52
YORK INTERNATIONAL
ELECTRICAL DATA
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMERS)
NO. OF
CONTROL
MCA
MAX DUAL
NON-FUSED
COMPRESSORS
POWER
(MAX LOAD
ELEMENT
DISCONNECT
SUPPLY
CURRENT)
FUSE SIZE
SWITCH SIZE
3 or 4
115V-1Ø
30A
30A
30A
(Non-CE 50/60Hz)
3 or 4
115V-1Ø
25A
30A
30A
(CE 50Hz)
CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF
CONTROL
MCA
RECOMMENDED
NON-FUSED
COMPRESSORS
POWER
(MAX LOAD
DUAL ELEMENT
DISCONNECT
SUPPLY
CURRENT)
FUSE SIZE
SWITCH SIZE
3 or 4
400V - 50 HZ
9.4A
15A
—
Technical Data