background image

FORM 160.73-N1 (904)

25

YORK INTERNATIONAL

FIG. 14  –  TYPICIAL REFRIGERANT VENT PIPING

Stop Valves

Stop valves may be provided (by others) in the 
evap o ra tor and condenser water piping adjacent to the 
unit  to  fa cil i tate  main te nance.  Thermometer  wells  and 
pres sure taps should be provided (by others) in the piping 
as close to the unit as pos si ble to facilitate operating 
check.

Flow Switches

Thermal type water 

fl

 ow switches are factory mounted in 

the chilled and condensed water nozzles and are factory 
wired to the OptiView control panel.  These solid-state 

fl

 ow sensors have a small internal heating element and 

use the cooling effect of the 

fl

 owing 

fl

 uid to sense when 

an adequate 

fl

 ow rate has been established.

Drain and Vent Valves

Drain and vent valves (by others) should be installed 
in the connections provided in the evaporator and 
con dens er liquid heads. These connections may be 
piped to drain if desired.

Checking Piping Circuits and Venting Air

After the water piping is completed, but before any wa ter 
box insulation is applied. Tighten and torque to main tain 
between 30 and 60 ft. lbs. (41 and 81 N·m) the nuts on 
the liquid head 

fl

 ang es. Gasket shrinkage and han dling 

dur ing tran sit cause nuts to loosen. If water pres sure is 
ap plied before tightening is done, the gas kets may be 
damaged and have to be replaced. Fill the chilled and 
condenser water circuits, operate the pumps man u al ly 

and care ful ly check the evaporator and condenser wa ter 
heads and piping for leaks. Repair leaks as nec es sary.

Before initial operation of the unit both water circuits 
should be thoroughly vented of all air at the high 
points.

REFRIGERANT RELIEF PIPING

Each unit is equipped with pressure relief valves lo cat ed 
on the condenser and on the evap o ra tor for the pur pose 
of quick ly relieving excess pres sure of the re frig er ant 
charge to the atmosphere as a safety pre cau tion in case 
of an emer gen cy, such as 

fi

 re.

Refrigerant relief vent piping (by others), from the re lief 
valves to the outside of the building, is required by code 
in most areas and should be installed on all chill ers. The 
vent line should be sized in accordance with the ANSI/
ASHRAE-15, or local code.

 

The vent line must include 

a dirt trap in the vertical leg to intercept and permit clean 
out and to trap any vent stack con den sa tion. The piping 
MUST be arranged to avoid strain on the relief valves, 
using a 

fl

 exible connection, if nec es sary.

UNIT PIPING

Compressor lubricant piping and system external pip ing 
are factory installed on all units shipped as sem bled. On 
units shipped dismantled, the following piping should 
be com plet ed under the supervision of the YORK 
rep re sen ta tive: (1) the lubricant piping to oil sump and 
oil evaporator and sys tem oil return connections using 
ma te ri al  fur nished.  See  Form  160.73-N3.

FLANGED JOINT
TO PERMIT PIPING
DISASSEMBLY

CONDENSATION
TRAP

DUAL RELIEF
VALVES

VENT TO ATMOSPHERE

SUPPORT VENT PIPING TO AVOID
STRAIN ON RELIEF PIPING

FLEXIBLE CONNECTOR

CONDENSER

COOLER

SEE NOTE

NOTE:

SHELLS MAY BE FURNISHED WITH
ONE 

OR

 TWO RELIEF VALVES,

DEPENDING ON SHELL SIZE.

LD03863

EVAPORATOR

Summary of Contents for MaxE YK

Page 1: ...TM CENTRIFUGAL LIQUID CHILLERS Supersedes 160 73 N1 1102 Form 160 73 N1 904 MODEL YK STYLE F R 134a COOLING ONLY WITH OPTIVIEW CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABL...

Page 2: ...CG CH CU CY 5CP 5CU DE DF DG DH DE DF DG DH P8 EK EL EM EK EL EM FK FL FM FK FL FM P8 P9 GJ GK GL GM GJ GK GL GM CH CZ 5CE 5CU HK HL HM HK HL HM EB EB EC ED FB FC FD H5 FB FC FD EB EC ED FB FC FD GB...

Page 3: ...al shall have read and understood this document and any referenced materials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertainin...

Page 4: ...elief Piping 25 Unit Piping 25 Control Panel Positioning 26 Control Wiring 26 Power Wiring 26 Insulation 27 Installation Check Request for Start up Service 27 LIST OF FIGURES Fig 1 Model YK MaxE Chill...

Page 5: ...FORM 160 73 N1 904 5 YORK INTERNATIONAL FIG 1 MODEL YK MaxE CHILLER 00611VIP OPTIVIEW CONTROL CENTER COMPRESSOR EVAPORATOR MOTOR CONDENSER...

Page 6: ...1 2 10 9 1 2 C 2 0 2 0 2 1 1 4 2 1 1 4 D 1 5 1 2 1 5 1 2 1 8 1 8 E 1 2 7 8 1 2 7 8 1 3 5 8 1 3 5 8 F 12 0 16 0 12 0 16 0 P1 P2 P3 P4 COMPRESSORS EVAPORATOR CONDENSER SHELL CODES A A B B A 5 6 5 6 B 6...

Page 7: ...ELL CODES E E F F G G H H A 2 108 2 108 2 299 2 299 B 3 137 3 137 3 289 3 289 C 610 610 641 641 D 445 445 508 508 E 378 378 397 397 F 3 658 4 877 3 658 4 877 P9 COMPRESSOR EVAPORATOR CONDENSER SHELL C...

Page 8: ...E E F F E F F F G G F G G A 6 6 6 9 6 11 7 2 7 6 7 4 1 2 7 8 1 2 B 8 0 1 4 8 2 3 4 8 0 1 4 8 2 3 4 8 6 3 4 8 2 3 4 8 6 3 4 C 1 9 1 2 1 9 1 2 2 0 2 0 2 0 2 1 1 4 2 1 1 4 D 1 5 1 2 1 7 1 5 1 2 1 7 1 9 1...

Page 9: ...PORATOR H5 COMPRESSORS EVAPORATOR CONDENSER SHELL CODES E E E F F E F F F G G F G G A 1 981 2 057 2 108 2 184 2 286 2 248 2 350 B 2 445 2 508 2 443 2 508 2 305 2 508 2 305 C 546 546 610 610 610 641 64...

Page 10: ...SER SHELL CODES J J T T T V V T V V W V A 9 1 9 1 9 6 9 1 9 6 9 11 B 10 0 3 4 10 0 3 4 10 5 3 4 10 0 3 4 10 5 3 4 10 5 3 4 C 2 5 1 2 2 5 1 2 2 5 1 2 2 5 1 2 2 5 1 2 2 8 D 2 1 2 1 2 3 1 2 2 1 2 3 1 2 2...

Page 11: ...1 7 5 8 1 7 5 8 1 10 1 8 1 7 5 8 K 1 2 2 0 1 4 1 7 5 8 1 7 5 8 1 10 1 8 1 7 5 8 1 PASS CONDENSERS DIM G H J T V X F 1 2 1 9 1 9 3 4 1 9 3 4 1 11 1 8 1 7 5 8 Dimensions Ft In 3 PASS CONDENSERS DIM G H...

Page 12: ...4267 4267 4267 4267 4267 4877 F 603 603 603 603 603 603 603 603 G 375 375 375 375 375 375 375 375 J3 COMPRESSORS EVAPORATOR CONDENSER SHELL CODES H H H J J H A 2502 2604 2667 B 2965 3067 2965 C 667 6...

Page 13: ...H 152 292 311 311 352 299 J 356 464 498 498 562 499 K 356 464 198 498 562 499 1 PASS CONDENSERS DIM G H J T V X F 356 533 552 552 587 499 Dimensions mm 3 PASS CONDENSERS DIM G H J T V X G 356 429 311...

