132
YORK INTERNATIONAL
FORM 150.52-NM2 (1001)
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 3:56 PM 28 AUG 00
SYS 1 HIGH DSCH PRESS SHUTDOWN
SYS 2
NO FAU.L.TS
OPTIONS
CHILLED LIQUID
WATER
AMBIENT CONTROL
STANDARD
REFRIGERANT TYPE
R-22
PROGRAM VALUES
DSCH PRESS CUTOUT
399 PSIG
DSCH PRESS UNLOAD
375 PSIG
SUCT PRESS CUTOUT
44 PSIG
HIGH AMBIENT CUTOUT
130.0 °F
LOW AMBIENT CUTOUT
25.0 °F
LEAVING LIQUID CUTOUT
36.0 °F
MOTOR CURRENT UNLOAD
100 %FLA
ANTI RECYCLE TIME
600 SECS
LOCAL/REMOTE MODE
REMOTE
LEAD /LAG CONTROL
AUTOMATIC
UNIT DATA
LEAVING LIQUID TEMP
49.0 °F
RETURN LIQUID TEMP
58.2 °F
MIXED LIQUID TEMP
51.3 °F
COOLING RANGE
42.0 +/-2.0 °F
AMBIENT AIR TEMP
74.8 °F
LEAD SYSTEM
SYS 2
EVAPORATOR PUMP
ON
EVAPORATOR HEATER
OFF
ACTIVE REMOTE CONTROL
NONE
SOFTWARE VERSION
C.RCP.09.00
SYSTEM 1 DATA
COMPRESSORS STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
0 AMPS 0 %FLA
SUCTION PRESSURE
125 PSIG
DISCHARGE PRESSURE
131 PSIG
OIL PRESSURE
130 PSID
SUCTION TEMPERATURE
68.4 °F
OIL TEMPERATURE
68.8 °F
SAT SUCTION TEMP
71.8 °F
SUCTION SUPERHEAT
3.4 °F
COMPRESSOR LOAD STAGE
0
COOLER INLET REFRIG
44.6 °F
LIQUID LINE SOLENOID
OFF
HOT GAS BYPASS SOLENOID
OFF
CONDENSER FAN STAGE
OFF
SYSTEM 2 DATA
COMPRESSORS STATUS
ON
RUN TIME
0- 0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS 87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
218 PSIG
SUCTION TEMPERATURE
42.9 °F
OIL TEMPERATURE
102.8 °F
SAT SUCTION TEMP
31.7 °F
SUCTION SUPERHEAT
11.2 °F
COMPRESSOR LOAD STAGE
2
COOLER INLET REFRIG
23.6 °F
LIQUID LINE SOLENOID
ON
HOT GAS BYPASS SOLENOID
ON
CONDENSER FAN STAGE
3
DAILY SCHEDU.L.E
S M T W T F S *=HOLIDAY
SAMPLE PRINTOUT OF FAULT HISTORY DATA
Micro Panel