51
Setting External Input/Output Function:
Function
No.
Input
Output
1
Fixed Heating Mode
Operation Signal
2
Fixed Cooling Mode
Alarm Signal
3
Demand Stoppage
Compressor ON Signal
4
Outdoor Fan Motor Start/Stop
Defrost Signal
5
Forced Stoppage
-
6
Demand Current Control 40%
-
7
Demand Current Control 60%
-
8
Demand Current Control 70%
-
9
Demand Current Control 80%
-
10
Demand Current Control 100%
-
11
Low noise setting 1
-
12
Low noise setting 2
-
13
Low noise setting 3
-
0
No Setting
No setting
Same input/output function cannot be set to different input/output terminal. Otherwise, the larger
function number setting will be invalid.
2. Function selection Setting
(1) Function selection Setting Method
1) Setting start
When unit is stopped, set DSW4-No.4 to ON and set DSW4-No.5 to ON.
2) Setting end
Set DSW4-No.5 to OFF and set DSW4-No.4 to OFF.
(2) Function Setting Option
By pressing the push-switches PSW3 (►) and PSW5 (◄) the setting can be changed.
PSW4 (▼): forward, PSW2 (▲): backward
Refer to the Technical Manual for more details.