Page 14: ...1 790 F E H5 23 897 29 300 1 900 F F H5 H6 25 396 31 395 2 020 F G H5 H6 27 788 34 635 2 150 G F H3 H5 H6 H7 H8 27 932 34 780 2 290 G G H3 H5 H6 H7 H8 30 315 37 995 2 415 G G J1 J2 29 410 36 850 2 41...

Page 15: ...H5 10 840 13 290 863 F F H5 H6 11 520 14 240 918 F G H5 H6 12 605 15 710 977 G F H3 H5 H6 H7 H8 12 670 15 775 1 040 G G H3 H5 H6 H7 H8 13 750 17 235 1 097 G G J1 J2 13 340 16 715 1 097 G H J1 J2 13 9...

Page 16: ...are shipped dismantled notify the nearest YORK office in ample time for a YORK representative to supervise rigging the unit to its operating position and the assembly of components 4 Do not make fina...

Page 17: ...uld be checked on arrival to see that all major pieces boxes and crates are received Each unit should be checked on the trailer or rail car when received before unloading for any visible signs of dama...

Page 18: ...ove the unit and particularly space provided at either end to permit cleaning or replacement of evaporator and condenser tubes see CLEARANCE A doorway LD00700 R FIG 8 RIGGING or other sufficiently lar...

Page 19: ...EIGHT UP TO 16365 LBS LD08521 UNIT WEIGHT 16 366 TO 28 835 LBS LD08522 LD10114 10 10 10 10 8 3 8 3 2 CONDENSOR CONDENSOR CENTERLINE CENTERLINE END SHEET END SHEET COOLER COOLER CENTERLINE CENTERLINE 3...

Page 20: ...NSOR CONDENSOR CENTERLINE CENTERLINE END SHEET END SHEET COOLER COOLER CENTERLINE CENTERLINE 76 76 SHELLS CENTERLINE SHELLS CENTERLINE END END SHEET SHEET 51 51 FLOOR LAYOUT FLOOR LAYOUT 76 76 A A UNI...

Page 21: ...GHT 35 010 LBS UP TO 58 349 LBS UNIT WEIGHT 10 000 LBS UP TO 35 009 LBS LD03831 LD03830 CONDENSER CENTERLINE SHELL EVAPORATOR CENTERLINE CAP SCREW ADJUSTING BOLT SHELLS CENTERLINE A A 13 8 8 13 ACOUST...

Page 22: ...TO 26 467 Kgs UNIT WEIGHT 4 536 Kgs UP TO 15 880 Kgs LD03834 LD03835 CONDENSER CENTERLINE SHELL EVAPORATOR CENTERLINE CAP SCREW ADJUSTING BOLT SHELLS CENTERLINE A A 343 mm 343 mm 203 mm 203 mm 13 mm 1...

Page 23: ...assemblies will be furnished with the unit The 4 assemblies are identical and can be placed at any of the 4 corners of the unit While the unit is still suspended by the rigging the isolators should b...

Page 24: ...protect the chiller as well as the pumps tower spray nozzles chilled water coils and controls etc The strainer must be installed in the entering chilled water line directly upstream of the chiller Wa...

Page 25: ...nser water heads and piping for leaks Repair leaks as necessary Before initial operation of the unit both water circuits should be thoroughly vented of all air at the high points REFRIGERANT RELIEF PI...

Page 26: ...amperes must be furnished to the control center from the control transformer 2 KVArequired included with the compressor motor starter DO NOT make final power connections to control center until appro...

Page 27: ...r Variable Speed Drive INSULATION SEE PRODUCT DRAWINGS FORM 160 52 PA1 DONOTfieldinsulateuntiltheunithas been leak tested under the supervision of the YORK representative Insulation of the type specif...

Page 28: ...ww york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2004 ALL RIGHTS RESERVED Form 160 73 N1 904 Supers...

Reviews: