background image

heat pump CFM selections. Find the recommended system air-
flow in the table for the installed Air Handler model.

Moving up the table, identify the “COOL” tap jumper position (“A”,
“B”, “C” or No Jumper). Go to the connector board and set the
jumper horizontally for the “COOL” tap position. See Figure 8 for
the layout of the connector board.

NOTE: No jumper indicates the jumper should be removed or

placed in the “store” position (see Figure 8).

Return to Table 1 and move to the right to identify the “ADJ” tap
jumper position. Go to the connector board and set the jumper
horizontally for the “ADJ” tap position (refer to Figure 8). Again,
“No jumper” indicates the jumper should be removed or placed in
the “store” position.

To Set Heat Pump CFM:

The heat pump CFM setting is the same as the cooling CFM. No
additional CFM setting is required, however, you must remove the
jumper at the bottom of the connector board labeled “Remove for
Heat Pump” for heat pump operation. (See Figure 8.)

To Set Electric Heat CFM:

The blower speed required for the Electric Heat is different than
cooling. Refer to the label on the blower housing or Table 1 for the
possible CFM selections. Refer to Table 4 for the minimum
required CFM for the electric heater installed. Find the desired
airflow in Table 1. Moving up the table, identify the “HEAT” tap
jumper position. Go to the connector board and set the jumper
horizontally for the “HEAT” tap position.

CAUTION: DO NOT change the “ADJ” tap position on the con-

nector board as this will change your cooling CFM
previously selected.

To Set Delay Profile:

Every variable speed air handler has multiple “blower off delay”
profiles to optimize system performance and efficiency.

Refer to Table below for the type of system installed. set the
“DELAY” jumper tap position horizontally on the connector board
for the appropriate setting.

To Install Humidistat Accessory:

If the system is used with a humidistat accessory, connect the field
wires to screw terminals “R” and “BK” on the connector board.
See Figures 10 or 11. 

IMPORTANT: Remove the jumper at the bottom of the connector
board marked “Remove for Humidistat” for humidistat operation.

MAINTENANCE

One permanent high velocity washable filter is provided with each
filter rack. This filter may be cleaned with a vacuum cleaner or
washed with warm water using a mild detergent. Do not use a
high velocity water stream. No coating is required. Install filter with
cloth mesh towards blower. Never turn a dirty filter to allow air flow
in the opposite direction.

Filters must be cleaned when they become dirty. Inspect at least
once per month. The frequency of cleaning depends upon the
hours of operation and the local atmospheric conditions. Clean
filters keep unit efficiency high.

COIL CLEANING

If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.

Delay Profile

“DELAY” Tap

Unit Type

Jumper at “A”

System wo/TXV or wo/ S.V.

Jumper at “B”

System w/TXV or w/ S.V.

Jumper at “C”

Two Stage Condensor

No Jumper

Test Mode

TXV= Thermal Expansion Valve
SV= Solenoid Valve

535.03-N1Y

Unitary Products Group

7

Summary of Contents for N1VSD10A06

Page 1: ...be made in writing See Form 50 15 NM for more information REFERENCE This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching...

Page 2: ...an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the coil as is specified by most local building codes If the coil is provided w...

Page 3: ...uction 1 Attach coil casing to blower section in a way appropriate to indoor unit application See Form 535 01 N5V for G HC or G FC Coils and Form 535 01 N6V for G HT Coils Confirm the orifice size bef...

Page 4: ...nnect Line Sizes A B C D E F G H J K L M Liquid Vapor Liquid Vapor D10 024 16 1 4 1 12 1 8 3 7 8 12 1 8 14 1 4 22 3 4 54 1 2 3 1 2 1 1 2 1 3 4 3 1 2 F 6 F 11 5 16 5 8 030 14 1 4 22 3 4 54 1 2 3 1 4 6...

Page 5: ...the use of smaller size power wire but will require a greater number of wires To accomplish this field con version refer to Figure 5 Dual Supply as an example and proceed as follows 1 Remove the jumpe...

Page 6: ...thermostat used has an adjustable heat anticipator see Table below for proper setting BLOWER SPEED SELECTION All variable speed air handlers N VS are designed to deliver constant CFM regardless of the...

Page 7: ...lected To Set Delay Profile Every variable speed air handler has multiple blower off delay profiles to optimize system performance and efficiency Refer to Table below for the type of system installed...

Page 8: ...ION HEAT Tap Jumper at A Jumper at B Jumper at C No Jumper Cubic Foot Per Minute CFM 1300 1300 1450 1600 TABLE 1 CFM TAP SELECTION BLOWER SIZE TRANFORMER KIT MIN CIRCUIT AMPACITY MAX T D FUSE SIZE MIN...

Page 9: ...ABLE 4 ELECTRICAL DATA HEATER ACCESSORY FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 1 KW MBH CONVERSIONS Blower Size Heater Accessory Model No Field Wiring 2...

Page 10: ...W 6 6 C Y R G CONNECTOR BOARD X or L B or C 6 0 5 3 O X HUMIDISTAT JUMPER MUST BE REMOVED DEHUMIDIFICATION CONTROL CONNECTION N O T U S E D NO T US E D B K THE RMOS TA T G W 1 X or L C or B R WIRE NU...

Page 11: ...IRE NUT RED OUTDOOR UNIT R C Y G O X W W1 W2 HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATION CONTROL CONNECTION R C Y 1 Y 2 Y2 OUT NO Y 1 Y 2 W 2 TWO STAGE COOL ING MUST BE USED BRN YEL...

Page 12: ...USED WITH A HEAT PUMP UNIT HEAT PUMP MODELS E FH THERMO STAT G X or L R O UTDO OR HEATPUMP R C Y G O X W W1 W2 INDOOR UNIT CONNECTOR BOARD HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATIO...

Reviews: