2 58 2 56 2 53 COOLING PERFORMANCE DATA 3 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B36...

Page 12: ...3 19 1 16 9 17 9 12 8 22 7 19 9 18 9 20 4 14 1 K W 3 04 3 03 3 02 3 02 2 97 3 03 3 02 3 03 3 02 2 98 3 03 3 02 3 04 3 03 3 00 COOLING PERFORMANCE DATA 3 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B4...

Page 13: ...3 2 20 0 17 4 20 8 14 3 24 4 22 1 18 8 23 3 16 0 K W 4 16 4 16 4 15 4 15 4 09 4 11 4 12 4 14 4 11 4 07 4 06 4 08 4 12 4 06 4 04 COOLING PERFORMANCE DATA 4 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B48...

Page 14: ...6 7 24 9 21 6 23 2 16 7 27 1 24 7 22 6 24 6 17 6 K W 4 79 4 77 4 78 4 74 4 70 4 78 4 77 4 78 4 75 4 71 4 78 4 77 4 79 4 75 4 72 COOLING PERFORMANCE DATA 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B60...

Page 15: ...DOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 550 750 950 MBH COP KW MBH COP KW MBH COP KW 60 60 28 9 4 46 1 83 30 1 4 96 1 69 31 4 5 51 1 55 70 27 5 3 87 2 01 28 7 4 30 1 86 29 9 4 80 1 71 80 26 2 3...

Page 16: ...IT AIR TEMP ENTERING INDOOR COIL ID CFM 750 950 1150 MBH COP KW MBH COP KW MBH COP KW 60 60 38 5 4 76 2 13 37 5 4 60 2 22 36 6 4 44 2 30 70 36 5 4 15 2 34 35 7 3 99 2 44 34 8 3 83 2 55 80 34 6 3 63 2...

Page 17: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBH COP KW MBH COP KW MBH COP KW 60 60 43 9 4 52 2 53 43 0 4 45 2 58 42 0 4 37 2 64 70 42 1 4 01 2 76 41 2 3 94 2 82 40 3 3 87 2 88 80 4...

Page 18: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1070 1270 1470 MBH COP KW MBH COP KW MBH COP KW 60 60 47 0 4 42 2 80 46 5 4 36 2 89 46 1 4 30 2 98 70 44 7 3 86 3 07 44 3 3 81 3 17 43 9 3 76 3 26 80 4...

Page 19: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1300 1500 1700 MBH COP KW MBH COP KW MBH COP KW 60 60 61 4 4 63 3 46 60 8 4 52 3 56 60 1 4 42 3 68 70 58 7 4 04 3 82 58 2 3 93 3 97 57 7 3 82 4 12 80 56...

Page 20: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1530 1730 1930 MBH COP KW MBH COP KW MBH COP KW 60 60 73 6 4 77 4 15 73 1 4 56 4 18 72 5 4 37 4 21 70 70 6 4 22 4 53 70 2 4 03 4 60 69 8 3 85 4 67 80 67...

Page 21: ...within a confined space and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge...

Page 22: ...ne Frequency Hz 125 250 500 1000 2000 4000 8000 PHG6A24 70 3 64 7 59 2 59 8 58 1 54 3 49 2 43 2 PHG6A30 69 0 57 5 58 0 58 0 63 8 53 2 47 6 49 7 PHG6B36 72 8 60 1 62 5 60 4 64 5 58 8 53 0 46 0 PHG6B42...

Page 23: ...453 28 15 161 102 90 100 PHG6B36065 503 498 29 14 176 122 104 96 PHG6B36100 510 505 29 14 178 123 109 95 PHG6B42065 537 532 29 14 190 132 112 98 PHG6B42100 539 534 29 14 191 133 109 101 PHG6B48065 556...

Page 24: ...237 192 Low Cool A 902 822 764 713 669 612 557 513 480 437 B 855 734 669 615 572 509 454 418 385 334 C 827 678 611 545 504 448 396 356 311 263 D 675 546 466 404 347 277 205 160 126 80 High Heat A 118...

Page 25: ...A 1126 1067 1006 945 860 777 718 664 608 551 B 1015 952 884 802 709 646 582 528 467 402 C 955 886 821 721 642 584 508 453 391 324 D 910 836 774 661 592 537 453 396 333 265 Low Heat A 970 902 837 742...

Page 26: ...704 1667 1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low...

Page 27: ...4 930 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 152...

Page 28: ...75 1329 1280 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1...

Page 29: ...06 0 02 0 16 1300 0 07 0 03 0 17 1400 0 08 0 04 0 18 42 3 5 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08...

Page 30: ...N REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCON...

Page 31: ...roducts 31 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOF...

Page 32: ...change without notice Published in U S A 5331896 YTG C 1017 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 5331896 YTG B 0817 York International Corp 5005 York Drive Norman OK 7...

Reviews: