York MCC Technical Manual Download Page 12

DE - COMMISSIONING DISMANTLING & DISPOSAL

This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!

All work must only be carried out by competent persons using suitable protective clothing and safety precautions.

                            Read the Manual                 Risk of electric shock                 Unit is remotely controlled and               may start without warning

  1

.  Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas

       isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
       to unit installation instructions.
 

 2

.  Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be

       re-used, if appropriate, or returned to the manufacturer for disposal.

 Under No circumstances should refrigerant be vented to atmosphere.

 Where

       appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing
       disposal of oily wastes.
  

3.

  Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted

       from position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for

unit weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.

  

4.

  After removal from position the unit parts may be disposed of according to local laws and regulations.

Summary of Contents for MCC

Page 1: ...MOC MOH MCC MCH MINISPLIT Floor Ceiling TECHNICAL GUIDE Cooling only and Heat Pump Systems Models MCC MOC MCH MOH 09 to 25 Infrared remote control 035 T 700049 001...

Page 2: ...make sure that the power supply has been disconnected ELECTRICAL CONNECTIONS All electrical wiring and connections must comply with local standards Power supply cord used must not be lighter than Poly...

Page 3: ...Nominal Current Starting Current Fuse Size Indoor Airflow high speed Indoor unit Outdoor unit V Ph Hz Ph kW A A A m h 09 09 1 0 99 4 6 21 10 490 12 12 1 1 30 6 1 28 10 580 18 18 1 1 89 8 7 43 16 700...

Page 4: ...clearances A minimium of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance Clearance required for indoor units Clearance required for outdoor uni...

Page 5: ...urely tighten the hex bolts on both sides Disassemble the side panels and the air inlet grill as shown First open the grill then remove the side panel installation screws Slide the panel toward the to...

Page 6: ...Pa 3 When pump down is finisned wait 15 minutes to detect potential circuit leakage Open service valves on the outdoor unit Note The expansion device is located in the outdoor unit 6 Table 2 Maximum p...

Page 7: ...point entered on the control SYSTEM OPERATION MODE SELECTION ROOM TEMPERATURE SETTING Press the TEMP button up or down to change the setting to the desired room temperature The setting range is from 1...

Page 8: ...ityofthebatteries and that they are in good working condition Also make sure that the controlispointeddirectlyattheairconditioningunitwhenyouareusing it that the distance is a maximum of 10 meters and...

Page 9: ...it 9 The units are designed to operate for long periods of time with a minimum of maintenance However the following operations must be performed regularly RECOMMENDED FREQUENCY MAINTENANCE OPERATIONS...

Page 10: ...nt kit 8 C Inlet air wet bulb temperature indo or unit CWB 10 15 20 25 30 35 20 25 30 35 40 Air intake dry bulb temperature outdoor unit CDB Capacity correction factor C1 Operating temperature range 1...

Page 11: ...35 MSC 35 to 55 MSH 35 to 55 MKC 12 to 55 MKH 12 to 55 MAC 18 to 55 MAH 18 to 55 IS IN COMPLIANCE WITH REQUIREMENTS OF MACHINERY DIRECTIVE CEE 89 392 AS MODIFIED WITH DIRECTIVES CEE 91 368 93 44 93 6...

Page 12: ...the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circumstances...

Reviews: