background image

255427-YTG-F-1006

                                                                                                                                                                                                                               

Unitary Products Group

3

COOLING CAPACITY - COIL ONLY

Blower

Model

Coil

Model

Rated

CFM

Entering

 Air 

°

F

(Dry / Wet Bulb)

MBH @ Evaporator Temperature and

Corresponding Pressure °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

Multi-Position - Upflow / Downflow / Horizontal

MV12B

MC30B**H

1025

85 / 72

41.5

37.8

33.7

29.5

80 / 67

36.2

32.4

28.6

24.5

75 / 62

29.1

25.3

24.0

19.2

70 / 57

24.1

21.5

18.7

15.8

MC36B**H

1250

85 / 72

52.0

47.3

42.3

37.3

80 / 67

41.7

36.8

32.3

27.4

75 / 62

32.5

27.3

29.8

22.2

70 / 57

27.9

25.8

23.8

22.2

MV12D

MC48D**H

1125

85 / 72

46.8

42.4

37.6

33.0

80 / 67

37.4

33.3

29.4

24.3

75 / 62

28.9

24.6

21.7

19.6

70 / 57

25.1

23.3

21.7

19.6

MC60D**H

1275

85 / 72

53.7

48.4

43.5

37.5

80 / 67

43.0

38.0

33.3

27.7

75 / 62

33.1

28.1

24.5

22.4

70 / 57

28.8

26.5

24.5

22.4

MC61D**H

1450

85 / 72

91.7

78.4

68.1

52.3

80 / 67

73.4

61.5

52.0

38.6

75 / 62

57.3

45.6

38.4

31.2

70 / 57

49.2

43.0

38.4

31.2

MV16C

MC42C**H

1400

85 / 72

88.4

76.0

63.3

50.0

80 / 67

70.8

59.4

48.4

37.0

75 / 62

55.2

43.9

35.8

29.9

70 / 57

47.4

41.5

35.8

29.9

MC48C**H

1650

85 / 72

100.5

86.4

72.0

56.8

80 / 67

80.4

67.5

55.0

42.1

75 / 62

62.7

49.9

40.7

34.0

70 / 57

53.9

47.2

40.7

34.0

MV20D

MC48D**H

1725

85 / 72

119.9

101.0

80.0

62.2

80 / 67

96.0

79.2

62.6

45.8

75 / 62

74.0

58.6

46.2

37.0

70 / 57

64.3

55.4

46.2

37

MC60D**H

2000

85 / 72

124.8

105.2

85.3

64.7

80 / 67

99.9

82.5

65.2

47.7

75 / 62

77

61.1

48.1

38.6

70 / 57

66.9

57.7

48.1

38.6

MC61D**H

2200

85 / 72

131.0

110.5

89.6

67.9

80 / 67

104.9

86.6

68.5

50.1

75 / 62

81.8

64.2

50.5

40.5

70 / 57

70.2

60.6

50.5

40.5

Summary of Contents for MV

Page 1: ...e 1 inch foil face fiber glass insulation providing a thermal insulation value of R 4 2 COILS Staggered rows of rifled copper tubes are mechanically expanded into enhanced surface aluminum fins to pro...

Page 2: ...epending on combination 16 1 2 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 MV12D 25 24 1 2 23 1 2 21 19 32 MV16C 25 21 20 18 3 32 MV20D 25 24 1 2 23 1 2 21 19 32 MC24B H 26 1 2 17 1 2 16 1 2 16 3 8...

Page 3: ...60D H 1275 85 72 53 7 48 4 43 5 37 5 80 67 43 0 38 0 33 3 27 7 75 62 33 1 28 1 24 5 22 4 70 57 28 8 26 5 24 5 22 4 MC61D H 1450 85 72 91 7 78 4 68 1 52 3 80 67 73 4 61 5 52 0 38 6 75 62 57 3 45 6 38 4...

Page 4: ...Pump Sweat 3 40 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced None 53 MC18A2AH1 2A MC18B3XH1 3 40 2 14 2 14 x 17 5 None 53 MC18B2AH1 2A MC24A3XH1 4 38 2 14 2 18 x 17 5 None 56 MC24A2AH1 2A MC24B3XH1 4 38 2...

Page 5: ...6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 4HK16502006 0 5 Heat D 14 4 19 2 49 2 65 5 3 6 4 8 7 2 9 6 14 4 19 2 MV20D 4HK 6501006 0 5 Heat D 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Heat...

Page 6: ...133 75 125 150 1 1 0 1 30 KW 3 phase not approved for single source power supply 2 OCP Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse May be 0 no breaker or 1 wit...

Page 7: ...ay fuse KW MBH CONVERSIONS FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 ELECTRICAL DATA COOLING UNIT ONLY 60 Hz MODEL Total Motor Amps Minimum Circuit Ampacit...

Page 8: ...f an electric heat accessory which is rated for greater than zero clearance to combustible surfaces is installed in these air handlers in the downflow operating positions on a combustible floor one of...

Page 9: ...0 47 64 PLENUM 12 1 2 FLOOR OPENING APPROX 1 2 CLEARANCE ALL AROUND FLOOR A AIR HANDLER WIDTH COMBUSTIBLE FLOOR BASE 1 1 APPROX 1 2 CLEARANCE ALL AROUND C FLOOR OPENING B PLENUM All dimensions are in...

Page 10: ...ic pressure From 0 6 to 1 0 static pressure CFM is reduced by 2 per 0 1 increase in static Operation on duct systems with greater than 1 0 w c external static pressure is not recommended NOTE At some...

Page 11: ...AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT MA SERI...

Page 12: ...o change without notice Printed in U S A 255427 YTG F 1006 Copyright by York International JCI 2006 All rights reserved Supersedes 255427 YTG E 0906 Unitary 5005 Norman Products York OK Group Drive 73...