TECHNICAL GUIDE
SINGLE PACKAGE  
HEAT PUMP / GAS HEAT
16 SEER – R-410A – 208/230V - 1 PHASE 
2 THRU 5 NOMINAL TONS 
50 THRU 125 MBH HEAT INPUT

MODELS: PHG6*24 THRU 60

Due to continuous product improvement, specifications 
are subject to change without notice.

Visit us on the web at  

www.upgnet.com and www.york.com

Additional rating information can be found at: 

www.ahridirectory.org

WARRANTY SUMMARY*

Extended 10-Years limited parts and compressor warranty
Lifetime gas heat exchanger warranty with registration.

* Extended warranty requires online registration within 90 days of purchase for 
replacement or closing for new home purchase. See limited warranty certificate 
in User’s Information Manual for details.

Š

Š

 

5331896-YTG-C-1017

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

These packaged duel fuel cooling/gas heating/heat pumps are 
designed for outdoor installation. Only utility and duct 
connections are required at the point of installation.

FEATURES

Operating Efficiency 

- All PHG6 models provide a minimum 

AFUE of 81.0% in gas heating and 16.0 SEER, 12.5 or 12.0 
EER and 8.2 HSPF ratings for heat pump cooling/heating 
operation. All models meet California Low-Nox requirements 
of 40 ng/joule emission level for Air Quality Management Dis-
tricts.

On Site Flexibility -

 All model sizes use a compact design 

cabinet in one of two footprints. This provides installer flexi-
bility for placing the proper capacity unit on curbs or pads 
with the smallest footprint after the internal load has been 
determined. Field convertible duct connections from side 
shot to down shot allows the installer to have greater flexibil-
ity with less inventory.

Lower Installation Cost -

 Installation time and costs are 

reduced by easy power and control wiring connections. The 
small base dimension means less space is required on the 
ground or roof. All units are completely wired, charged with 
R-410A refrigerant and tested prior to shipment. Test sta-
tions using a state-of-the-art computerized process system 
are used to insure product quality. Refrigerant charge and 
component part numbers are verified via computers during 
assembly. Vital run test statistics such as system pressure, 
motor currents, air velocity and temperature, unit vibration, 
and gas system safeties are monitored and recorded by the 
system to insure unit performance. Equal size side supply 
and return duct connections allow easy connection of ducts 
to match low crawl spaces without transition pieces.

Utility Connections Made Easy -

 Gas and electric utility 

access provided through the bottom or the side of the unit. 
Utility connections can be made quickly and with a minimum 
amount of field labor. A field supplied and field installed elec-
trical disconnect switch must be installed.

Convertible Airflow Design -

 The bottom duct openings are 

covered when they leave the factory, ready to be used for a 
side supply/side return application. If a bottom supply/bottom 
return application is desired, simply remove the two panels 
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and 
no accessory panel is necessary. Convertible airflow design 
allows maximum field flexibility and minimum inventory.

Condensate Pan -

 A corrosion-resistant, long-lasting, water-

tight pan is positioned below the indoor coil to collect and 
drain all condensate, preventing build-up of stagnant con-
densate. The condensate pan conforms to ASHRAE 62-89 
standards (Ventilation for Acceptable Indoor Air Quality).

Condensate Drain -

 The 3/4 inch NPT female connection is 

rigidly mounted to assure proper fit and leak tight seal.

Durable Finish -

 The cabinet is made of G90 galvanized 

steel with a powder paint coating for appearance and protec-
tion. The pre-treated galvanized steel provides a better paint-
to-steel bond, which resists corrosion and rust creep. Pow-
der paint finish insures less fading when exposed to sunlight, 
and provides superior corrosion resistance (1000 hour salt 
spray tested).

Continued on next page.

Summary of Contents for PHG6 24 Series

Page 1: ...t and tested prior to shipment Test sta tions using a state of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via com...

Page 2: ...ed The electrical control box is not located in the compressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affect...

Page 3: ...minal Capacity etc 9 Revision Level A original release B second release Examples PHG4B421002X1 is a dual fuel 14 SEER 3 1 2 ton large cabinet single stage heat 100 000 BTU gas heat 230 volt single pha...

Page 4: ...e to round duct adapter Adapters are preformed and designed to fit over current horizontal duct openings on the base unit Transition is from rectangle to 12 round for the 1AK0110 kit and from rectangl...

Page 5: ...it Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPT female ridged mount connection Durable Finish The cabinet shall be is made of G90 galva ni...

Page 6: ...l be of the tubular type constructed of stainless steel for corrosion resistance and allowing minimum mixed air entering temperature of 40 F Burners shall be of the in shot type constructed of aluminu...

Page 7: ...burners 2 3 2 3 2 3 2 3 2 3 4 2 3 4 No stages 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 20 50 20 50 25 55 25...

Page 8: ...gal Centrifugal Centrifugal Centrifugal Motor HP each 1 3 1 2 1 3 1 2 1 2 3 4 3 4 3 4 1 RPM 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max 1200 Max Frame size 48 48 48 48 48 48 Filters Filter Size A A B...

Page 9: ...6 6 9 0 7 1 7 9 8 5 7 9 K W 1 71 1 71 1 70 1 69 1 68 1 64 1 64 1 64 1 63 1 62 1 57 1 56 1 58 1 57 1 55 COOLING PERFORMANCE DATA 2 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A24 CONDENSER ENTERING AIR...

Page 10: ...9 2 8 9 10 1 8 2 11 6 8 8 8 1 10 3 9 1 K W 2 55 2 54 2 54 2 53 2 51 2 54 2 53 2 53 2 53 2 50 2 53 2 51 2 53 2 53 2 50 COOLING PERFORMANCE DATA 2 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6A30 CONDEN...

Page 11: ...5 16 1 14 3 14 9 11 2 15 7 17 5 16 6 17 4 12 8 K W 2 68 2 67 2 68 2 66 2 64 2 62 2 61 2 63 2 61 2 58 2 56 2 56 2 58 2 56 2 53 COOLING PERFORMANCE DATA 3 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B36...

Page 12: ...3 19 1 16 9 17 9 12 8 22 7 19 9 18 9 20 4 14 1 K W 3 04 3 03 3 02 3 02 2 97 3 03 3 02 3 03 3 02 2 98 3 03 3 02 3 04 3 03 3 00 COOLING PERFORMANCE DATA 3 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B4...

Page 13: ...3 2 20 0 17 4 20 8 14 3 24 4 22 1 18 8 23 3 16 0 K W 4 16 4 16 4 15 4 15 4 09 4 11 4 12 4 14 4 11 4 07 4 06 4 08 4 12 4 06 4 04 COOLING PERFORMANCE DATA 4 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B48...

Page 14: ...6 7 24 9 21 6 23 2 16 7 27 1 24 7 22 6 24 6 17 6 K W 4 79 4 77 4 78 4 74 4 70 4 78 4 77 4 78 4 75 4 71 4 78 4 77 4 79 4 75 4 72 COOLING PERFORMANCE DATA 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PHG6B60...

Page 15: ...DOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 550 750 950 MBH COP KW MBH COP KW MBH COP KW 60 60 28 9 4 46 1 83 30 1 4 96 1 69 31 4 5 51 1 55 70 27 5 3 87 2 01 28 7 4 30 1 86 29 9 4 80 1 71 80 26 2 3...

Page 16: ...IT AIR TEMP ENTERING INDOOR COIL ID CFM 750 950 1150 MBH COP KW MBH COP KW MBH COP KW 60 60 38 5 4 76 2 13 37 5 4 60 2 22 36 6 4 44 2 30 70 36 5 4 15 2 34 35 7 3 99 2 44 34 8 3 83 2 55 80 34 6 3 63 2...

Page 17: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBH COP KW MBH COP KW MBH COP KW 60 60 43 9 4 52 2 53 43 0 4 45 2 58 42 0 4 37 2 64 70 42 1 4 01 2 76 41 2 3 94 2 82 40 3 3 87 2 88 80 4...

Page 18: ...UTDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1070 1270 1470 MBH COP KW MBH COP KW MBH COP KW 60 60 47 0 4 42 2 80 46 5 4 36 2 89 46 1 4 30 2 98 70 44 7 3 86 3 07 44 3 3 81 3 17 43 9 3 76 3 26 80 4...

Page 19: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1300 1500 1700 MBH COP KW MBH COP KW MBH COP KW 60 60 61 4 4 63 3 46 60 8 4 52 3 56 60 1 4 42 3 68 70 58 7 4 04 3 82 58 2 3 93 3 97 57 7 3 82 4 12 80 56...

Page 20: ...TDOOR UNIT AIR TEMP ENTERING INDOOR COIL ID CFM 1530 1730 1930 MBH COP KW MBH COP KW MBH COP KW 60 60 73 6 4 77 4 15 73 1 4 56 4 18 72 5 4 37 4 21 70 70 6 4 22 4 53 70 2 4 03 4 60 69 8 3 85 4 67 80 67...

Page 21: ...within a confined space and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge...

Page 22: ...ne Frequency Hz 125 250 500 1000 2000 4000 8000 PHG6A24 70 3 64 7 59 2 59 8 58 1 54 3 49 2 43 2 PHG6A30 69 0 57 5 58 0 58 0 63 8 53 2 47 6 49 7 PHG6B36 72 8 60 1 62 5 60 4 64 5 58 8 53 0 46 0 PHG6B42...

Page 23: ...453 28 15 161 102 90 100 PHG6B36065 503 498 29 14 176 122 104 96 PHG6B36100 510 505 29 14 178 123 109 95 PHG6B42065 537 532 29 14 190 132 112 98 PHG6B42100 539 534 29 14 191 133 109 101 PHG6B48065 556...

Page 24: ...237 192 Low Cool A 902 822 764 713 669 612 557 513 480 437 B 855 734 669 615 572 509 454 418 385 334 C 827 678 611 545 504 448 396 356 311 263 D 675 546 466 404 347 277 205 160 126 80 High Heat A 118...

Page 25: ...A 1126 1067 1006 945 860 777 718 664 608 551 B 1015 952 884 802 709 646 582 528 467 402 C 955 886 821 721 642 584 508 453 391 324 D 910 836 774 661 592 537 453 396 333 265 Low Heat A 970 902 837 742...

Page 26: ...704 1667 1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low...

Page 27: ...4 930 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 152...

Page 28: ...75 1329 1280 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1...

Page 29: ...06 0 02 0 16 1300 0 07 0 03 0 17 1400 0 08 0 04 0 18 42 3 5 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08...

Page 30: ...N REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCON...

Page 31: ...roducts 31 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOF...

Page 32: ...change without notice Published in U S A 5331896 YTG C 1017 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 5331896 YTG B 0817 York International Corp 5005 York Drive Norman OK 7...