Johnson Controls Unitary Products

13

5006167-YTG-F-0517

Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. 

 

Heating applications tested at 0.50” w.c. esp.

AIR FLOW DATA - CFM

1

 (208 Volt)

Models

CM Models

Blower

Motor Speed

External Static Pressure (in. WC.)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

208 Volt

MP08B

CM18B

High

975

965

953

926

889

772

724

Medium

729

719

700

643

614

540

354

Low

576

561

501

455

407

289

209

CM24B

High

950

944

927

907

876

838

742

Medium

713

703

686

656

591

533

478

Low

560

546

511

448

398

294

208

MP12B

CM30B

High

1459

1410

1342

1275

1200

1129

1022

Medium

1241

1210

1156

1110

1044

1002

917

Low

992

965

940

911

867

822

758

CM36B

High

1487

1438

1383

1315

1245

1150

1073

Medium

1226

1202

1166

1119

1079

1007

945

Low

959

950

925

892

866

818

716

MP14D

CM30D

High

1944

1891

1832

1767

1693

1594

1303

Medium

1518

1494

1470

1425

1377

1186

1071

Low

1208

1198

1180

1155

1019

968

830

CM36D

High

1967

1920

1848

1781

1710

1623

1532

Medium

1520

1508

1486

1446

1398

1203

1101

Low

1207

1202

1176

1156

1028

970

885

CM42D

High

1949

1912

1854

1791

1715

1645

1358

Medium

1538

1521

1492

1458

1406

1265

1144

Low

1197

1190

1179

1128

1052

998

903

MP16C

CM36C

High

1776

1709

1646

1573

1491

1328

1171

Medium

1591

1545

1486

1424

1300

1173

1066

Low

1360

1331

1285

1194

1097

1027

941

CM42C

High

1746

1687

1616

1536

1386

1265

1147

Medium

1564

1507

1451

1388

1246

1148

998

Low

1339

1301

1258

1136

1052

994

876

CM48C

High

1817

1756

1678

1599

1511

1296

1120

Medium

1673

1618

1542

1477

1349

1138

915

Low

1448

1419

1362

1281

1136

1001

948

MP20D

CM42D

High

2035

1994

1922

1858

1781

1658

1562

Medium

1849

1819

1771

1694

1650

1575

1364

Low

1679

1654

1624

1578

1526

1339

1263

CM48D

High

2061

2001

1937

1871

1780

1684

1570

Medium

1867

1835

1786

1727

1653

1563

1328

Low

1678

1657

1615

1572

1518

1441

1235

CM60D

High

2021

1979

1897

1833

1751

1668

1521

Medium

1852

1811

1758

1697

1639

1547

1389

Low

1646

1630

1596

1555

1491

1384

1247

CM64D

High

1867

1832

1784

1729

1652

1572

1462

Medium

1498

1484

1443

1411

1361

1233

1138

Low

1128

1122

1115

1096

1020

967

893

1. Air handler units have been tested to UL 1995 / CSA 22.2 No. 236 standards up to 0.50" WC. external static pressure.

 

Summary of Contents for MP SERIES

Page 1: ...resists corrosion and rust creep Quality Construction Structural components are made of Aluminum or G90 galvanized steel to prevent corrosion Improved Insulation Design Single piece with no external screws to reduce thermal transmission paths to prevent sweating Foil faced insulation for ease of cleaning Case Depth These models have 20 5 casing which provide ease of attic access and tight applicat...

Page 2: ...TOTAL POWER INPUT REQUIREMENT 9 APPLICATION FACTORS RATED CFM VS ACTUAL CFM 9 POWER WIRING LINE CONNECTIONS 9 BLOWER SPEED CONNECTIONS 9 ACCESSORIES 10 FILTER RACK DIMENSIONS 10 COMBUSTIBLE FLOOR BASE ACCESSORY 11 LIMITATIONS 11 TYPICAL APPLICATIONS 11 TYPICAL THERMOSTAT CONNECTION 12 AIR FLOW DATA CFM 208 Volt 13 AIR FLOW DATA CFM 230 Volt 14 NOMENCLATURE PRODUCT TYPE M M Modular Blower POSITION ...

Page 3: ...stalled TXV Dimensions 1 Height Width Opening Widths Refrigerant Connections 3 4 5 3 Refrigerant line sizes may require larger lines for extended line lengths See Application Data part number 247077 4 Adapter fitting must be field installed for other line set size 5 See outdoor unit technical guide for proper line set size Line Size A B C D Liquid Vapor CM18A 19 1 2 14 1 2 13 1 2 13 1 2 3 8 3 4 CM...

Page 4: ... 37 8 30 1 21 5 16 2 CM30D 1000 85 72 75 3 67 8 56 8 47 1 80 67 62 6 54 6 44 2 34 5 75 62 50 2 41 3 32 0 22 9 70 57 37 8 30 1 21 5 16 2 CM36B 1000 85 72 82 1 73 7 64 1 54 4 80 67 68 6 60 1 50 5 39 5 75 62 56 3 47 0 37 3 29 2 70 57 43 5 36 0 28 3 21 6 CM36B 1200 85 72 91 6 82 4 71 3 59 4 80 67 76 5 65 4 54 6 42 8 75 62 61 3 51 2 40 0 30 5 70 57 47 5 38 1 28 7 22 3 CM42C 1200 85 72 98 0 88 6 77 4 66...

Page 5: ...ed CFM2 Entering Air Dry Wet Bulb F MBH Evap Temp and Corresponding R 410A Pressure F PSIG 35 107 9 40 118 9 45 130 7 50 143 3 PHYSICAL ELECTRICAL DATA COOLING ONLY Models MP08B MP12B MP14D MP16C MP20D Blower Diameter x Width 10 x 8 10 x 8 10 x 10 10 x 10 10 x 10 Motor HP 1 4 HP 1 2 HP 1 2 HP 1 2 HP 1 HP Nominal RPM 850 1085 1085 1040 1007 Voltage 208 230 208 230 208 230 208 230 208 230 Full Load ...

Page 6: ...Nominal kW 240V Total Heat 4 kW Staging kW MBH W1 Only W1 W2 208V 230V 208V 230V 208V 230V 208V 230V 1PH 6HK 0 1 6500206 2 4 1 8 2 2 6 2 7 5 1 8 2 2 1 8 2 2 6HK 0 1 6500506 4 8 3 6 4 4 12 3 15 3 6 4 4 3 6 4 4 6HK 0 1 6500806 7 7 5 8 7 1 19 7 24 1 5 8 7 1 5 8 7 1 6HK 0 1 6501006 9 6 7 2 8 8 24 6 30 1 7 2 8 8 7 2 8 8 6HK 1 2 6501306 12 5 9 4 11 5 32 39 2 3 1 3 8 9 4 11 5 6HK 1 2 6501506 14 4 10 8 13...

Page 7: ...2 70 80 6HK 1 2 6501806 72 81 6 89 9 90 90 6HK 1 2 6502006 80 90 0 99 2 90 100 MP16C 6HK 0 1 6500206 10 14 4 15 6 15 20 6HK 0 1 6500506 20 25 3 27 5 30 30 6HK 0 1 6500806 32 38 5 42 2 40 45 6HK 0 1 6501006 40 46 9 51 5 50 60 6HK 1 2 6501306 52 60 1 66 1 70 70 6HK 1 2 6501506 60 68 5 75 4 70 80 6HK 1 2 6501806 72 81 8 90 0 90 90 6HK 1 2 6502006 80 90 2 99 3 90 100 MP20D 6HK 0 1 6500206 10 15 9 17 1...

Page 8: ... or in Canada the Canadian electrical Code and local codes to determine correct wire sizing ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models1 Heater Amps 240V Field Wiring Min Circuit Ampacity2 MOP 208V 230V 208V 230V MP08B 6HK36501025 23 1 26 8 29 4 30 30 MP12B 6HK36501025 23 1 28 3 30 9 30 35 6HK36501525 34 6 40 8 44 7 45 45 6HK36501825 41 6 48 4 53 2 ...

Page 9: ...ge multiply the kW and MBH data from the table by the conversion factor in the following table DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR 208V 240V 0 75 220V 240V 0 84 230V 240V 0 92 APPLICATION FACTORS RATED CFM VS ACTUAL CFM Of Rated Airflow CFM 80 90 100 110 120 Capacity Factor 0 96 0 98 1 00 1 02 1 03 POWER WIRING LINE CONNECTIONS 32 5 5 1 9 20321 17 2 6 1 5281 8 6 6 59 6 211 7 7 5 8...

Page 10: ...t moisture barrier seals the service disconnect s from humidity and dust The flexibility of the clear cover allows service disconnects to be turned ON or OFF without removing the cover The cover firmly attaches to the access panel around the service disconnects with the use of double backed adhesive tape To ensure that moisture or dust does not contaminate service disconnects an S1 02435672000 Cov...

Page 11: ... MP14D MP20D 24 5 21 0 23 0 DOWNFLOW AIR HANDLER WARM AIR PLENUM with 1 flange out on each side FIBERGLASS INSULATION FIBERGLASS TAPE under flange COMBUSTIBLE FLOOR BASE ACCESSORY A B B A AIR HANDLER DEPTH FRONT FLOOR 1 11 PLENUM 13 FLOOR OPENING APPROX 1 2 CLEARANCE ALL AROUND FLOOR A AIR HANDLER WIDTH COMBUSTIBLE FLOOR BASE APPROX 1 2 CLEARANCE ALL AROUND C FLOOR OPENING B PLENUM 1 1 A0457 001 C...

Page 12: ...12 Johnson Controls Unitary Products 5006167 YTG F 0517 TYPICAL THERMOSTAT CONNECTION A0370 002 W2 X L X L X L X L FIELD INSTALLED JUMPER IF SINGLE STAGE THERMOSTAT IS USED ...

Page 13: ...edium 1520 1508 1486 1446 1398 1203 1101 Low 1207 1202 1176 1156 1028 970 885 CM42D High 1949 1912 1854 1791 1715 1645 1358 Medium 1538 1521 1492 1458 1406 1265 1144 Low 1197 1190 1179 1128 1052 998 903 MP16C CM36C High 1776 1709 1646 1573 1491 1328 1171 Medium 1591 1545 1486 1424 1300 1173 1066 Low 1360 1331 1285 1194 1097 1027 941 CM42C High 1746 1687 1616 1536 1386 1265 1147 Medium 1564 1507 14...

Page 14: ...Low 1374 1366 1339 1316 1250 1070 904 CM36D High 2099 2040 1980 1903 1814 1680 1605 Medium 1725 1694 1652 1605 1541 1467 1182 Low 1388 1372 1340 1306 1277 1106 1026 CM42D High 2083 2033 1960 1894 1820 1720 1459 Medium 1690 1662 1623 1587 1534 1460 1233 Low 1399 1393 1370 1338 1269 1159 1073 MP16C CM36C High 1850 1785 1705 1625 1541 1373 1242 Medium 1693 1642 1574 1499 1378 1261 1145 Low 1512 1465 ...