Johnson Controls Unitary Products

5006167-YTG-F-0517

ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60

Air Handler

Models

Heater 

Models

Heater

Amps

@240V

Min. Circuit Ampacity

MOP.

1

208V

230V

208V

230V

Circuit

Circuit

1st

2nd

1st

3

2nd

1st

3

2nd

1st

3

2nd

MP08B

6HK16501306

52

20.5

37.6

22.5

41.5

25

40

25

45

MP12B

6HK16501306

52

22.0

37.6

24.0

41.5

25

40

25

45

6HK16501506

60

24.9

43.3

27.2

47.9

25

45

30

50

6HK16501806

72

42.3

39.0

46.4

43.1

45

40

50

45

6HK16502006

80

46.6

43.3

51.2

47.9

50

45

60

50

MP14D

6HK16501306

52

22.3

37.6

24.3

41.5

25

40

25

45

6HK16501506

60

25.2

43.3

27.5

47.9

30

45

30

50

6HK16501806

72

29.5

39.0

46.6

43.1

30

40

50

45

6HK16502006

80

32.4

43.3

51.4

47.9

35

45

60

50

MP16C

6HK16501306

52

22.4

37.6

24.4

41.5

25

40

25

45

6HK16501506

60

25.3

43.3

27.6

47.9

30

45

30

50

6HK16501806

72

42.6

39.0

46.8

43.1

30

40

50

45

6HK16502006

80

47.0

43.3

51.5

47.9

35

45

60

50

MP20D

6HK16501306

52

23.9

37.6

25.9

41.5

25

40

30

45

6HK16501506

60

26.8

43.3

29.1

47.9

30

45

30

50

6HK16501806

72

44.1

39.0

48.3

43.1

45

40

50

45

6HK16502006

80

48.5

43.3

53.0

47.9

50

45

60

50

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. 

Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-3-60 

Air Handler 

Models

Heater 

Models

1

Heater

Amps

@240V

Field Wiring

Min. Circuit Ampacity

2

MOP

208V

230V

208V

230V

MP08B

6HK36501025

23.1

26.8

29.4

30

30

MP12B

6HK36501025

23.1

28.3

30.9

30

35

6HK36501525

34.6

40.8

44.7

45

45

6HK36501825

41.6

48.4

53.2

50

55

6HK46502025

3

46.2

53.3

58.5

55

60

MP14D

6HK36501025

23.1

28.5

31.1

30

35

6HK36501525

34.6

41.0

45.0

45

45

6HK36501825

41.6

48.7

53.4

50

55

6HK46502025

3

46.2

53.5

58.8

55

60

MP16C

6HK36501025

23.1

28.6

31.3

30

35

6HK36501525

34.6

41.1

45.1

45

50

6HK36501825

41.6

48.8

53.6

50

55

6HK46502025

3

46.2

53.6

58.9

55

60

MP20D

6HK36501025

23.1

30.1

32.8

35

35

6HK36501525

34.6

42.6

46.6

45

50

6HK36501825

41.6

50.3

55.1

55

60

6HK46502025

3

46.2

55.1

60.4

60

70

1. 6HK3 = 3-Phase with terminal block connections only, 6HK4 = 3-Phase with service disconnect
2. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard. Single source power MCA and MOP 
requirements are given here only for reference if used with field installed single point power modification (S1-32436041000).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. 

Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

Summary of Contents for MP SERIES

Page 1: ...resists corrosion and rust creep Quality Construction Structural components are made of Aluminum or G90 galvanized steel to prevent corrosion Improved Insulation Design Single piece with no external screws to reduce thermal transmission paths to prevent sweating Foil faced insulation for ease of cleaning Case Depth These models have 20 5 casing which provide ease of attic access and tight applicat...

Page 2: ...TOTAL POWER INPUT REQUIREMENT 9 APPLICATION FACTORS RATED CFM VS ACTUAL CFM 9 POWER WIRING LINE CONNECTIONS 9 BLOWER SPEED CONNECTIONS 9 ACCESSORIES 10 FILTER RACK DIMENSIONS 10 COMBUSTIBLE FLOOR BASE ACCESSORY 11 LIMITATIONS 11 TYPICAL APPLICATIONS 11 TYPICAL THERMOSTAT CONNECTION 12 AIR FLOW DATA CFM 208 Volt 13 AIR FLOW DATA CFM 230 Volt 14 NOMENCLATURE PRODUCT TYPE M M Modular Blower POSITION ...

Page 3: ...stalled TXV Dimensions 1 Height Width Opening Widths Refrigerant Connections 3 4 5 3 Refrigerant line sizes may require larger lines for extended line lengths See Application Data part number 247077 4 Adapter fitting must be field installed for other line set size 5 See outdoor unit technical guide for proper line set size Line Size A B C D Liquid Vapor CM18A 19 1 2 14 1 2 13 1 2 13 1 2 3 8 3 4 CM...

Page 4: ... 37 8 30 1 21 5 16 2 CM30D 1000 85 72 75 3 67 8 56 8 47 1 80 67 62 6 54 6 44 2 34 5 75 62 50 2 41 3 32 0 22 9 70 57 37 8 30 1 21 5 16 2 CM36B 1000 85 72 82 1 73 7 64 1 54 4 80 67 68 6 60 1 50 5 39 5 75 62 56 3 47 0 37 3 29 2 70 57 43 5 36 0 28 3 21 6 CM36B 1200 85 72 91 6 82 4 71 3 59 4 80 67 76 5 65 4 54 6 42 8 75 62 61 3 51 2 40 0 30 5 70 57 47 5 38 1 28 7 22 3 CM42C 1200 85 72 98 0 88 6 77 4 66...

Page 5: ...ed CFM2 Entering Air Dry Wet Bulb F MBH Evap Temp and Corresponding R 410A Pressure F PSIG 35 107 9 40 118 9 45 130 7 50 143 3 PHYSICAL ELECTRICAL DATA COOLING ONLY Models MP08B MP12B MP14D MP16C MP20D Blower Diameter x Width 10 x 8 10 x 8 10 x 10 10 x 10 10 x 10 Motor HP 1 4 HP 1 2 HP 1 2 HP 1 2 HP 1 HP Nominal RPM 850 1085 1085 1040 1007 Voltage 208 230 208 230 208 230 208 230 208 230 Full Load ...

Page 6: ...Nominal kW 240V Total Heat 4 kW Staging kW MBH W1 Only W1 W2 208V 230V 208V 230V 208V 230V 208V 230V 1PH 6HK 0 1 6500206 2 4 1 8 2 2 6 2 7 5 1 8 2 2 1 8 2 2 6HK 0 1 6500506 4 8 3 6 4 4 12 3 15 3 6 4 4 3 6 4 4 6HK 0 1 6500806 7 7 5 8 7 1 19 7 24 1 5 8 7 1 5 8 7 1 6HK 0 1 6501006 9 6 7 2 8 8 24 6 30 1 7 2 8 8 7 2 8 8 6HK 1 2 6501306 12 5 9 4 11 5 32 39 2 3 1 3 8 9 4 11 5 6HK 1 2 6501506 14 4 10 8 13...

Page 7: ...2 70 80 6HK 1 2 6501806 72 81 6 89 9 90 90 6HK 1 2 6502006 80 90 0 99 2 90 100 MP16C 6HK 0 1 6500206 10 14 4 15 6 15 20 6HK 0 1 6500506 20 25 3 27 5 30 30 6HK 0 1 6500806 32 38 5 42 2 40 45 6HK 0 1 6501006 40 46 9 51 5 50 60 6HK 1 2 6501306 52 60 1 66 1 70 70 6HK 1 2 6501506 60 68 5 75 4 70 80 6HK 1 2 6501806 72 81 8 90 0 90 90 6HK 1 2 6502006 80 90 2 99 3 90 100 MP20D 6HK 0 1 6500206 10 15 9 17 1...

Page 8: ... or in Canada the Canadian electrical Code and local codes to determine correct wire sizing ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models1 Heater Amps 240V Field Wiring Min Circuit Ampacity2 MOP 208V 230V 208V 230V MP08B 6HK36501025 23 1 26 8 29 4 30 30 MP12B 6HK36501025 23 1 28 3 30 9 30 35 6HK36501525 34 6 40 8 44 7 45 45 6HK36501825 41 6 48 4 53 2 ...

Page 9: ...ge multiply the kW and MBH data from the table by the conversion factor in the following table DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR 208V 240V 0 75 220V 240V 0 84 230V 240V 0 92 APPLICATION FACTORS RATED CFM VS ACTUAL CFM Of Rated Airflow CFM 80 90 100 110 120 Capacity Factor 0 96 0 98 1 00 1 02 1 03 POWER WIRING LINE CONNECTIONS 32 5 5 1 9 20321 17 2 6 1 5281 8 6 6 59 6 211 7 7 5 8...

Page 10: ...t moisture barrier seals the service disconnect s from humidity and dust The flexibility of the clear cover allows service disconnects to be turned ON or OFF without removing the cover The cover firmly attaches to the access panel around the service disconnects with the use of double backed adhesive tape To ensure that moisture or dust does not contaminate service disconnects an S1 02435672000 Cov...

Page 11: ... MP14D MP20D 24 5 21 0 23 0 DOWNFLOW AIR HANDLER WARM AIR PLENUM with 1 flange out on each side FIBERGLASS INSULATION FIBERGLASS TAPE under flange COMBUSTIBLE FLOOR BASE ACCESSORY A B B A AIR HANDLER DEPTH FRONT FLOOR 1 11 PLENUM 13 FLOOR OPENING APPROX 1 2 CLEARANCE ALL AROUND FLOOR A AIR HANDLER WIDTH COMBUSTIBLE FLOOR BASE APPROX 1 2 CLEARANCE ALL AROUND C FLOOR OPENING B PLENUM 1 1 A0457 001 C...

Page 12: ...12 Johnson Controls Unitary Products 5006167 YTG F 0517 TYPICAL THERMOSTAT CONNECTION A0370 002 W2 X L X L X L X L FIELD INSTALLED JUMPER IF SINGLE STAGE THERMOSTAT IS USED ...

Page 13: ...edium 1520 1508 1486 1446 1398 1203 1101 Low 1207 1202 1176 1156 1028 970 885 CM42D High 1949 1912 1854 1791 1715 1645 1358 Medium 1538 1521 1492 1458 1406 1265 1144 Low 1197 1190 1179 1128 1052 998 903 MP16C CM36C High 1776 1709 1646 1573 1491 1328 1171 Medium 1591 1545 1486 1424 1300 1173 1066 Low 1360 1331 1285 1194 1097 1027 941 CM42C High 1746 1687 1616 1536 1386 1265 1147 Medium 1564 1507 14...

Page 14: ...Low 1374 1366 1339 1316 1250 1070 904 CM36D High 2099 2040 1980 1903 1814 1680 1605 Medium 1725 1694 1652 1605 1541 1467 1182 Low 1388 1372 1340 1306 1277 1106 1026 CM42D High 2083 2033 1960 1894 1820 1720 1459 Medium 1690 1662 1623 1587 1534 1460 1233 Low 1399 1393 1370 1338 1269 1159 1073 MP16C CM36C High 1850 1785 1705 1625 1541 1373 1242 Medium 1693 1642 1574 1499 1378 1261 1145 Low 1512 1465 ...

Reviews: