INSTALLATION & OWNER'S MANUAL

HIGH STATIC DUCTED

ELECTRIC HEATER WITH PLENUM

Models

MBC-MBH 25-65E

ELECTRICAL CONNECTIONS

All electrical wiring and connections must comply with
local standards.

Disconnecting device must have a contact separation of
at least 3 mm with all pole disconnected.

GENERAL PRECAUTIONS

Check that the power supply available agrees with
nameplate voltage.

Use adequate line protection.

The unit must be grounded.

Installation and maintenance of this air conditioning system should only be carried out by trained and qualified
personnel.

Regular maintenance operations such as cleaning the coils and air filters must be performed to keep the
units in proper operating condition.

SAFETY

TEC

HN

ICA

L G

UID

E

CAUTION

Before undertaking any work on the unit, make sure that the power supply has been disconnected.

INDOOR UNITS

Each unit is shipped with the following items:

– an indoor unit ready for connection to the

condensing unit.

– a mounting bracket set.
– a technical guide.
– a control user guide.

INDOOR & OUTDOOR UNITS

OUTDOOR UNITS

The units are shipped complete with a charge of R22/
R407C refrigerant sufficient for a piping length of 5
meters.

Summary of Contents for MBC-MBH 25

Page 1: ...nditioning system should only be carried out by trained and qualified personnel Regular maintenance operations such as cleaning the coils and air filters must be performed to keep the units in proper...

Page 2: ...Outdoor Unit it Power Supply Indoor Unit Fan Air flow Running Current Input Power Electric Heater MBC MBH MOC MOH 220 240 1 50 or 380 415 3 50 Models Power Supply High Static Duct Type MBC MBH P with...

Page 3: ...0 924 Model MBC MBH25 H mm 300 W mm 710 D mm 300 1404 MBC MBH35 MBC MBH45 MBC MBH50 55 MBC MBH65 400 400 400 400 A mm 400 220 220 220 220 220 CONTROL BOX MBC MBH 35 65 LH VIEW REAR VIEW RH VIEW FRONT...

Page 4: ...r 250 Plenum Electric Heater CLEARANCE REQUIRED FOR OUTDOOR UNITS Unit A B C D E 25 400 200 100 300 600 35 400 200 100 300 800 45 400 200 100 300 800 55 400 200 100 300 800 65 400 200 100 300 800 MOC...

Page 5: ...hout any upward slopes An elbow trap at least 50 mm in height must also be provided If possible install a U bend fitted with an inspection cap REFRIGERANT PIPING CONNECTIONS Where the condensate lines...

Page 6: ...H Airflow 1800 2000 3200 2200 2400 2600 2800 3000 Available Ext Static Pa HI ME LO Fan Performance MBC MBH 35 250 200 150 100 50 0 1400 1600 1800 415 470 525 580 635 690 745 800 L S CMH 2000 2200 Airf...

Page 7: ...ssor start up will be delayed until 3 minutes has passed SYSTEM OPERATION MODE SELECTION There are five different operating modes Cool Only and Heat Pump Units Cooling mode Electric Heating Units Only...

Page 8: ...e control is equipped with a diagnostic information system to report operation of the unit as well as operational failures If your remote control does not operate properly first check the polarity of...

Page 9: ...fore start up Each season before start up MAINTENANCE OPERA COMPONENT TIONS 1 Clean with a vacuum cleaner or tap gently then wash in warm water 40 C with a mild detergent 2 Rinse and dry before replac...

Page 10: ...hing and safety precautions Read the Manual Risk of electric shock Unit is remotely controlled and may start without warning 1 Isolate all sources of electrical supply to the unit including any contro...