background image

LIMITATIONS

These units must be wired and installed in accordance with all
national and local safety codes.

Voltage limits are as follows:

Air flow must be within the minimum and maximum limits ap-
proved for electric heat, evaporator coils and outdoor units.

CLEARANCE

Clearance must be provided for:

1. Refrigerant piping and connections - minimum 12" 
    recommended.

2. Maintenance and servicing access - minimum 36" from  front
    of unit recommended for blower motor / coil replacement.

3. Condensate drain line.

4. Filter removal - minimum 36" recommended.

LOCATION

Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the
following in choosing a suitable location:

1. Select a location with adequate structural support, space for

service access, clearance for air return and supply duct
connections.

2. Normal operating sound levels may be objectionable if the air

handler is placed directly over some rooms such as bed-
rooms, study, etc.  A flexible duct collar is recommended as
shown in Figure 2 to minimize noise.

3. Precautions should be taken to locate the unit and ductwork

so that supply air does not short circuit to the return air.

4. If evaporator coil is used, locate to permit installation of a

trapped condensate line to an open drain.

5. When an evaporator coil is installed in an attic or above a

finished ceiling, an auxiliary drain pan should be provided
under the coil as is specified by most local building codes.

If the coil is provided with a secondary drain it should be
trapped and piped to a location that will give the occupant a
visual warning that the primary drain is clogged. If the secon-
dary drain is not used it must be capped.

6. If unit is located in an area of high humidity, ie. an uncondi-

tioned garage or attic, nuisance sweating of casing may
occur. On these installations a wrap of 2"  fiberglass insulation
with vinyl vapor barrier should be used.

7. Proper electrical supply must be available.

8. Clearances must also be taken into consideration, and pro-

vided for as follows:

a. Maintenance and servicing thru the front or access side of

unit with both sides and rear of unit having zero inch
clearance.

b. When no electric heat is used, the unit as well as all duct

work and plenum are designed for zero clearance to
combustible material.

c. If electric heat is used or anticipated, be sure a minimum

clearance of one inch is allowed on all sides of the supply

FLEXIBLE
DUCT
COLLAR

MINIMUM CLEARANCE
OF 1" ALL SIDES

  3’

FIGURE 2 - Duct Clearance

FIGURE 3 - Typical Wiring and Piping

Air Handler 

Voltage

*Normal Operating

Voltage Range

208/230 (06)

187-253

*Utilization range “A” in accordance with ARI Std. 110.

Entering Air Temperature Limits

Wet Bulb Temp. 

°

F

Dry Bulb Temp. 

°

F

MIN.

MAX.

MIN.

MAX.

57

72

65

95

535.03-N1Y

2

Unitary Products Group

Summary of Contents for N1VSD10A06

Page 1: ...be made in writing See Form 50 15 NM for more information REFERENCE This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching...

Page 2: ...an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the coil as is specified by most local building codes If the coil is provided w...

Page 3: ...uction 1 Attach coil casing to blower section in a way appropriate to indoor unit application See Form 535 01 N5V for G HC or G FC Coils and Form 535 01 N6V for G HT Coils Confirm the orifice size bef...

Page 4: ...nnect Line Sizes A B C D E F G H J K L M Liquid Vapor Liquid Vapor D10 024 16 1 4 1 12 1 8 3 7 8 12 1 8 14 1 4 22 3 4 54 1 2 3 1 2 1 1 2 1 3 4 3 1 2 F 6 F 11 5 16 5 8 030 14 1 4 22 3 4 54 1 2 3 1 4 6...

Page 5: ...the use of smaller size power wire but will require a greater number of wires To accomplish this field con version refer to Figure 5 Dual Supply as an example and proceed as follows 1 Remove the jumpe...

Page 6: ...thermostat used has an adjustable heat anticipator see Table below for proper setting BLOWER SPEED SELECTION All variable speed air handlers N VS are designed to deliver constant CFM regardless of the...

Page 7: ...lected To Set Delay Profile Every variable speed air handler has multiple blower off delay profiles to optimize system performance and efficiency Refer to Table below for the type of system installed...

Page 8: ...ION HEAT Tap Jumper at A Jumper at B Jumper at C No Jumper Cubic Foot Per Minute CFM 1300 1300 1450 1600 TABLE 1 CFM TAP SELECTION BLOWER SIZE TRANFORMER KIT MIN CIRCUIT AMPACITY MAX T D FUSE SIZE MIN...

Page 9: ...ABLE 4 ELECTRICAL DATA HEATER ACCESSORY FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 1 KW MBH CONVERSIONS Blower Size Heater Accessory Model No Field Wiring 2...

Page 10: ...W 6 6 C Y R G CONNECTOR BOARD X or L B or C 6 0 5 3 O X HUMIDISTAT JUMPER MUST BE REMOVED DEHUMIDIFICATION CONTROL CONNECTION N O T U S E D NO T US E D B K THE RMOS TA T G W 1 X or L C or B R WIRE NU...

Page 11: ...IRE NUT RED OUTDOOR UNIT R C Y G O X W W1 W2 HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATION CONTROL CONNECTION R C Y 1 Y 2 Y2 OUT NO Y 1 Y 2 W 2 TWO STAGE COOL ING MUST BE USED BRN YEL...

Page 12: ...USED WITH A HEAT PUMP UNIT HEAT PUMP MODELS E FH THERMO STAT G X or L R O UTDO OR HEATPUMP R C Y G O X W W1 W2 INDOOR UNIT CONNECTOR BOARD HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATIO...

Reviews: