FIG. 23 – RUN CONTACTS/REMOTE RUN LIGHT AND
SHUTDOWN INDICATOR PLUS EMS

When run contacts are required for a Remote Run Light
and/or Shutdown Indicator AND Energy Management

On solid state starter units only, when the Current Imbal-
ance
 option is selected via the Solid State Starter screen,
three phase current imbalance protection is provided. A
safety shutdown occurs (following a 45 second by-pass at
startup) whenever the % FLA readout exceeds 80% for
45 seconds continuously and the % imbalance is > 30%.
When all safety controls are satisfied, and the Graphic Con-
trol Center COMPRESSOR switch has been manually
“Reset” (de-energizing alarm) and returned to the RUN
position (“1”), the unit may be restarted, if panel is in “Re-
mote”
 mode, via the Remote Start contacts (Fig. 6); or, if
panel is in “local” mode by momentarily pressing the key-
pad compressor switch to the START (“

”) position.

If the unit was shut down because of
Cycling Shutdown Contacts (see Fig.
2) the alarm will not be energized, but
the unit will have been shut down. A
closure of the safety alarm contacts
means that an operator must manu-
ally reset and restart the unit.

When the Safety Shutdown contacts close, the Graphic
Control Center will display the following message:
“SAFETY  SHUTDOWN – MANUAL RESTART”,
and cause of shutdown.

_

LD04398

FIG. 23 – RUN CONTACTS / REMOTE RUN LIGHT

AND SHUTDOWN INDICATOR PLUS EMS

System (EMS), connect (by others) as shown in the
diagram. The EMS, control relay, shutdown and run
lights are furnished by others. When the N.O. contacts
close, between terminals

35

and

36

on field wiring ter-

minal block TB2 in the Graphic Control Center, this in-
dicates that the unit is operating; the remote Run Light
will be energized. The unit run contacts open when the
unit is shutdown (safety or cycling) and the remote
indicator will then be energized. For run contacts to EMS
only refer to Fig. 4. When terminals 

35

 and 

36

are not

used for an EMS, they may be connected to a remote
Run Light. The control relay scheme shown in Fig. 23
can also be applied for a remote Run Light AND a
Remote Shutdown Indicator, when an EMS is not used.

When Evaporator Water is flowing, the flow switch con-
tact will close. If the flow switch opens for 2 seconds,
the unit shuts down and displays “CYCLING SHUT-
DOWN – AUTO RESTART” and “LEAVING
CHILLED LIQUID – FLOW SWITCH OPEN”. The
chiller will automatically restart when the switch again
closes. The flow switch status is checked 25 seconds
into “START SEQUENCE INITIATED” and continu-
ously thereafter.

FIG. 25 – EVAPORATOR WATER PUMP INTERLOCK

OR FLOW SWITCH

LD04400

LD04399

FIG. 24 – AUXILIARY SAFETY SHUTDOWN INPUT

The closure of a Momentary or Maintained N.O. Switch
or Relay Contacts will cause the unit to shut down and
display: “SAFETY SHUTDOWN – MANUAL RE-
START” and “AUXILIARY SAFETY – CONTACTS
CLOSED”. The unit will not restart until the contacts
open and the keypad COMPRESSOR switch is moved
to the “STOP-RESET” position (“O”) and then to the
“START”  (“      ”)position.

_

Summary of Contents for MILLENNIUM YT J

Page 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Page 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Page 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Page 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Page 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Page 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Page 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Page 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Page 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Page 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Page 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Page 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Page 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Page 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Page 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Page 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Reviews: