ELECTRICAL CONNECTIONS

Wire Transformer Kit or Electric Heater per wiring diagram on the
accessory. Typical field wiring is shown in Figures  9, 10 and 11.

CAUTION:  Break off tab must be removed from 2HW electric

heat control boards for variable speed operation. See
Figure 6.

NOTE: All wiring must comply with local and national electrical

code requirements. Read and heed all unit caution labels.

LINE POWER CONNECTIONS

Power may be brought into the unit through the supply air end of
the unit (top when unit is vertical) or the right side panel. Use the
hole appropriate to the unit’s orientation in each installation to
bring conduit from the disconnect. The power lead conduit should

be terminated at the transformer or electric heater box. Refer to
Tables 2 and 5 for single source wire sizes. Also see Figure 5.

ALTERNATE LINE POWER CONNECTIONS 

When desired or required by local conditions the units equipped
with circuit breakers may be field converted to use multiple power
sources, this will permit the use of smaller size power wire but will
require a greater number of wires. To accomplish this field con-
version refer to Figure 5 - (Dual Supply) as an example and
proceed as follows.

1. Remove the jumper bar assembly and cover at the line side

connection to the circuit breakers.

2. Select the proper wire size from Table 3.

3. Connect the multiple power sources direct to the circuit breakers.

NOTE: LINE VOLTAGE POWER CONNECTS
             DIRECTLY TO 10 KW BOARDS

EDGE CONNECTOR
(For Wiring Harness that
attaches to Connection Board)

BREAK OFF TABS
(For Variable Speed Air
Handler ONLY - must be
removed)

5, 7.5 & 10 KW CONTROL BOARDS

EDGE CONNECTOR
(For Wiring Harness that
attaches to Connection Board)

12.5, 15 & 20 KW CONTROL BOARDS

BREAK OFF TABS
(For Variable Speed Air
Handler ONLY - must be
removed)

GRD.
LUG

DUAL SUPPLY

SINGLE SUPPLY

POWER WIRING

NOTE: Two circuits permit smaller wire.

POWER

SUPPLY

WITHOUT CIRCUIT BREAKER

WITH CIRCUIT BREAKER

GRD.

GRD.
LUG

GRD.

CIRCUIT BREAKERS

POWER

SUPPLY

GRD.
LUG

GRD.

CIRCUIT BREAKERS

POWER

SUPPLY 1

POWER

SUPPLY 2

WITH CIRCUIT BREAKER

FIELD 
REMOVED 
BUSSBAR

FIGURE 5 - Line Power Connections

FIGURE 6 - Typical Electric Heat Control Boards - (5-20KW Single Phase)

535.03-N1Y

Unitary Products Group

5

Summary of Contents for N1VSD10A06

Page 1: ...be made in writing See Form 50 15 NM for more information REFERENCE This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching...

Page 2: ...an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the coil as is specified by most local building codes If the coil is provided w...

Page 3: ...uction 1 Attach coil casing to blower section in a way appropriate to indoor unit application See Form 535 01 N5V for G HC or G FC Coils and Form 535 01 N6V for G HT Coils Confirm the orifice size bef...

Page 4: ...nnect Line Sizes A B C D E F G H J K L M Liquid Vapor Liquid Vapor D10 024 16 1 4 1 12 1 8 3 7 8 12 1 8 14 1 4 22 3 4 54 1 2 3 1 2 1 1 2 1 3 4 3 1 2 F 6 F 11 5 16 5 8 030 14 1 4 22 3 4 54 1 2 3 1 4 6...

Page 5: ...the use of smaller size power wire but will require a greater number of wires To accomplish this field con version refer to Figure 5 Dual Supply as an example and proceed as follows 1 Remove the jumpe...

Page 6: ...thermostat used has an adjustable heat anticipator see Table below for proper setting BLOWER SPEED SELECTION All variable speed air handlers N VS are designed to deliver constant CFM regardless of the...

Page 7: ...lected To Set Delay Profile Every variable speed air handler has multiple blower off delay profiles to optimize system performance and efficiency Refer to Table below for the type of system installed...

Page 8: ...ION HEAT Tap Jumper at A Jumper at B Jumper at C No Jumper Cubic Foot Per Minute CFM 1300 1300 1450 1600 TABLE 1 CFM TAP SELECTION BLOWER SIZE TRANFORMER KIT MIN CIRCUIT AMPACITY MAX T D FUSE SIZE MIN...

Page 9: ...ABLE 4 ELECTRICAL DATA HEATER ACCESSORY FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 1 KW MBH CONVERSIONS Blower Size Heater Accessory Model No Field Wiring 2...

Page 10: ...W 6 6 C Y R G CONNECTOR BOARD X or L B or C 6 0 5 3 O X HUMIDISTAT JUMPER MUST BE REMOVED DEHUMIDIFICATION CONTROL CONNECTION N O T U S E D NO T US E D B K THE RMOS TA T G W 1 X or L C or B R WIRE NU...

Page 11: ...IRE NUT RED OUTDOOR UNIT R C Y G O X W W1 W2 HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATION CONTROL CONNECTION R C Y 1 Y 2 Y2 OUT NO Y 1 Y 2 W 2 TWO STAGE COOL ING MUST BE USED BRN YEL...

Page 12: ...USED WITH A HEAT PUMP UNIT HEAT PUMP MODELS E FH THERMO STAT G X or L R O UTDO OR HEATPUMP R C Y G O X W W1 W2 INDOOR UNIT CONNECTOR BOARD HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATIO...

Reviews: