background image

255427-YTG-F-1006

6

Unitary Products Group

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

Model

Heater Model

1,*

Field Wiring

Heater Amps

Ampacity Min. Circuit

Max. O.C.P.

Amps/Type

Wire Size - AWG 75°C

240V

208V

240V

208V

240V

208V

240V

MV12B

4HK*6500506

20.0

27.54

30.38

30

35

10

8

4HK*6500806

31.3

39.73

44.50

40

45

8

8

4HK*6501006

40.0

49.21

55.38

50

60

8

6

4HK165N1506

60.0

70.88

80.38

90

90

4

3

MV12D

4HK*6500506

20.0

27.54

30.38

30

35

10

8

4HK*6500806

31.3

39.73

44.50

40

45

8

8

4HK*6501006

40.0

49.21

55.38

50

60

8

6

4HK16501506

60.0

70.88

80.38

90

90

4

3

4HK16501806

73.3

85.32

97.00

90

100

4

3

4HK16502006

80.0

92.54

105.38

100

125

3

1

MV16C

4HK*6500506

20.0

29.29

31.88

30

35

10

8

4HK*6500806

31.3

41.48

46.00

45

50

8

8

4HK*6501006

40.0

50.96

56.88

60

60

6

6

4HK16501506

60.0

72.63

81.88

90

90

3

3

4HK16501806

73.3

87.07

98.50

90

100

3

2

4HK16502006

80.0

94.29

106.88

100

125

3

1

MV20D

4HK*6501006

40.0

53.08

58.75

60

60

6

6

4HK16501506

60.0

74.75

83.75

90

90

3

3

4HK16501806

73.3

89.19

100.38

90

110

3

2

4HK16502006

80.0

96.42

108.75

100

125

3

1

4HK16502506

100.0

118.08

133.75

125

150

1

1/0

1. 30 KW 3 phase not approved for single source power supply.
2. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
* May be 0 (no breaker) or 1 (with breaker).

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

Models

Heat Kit - 

Three Phase

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

75°C Wire Size - AWG

208V

240V

208V

240V

208V

240V

12B

4HK06501025

23.1

30.9

34.3

35

35

8

8

12D

4HK06501025

23.1

30.9

34.3

35

35

8

8

4HK06501525

34.7

43.4

48.8

45

50

8

8

4HK06501825

41.4

50.6

57.1

50

60

8

6

16C

4HK06501025

23.1

32.6

35.1

35

35

8

8

4HK06501525

34.7

45.1

49.6

45

50

8

8

4HK06501825

41.4

52.4

58.0

60

60

6

6

20D

4HK06501025

23.1

34.8

37.6

35

40

8

8

4HK06501525

34.7

47.3

52.1

50

60

8

6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 1: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60

Models

Heater 

Model

Minimum Circuit Ampacity

Max. O.C.P.

Amps/Type

75°C Wire Size - AWG

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

20D

4HK16502525

41.0 / 44.9

31.3 / 36.1

- / -

45 / 45

35 / 40

- / -

8 / 8

8 / 8

- / -

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

Summary of Contents for MV

Page 1: ...e 1 inch foil face fiber glass insulation providing a thermal insulation value of R 4 2 COILS Staggered rows of rifled copper tubes are mechanically expanded into enhanced surface aluminum fins to pro...

Page 2: ...epending on combination 16 1 2 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 MV12D 25 24 1 2 23 1 2 21 19 32 MV16C 25 21 20 18 3 32 MV20D 25 24 1 2 23 1 2 21 19 32 MC24B H 26 1 2 17 1 2 16 1 2 16 3 8...

Page 3: ...60D H 1275 85 72 53 7 48 4 43 5 37 5 80 67 43 0 38 0 33 3 27 7 75 62 33 1 28 1 24 5 22 4 70 57 28 8 26 5 24 5 22 4 MC61D H 1450 85 72 91 7 78 4 68 1 52 3 80 67 73 4 61 5 52 0 38 6 75 62 57 3 45 6 38 4...

Page 4: ...Pump Sweat 3 40 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced None 53 MC18A2AH1 2A MC18B3XH1 3 40 2 14 2 14 x 17 5 None 53 MC18B2AH1 2A MC24A3XH1 4 38 2 14 2 18 x 17 5 None 56 MC24A2AH1 2A MC24B3XH1 4 38 2...

Page 5: ...6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 4HK16502006 0 5 Heat D 14 4 19 2 49 2 65 5 3 6 4 8 7 2 9 6 14 4 19 2 MV20D 4HK 6501006 0 5 Heat D 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Heat...

Page 6: ...133 75 125 150 1 1 0 1 30 KW 3 phase not approved for single source power supply 2 OCP Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse May be 0 no breaker or 1 wit...

Page 7: ...ay fuse KW MBH CONVERSIONS FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 ELECTRICAL DATA COOLING UNIT ONLY 60 Hz MODEL Total Motor Amps Minimum Circuit Ampacit...

Page 8: ...f an electric heat accessory which is rated for greater than zero clearance to combustible surfaces is installed in these air handlers in the downflow operating positions on a combustible floor one of...

Page 9: ...0 47 64 PLENUM 12 1 2 FLOOR OPENING APPROX 1 2 CLEARANCE ALL AROUND FLOOR A AIR HANDLER WIDTH COMBUSTIBLE FLOOR BASE 1 1 APPROX 1 2 CLEARANCE ALL AROUND C FLOOR OPENING B PLENUM All dimensions are in...

Page 10: ...ic pressure From 0 6 to 1 0 static pressure CFM is reduced by 2 per 0 1 increase in static Operation on duct systems with greater than 1 0 w c external static pressure is not recommended NOTE At some...

Page 11: ...AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT MA SERI...

Page 12: ...o change without notice Printed in U S A 255427 YTG F 1006 Copyright by York International JCI 2006 All rights reserved Supersedes 255427 YTG E 0906 Unitary 5005 Norman Products York OK Group Drive 73...

Reviews: