background image

10. Lead selector and cycling control to provide similar

lead selection and cycling of lag units for three (3)
units is available: Kit No. 366-44684D (see Product
Drawing Form 160.00-PA1.1) in NEMA I enclosure.
Consult your YORK representative.

11. Sequence control kits (see Fig.9 and Note 10)  as-

sume a constant chilled water flow and a constant
leaving chilled water temperature to sense the cool-
ing load. Sequence control kits are not designed for
variable chilled water flow or with reset of the leav-
ing chilled water temperature  – see Figs. 18 to 20
and Note 2.

12. Maximum allowable current draw between circuits

24 and 2 for field installed devices is 2 amp hold-

ing and 10 amps inrush – see Graphic Control Cen-
ter Wiring Diagram Form No. in Note 1.

13. For required field wiring connections of the chilled

water pump contacts (terminals 44 and  45 on
Graphic Control Center field wiring terminal block
TB2) and chilled water flow switch (termin-
als 1 and 12 on Graphic Control Center field wir-
ing terminal board TB2), see Wiring Diagram – Field
Connections: Form 160.55-PW4, units having an
Electro-mechanical Starter; Product Drawing Form
160.55-PW5, units furnished with a YORK Solid
State Starter; or 160.55-PW6, units with a Variable
Speed Drive.

The chilled water flow switch is a safety control. It
must be connected to prevent operation of the chiller
whenever chilled water flow is stopped. The use of
the chilled water flow switch for purposes other than
protection of the chiller may be accomplished in sev-
eral ways. Two flow switches, a flow switch and a
relay or separate contacts on the same flow switch.

14.

15. Do not apply voltage on field wiring terminal blocks

TB4 and TB6 in YORK Graphic Control Center, as
115VAC source is fed from terminals 1 and 2 .

Proud Sponsor
of the 2000
U.S. Olympic Team

36USC380

P.O. Box 1592, York, Pennsylvania USA  17405-1592

Subject to change without notice. Printed in USA

Copyright © by York International Corporation 1999

ALL RIGHTS RESERVED

Form 160.55-PW7 (899)
Supersedes: Nothing

NOTES

1. This drawing shows recommended field control wir-

ing modifications (by others) to the standard Graphic
Control Center Wiring Diagram. Refer to Graphic
Control Center Wiring Diagram: Product Drawing
Form 160.55-PW1, units having an Electro-mechani-
cal Starter; Product Drawing Form 160.55-PW2,
units furnished with a YORK Solid State Starter; or
160.55-PW3, units with a Variable Speed Drive.

2. If more than one of these modifications is to be uti-

lized with a particular unit, additional consideration
must be given to the application to insure proper
functioning of the control system. Consult your
YORK representative.

3. The additional controls and wiring for these modifi-

cations are to be furnished and installed in the field
(by others). (See Warning on page 2.)

4. The controls specified are recommended for use,

but other controls of equal specifications are accept-
able.

5. All wiring shall be in accordance with the National

Electrical Code, and applicable State and Local
Codes.

6. Each 115VAC field connected inductive load, i.e. re-

lay coil, motor starter coil, etc., shall have a tran-
sient suppressor wired (by others) in parallel with
its coil, physically located at the coil. Spare transient
suppressors are furnished in a bag in the Graphic
Control Center.

7. The Graphic Control Center is factory furnished for

Manual Restart After Power Failure as a standard
function. The control center can be field changed
from Manual restart to Auto Restart after a power
failure by setting position 5 of Dip Switch SW1 to
the ON position - See Fig. 21.

8. Two (2) unit controls schemes are suitable for 8° –

12°F water range. Constant chilled water flow is
assumed at all loads. For other requirements contact
your YORK representative.

9.

Summary of Contents for MILLENNIUM YT J

Page 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Page 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Page 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Page 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Page 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Page 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Page 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Page 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Page 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Page 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Page 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Page 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Page 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Page 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Page 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Page 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Reviews: